APC 1609 user manual Connect Power and Equipment to the UPS, Front Panel

Page 3

Front Panel

120 V model depicted.

8 NO

ON

 

7 COM

BATTERY

Test

6 NC

 

 

5 NO

LOW

 

4 COM

BATTERY

 

3 NC

 

 

 

2 EPO COM

 

1 EPO

 

 

PUSH

TO

RESET

INPUT

 

OUTPUT

 

208/220-240V~ 50/60Hz, 7A MAX

230V~ 50/60Hz, 500VA

 

 

325W, 2.7A MAX

 

GROUND NEUTRAL

LINE

GROUND NEUTRAL

LINE

N

L

N

L

Connect Power and Equipment to the UPS

Hardwiring should be performed by a qualified electrician. Use appropriate size wires.

1.The UPS features a transient voltage surge-suppression (TVSS) screw located on the front panel. The TVSS screw is used for connecting the ground lead on surge suppression devices such as telephone and network line protectors.

Prior to connecting the grounding cable, ensure that the UPS is NOT connected to utility or battery power.

2.Hardwire the UPS.

In 230 V applications the UPS must be protected with a circuit breaker that complies with European standards for branch rated protection per the country of installation.

In 208 V applications, the 1609-U500E must be protected by a dual pole, 10 A branch rated circuit breaker with UL489 rating.

The 120 V 1609-U500N has supplementary circuit breaker protection. The unit should be protected by a single pole, 15 A branch rated circuit breaker with a UL489 rating. Allen-Bradley part number 1492-MCAA115 is suggested. Ensure that the branch circuit breaker is off prior to wiring the unit.

120 V

INPUT

 

OUTPUT

208/230 V

INPUT

OUTPUT

models

 

 

 

models

 

 

 

NEUTRAL

LINE

NEUTRAL

LINE

L2/N L1

L2/N L1

 

N

L

N

L

3.Connect equipment to the UPS.

4.Add optional accessories to the SmartSlot located on the front panel.

5.Turn on all connected equipment. To use the UPS as a master on/off switch, be sure all connected equipment is switched on.

6.Press the button on the front panel to start the UPS.

The battery charges to 90% capacity during the first four hours of normal operation.

Do not expect full battery run capability during this initial charge period.

7.For optimal computer system security, install PowerChute monitoring software included with the UPS.

4

Image 3
Contents Industrial Uninterruptible Power Supply Mount the UPS Battery InstallationFront Panel Connect Power and Equipment to the UPSParameter Value ConnectorsUPS Display Panel Display Panel Indicators and Function ButtonsIndicator Indicator Title Description OperationBattery Charge Feature Feature Title Function ButtonUPS settings User Configurable ItemsFunction Factory User Selectable Description Default Choices Storage, Maintenance, Transport Replacing the Battery ModuleStorage Problem and/or Possible Cause Solution TroubleshootingReplace Battery/Battery Disconnected LED is illuminated Input circuit breaker tripsAVR Boost or AVR Trim LEDs are illuminated Diagnostic utility voltage There is no utility powerUPS operates on battery although line voltage exists Battery Charge and Load LEDs flash simultaneouslyService and Contact Information ServiceContact Rockwell Automation Replacement and Recycling of Batteries Safety Information Save this Guide