APC 1609 user manual Storage, Maintenance, Transport, Replacing the Battery Module

Page 9

Storage, Maintenance, Transport

Storage, Maintenance, Transport

Storage

Store the UPS covered in a cool, dry location with the batteries fully charged.

At 5° to 86° F (–15° to 30° C), charge the UPS battery every six months.

At 86° to 113° F (30° to 45° C), charge the UPS battery every three months.

Replacing the Battery Module

This UPS has an easy-to-replace, hot-swappable battery module. Replacement is a safe procedure, isolated from electrical hazards. You may leave the UPS and connected equipment on during the replacement procedure.

Ensure battery replacement every 2-4 years.

Standard (40C) battery; Allen-Bradley catalog number: 1609-500SBAT.

High Temperature (50C) battery; Allen-Bradley catalog number: 1609-500HBAT.

Once the batteries are disconnected the connected equipment is not protected from power outages.

Refer to the appropriate replacement battery installation guide for battery module installation instructions. See your dealer or contact Rockwell Automation at 440-646-5800 for information on replacement battery modules.

Be sure to deliver the spent battery(s) to a recycling facility or ship it to the address specified in the replacement battery literature.

10

Image 9
Contents Industrial Uninterruptible Power Supply Mount the UPS Battery InstallationFront Panel Connect Power and Equipment to the UPSParameter Value ConnectorsIndicator Indicator Title Description Display Panel Indicators and Function ButtonsOperation UPS Display PanelBattery Charge Feature Feature Title Function ButtonUPS settings User Configurable ItemsFunction Factory User Selectable Description Default Choices Storage, Maintenance, Transport Replacing the Battery ModuleStorage Problem and/or Possible Cause Solution TroubleshootingReplace Battery/Battery Disconnected LED is illuminated Input circuit breaker tripsAVR Boost or AVR Trim LEDs are illuminated UPS operates on battery although line voltage exists There is no utility powerBattery Charge and Load LEDs flash simultaneously Diagnostic utility voltageService and Contact Information ServiceContact Rockwell Automation Replacement and Recycling of Batteries Safety Information Save this Guide