2. Installation

Required cable sizes for parallel UPS installations with an external bypass

Rated

Number of

Total rated

Bypass AC

Cable

power of

parallel

power of

input or

size(1)

each UPS

UPS units

the UPS

load line

in mm2

unit

 

 

current

 

 

 

 

 

 

20 kVA

2

40 kVA

58 A

16

 

3

60 kVA

87 A

35

 

4

80 kVA

116 A

50

 

 

 

 

 

30 kVA

2

60 kVA

80 A

25

 

3

90 kVA

129 A

50

 

4

120 kVA

172 A

70

 

 

 

 

 

40 kVA

2

80 kVA

116 A

35

 

3

120 kVA

174 A

70

 

4

160 kVA

232 A

120

 

 

 

 

 

60 kVA

2

120 kVA

174 A

70

 

3

180 kVA

261 A

150

 

4

240 kVA

348 A

185

 

 

 

 

 

80 kVA

2

160 kVA

232 A

120

 

3

240 kVA

348 A

185

 

4

320 kVA

464 A

2 x 120

 

 

 

 

 

100 kVA

2

200 kVA

288 A

150

 

3

300 kVA

432 A

2 x 95

 

4

400 kVA

576 A

2 x 150

 

 

 

 

 

120 kVA

2

240 kVA

348 A

185

 

3

360 kVA

522 A

2 x 150

 

4

480 kVA

696 A

2 x 185

 

 

 

 

 

External bypass

The table opposite is an example for an installation with up to four UPS units.

For installations with redundant units, take into account only the number of units required to supply the loads (e.g. in a three-unit installation where one unit is redundant, only two units count in determining the input and load currents).

This table is valid for 400 V input and load phase-to-phase voltages, at rated load with a power factor of 0.8. For voltages of 380 or 415 V, multiply the current values by 1.05 or 0.96 respectively and, if necessary, modify the cable sizes accordingly.

The cable sizes in this table concern the bold sections in the diagram below.

(1)Cable sizes are determined for U1000 R02V type copper conductors (for aluminium conductors, increase the size by 30%). Size calculations also take into account a voltage of 400 V and grouping of four cables.

Bypass AC

Normal AC

Bypass AC

Bypass AC

 

 

Normal AC

 

Bypass AC

 

Normal AC

GALAXY 5000

1

GALAXY 5000

2

GALAXY 5000

3

Load

34001813EN/AE - Page 16

Image 16
Contents Mgetm GalaxyTM Introduction Safety Safety rulesSafety of persons Product safetyPictograms ForewordDocumentDisplay Contents Assembly and connection of an empty battery cabinet OperationContents Presentation UPS cabinet External battery cabinet / auxiliary cabinetMgetm GalaxyTM Example of version with built-in battery Inside the UPS cabinet, access to connectionsSimplified diagram of power connections Cabinet layout normal or false floor View with terminal-block protection cover removedUser-machine interface Relay communication cardInstallation UPS cabinet Battery cabinetLocation Layout of cabinetsRemoving the cardboard protecting the batteries External battery cabinetUPS Required protective devices and cable sizes Recommended upstream protectionRecommended downstream protection Earth-leakage currentBattery/terminal Required cable sizesMinimum sizes Rating Separate Normal AC Separate Bypass For commonGalaxy TNS upstream and TNS downstream installation 2.5 System earthing arrangementsWith differential circuit breaker Without differential circuit breakerInstallation with upstream IT and downstream TNS TNC upstream, TNS downstreamFrequency converter without Bypass AC input Upstream and downstream Neutral not distributedInstallation Q3BP Q4S Connection of power cables in a single UPS unit Interconnecting the cabinet earthsUPS units with common normal and Bypass AC inputs UPS units with separate normal and Bypass AC inputsConnect the usage cable PEN to the UPS earthing terminal Equipotential bonding between parallel-connected units Connection of power cables for parallel UPS unitsConnection of earth cable and tying of cables This configuration does not have an external bypass To load Normal SourceConnection of the 150 kVA external bypass cabinet KeyConnection of the 360 kVA external bypass cabinet Connection of the 600 kVA external bypass cabinet Exchange-current interconnections Can // interconnectionsExternal bypass cabinet Jumpers connected to Aux. terminal blockExternal bypass cabinet Interconnections with the external bypass cabinetXMB 08 XMB Connection of the relay communications card Characteristics of the output contacts Characteristics of the input contactsCommunications card connection example Adding communication cardsSingle UPS Running the control/communications cablesCable description Insulation level Location on illustration Parallel UPS Assembly and connection of an empty battery cabinet Power connections for an external battery cabinetMounting the battery circuit breaker kit Mounting the shelves and the battery cells Control connections for an external battery cabinet Connection of an input isolating transformer Connection of an output isolating transformerOperation Shutting down a single UPSRestarting a single UPS Load is protected by the UPS 31 32Restarting a parallel configuration Shutting down a parallel configurationLoad is protected by the UPSs Operation of mimic-panel LEDs Single UPS start sequence on Normal AC inputNormal double conversion mode ECO mode single UPS onlyOperating modes Bypass AC source availableLoad on battery power Transfer to battery powerEnd of battery power Access to the personalisation functionsOperating mode BatteryFrequency Automatic bypassOutputs Factory setting Options available on all contacts Inputs Factory setting Options available on all contactsRelay contacts communications card Display functions Welcome screenMaintenance Identification of alarmsLife Cycle Monitoring LCM LED Buzzer SignificationUPS operating in ECO mode UPS isolationFrequency converter If supplied by the network via the Bypass AC channelShutdown and isolation of the first UPS unit Parallel UPS configuration without external bypass cabinetShutdown and isolation of the second UPS unit Shutdown and isolation of one UPS unit Parallel UPS configuration with external bypass cabinetShutdown and isolation of all the UPS units Return to the normal position UPS unit starts automatically LED 31 is onUPS unit starts automatically. LED 31 is on Restart the UPS unit for which all switches are set to OFFUPS restarts and LED 31 is on Parallel UPS configuration with external bypass cabinet Training centres Environment SubstancesPacking End of lifeAvailable options Appendices Technical sheetsCenter of gravity Tip angle to the rearElectrical characteristics Selection of protection devicesUPS unit with common normal and Bypass AC inputs UPS unit with separate normal and Bypass AC inputsInput / output characteristics Line current valuesWithout external bypass cabinet Maximum allowable power for parallel UPS unitsWith external bypass cabinet Thermal characteristics UPS power rating Heat losses Recommended air ThroughputRestrictions to parallel operation Single UPS Parallel UPSGeneral characteristics of Mgetm GalaxyTM 5000 UPSs UPS power in kVA 100 120 Normal AC inputBypass AC input InverterUPS power in kVA 100 120 UPS componentsIP32 installation OptionsUninterruptible Power Supply Glossary

5000 specifications

The APC 5000 series is a comprehensive power protection solution designed for various applications, leveraging advanced technology to ensure reliable performance. Engineered by APC by Schneider Electric, a leader in power management and surge protection, the APC 5000 series is the ideal choice for businesses and home offices alike.

One of the standout features of the APC 5000 is its exceptional power conditioning capabilities. This series includes advanced Automatic Voltage Regulation (AVR) technology, which maintains consistent voltage levels and protects connected devices from power fluctuations and outages. This ensures that sensitive equipment, such as computers and networking hardware, receive stable power for optimal performance.

The APC 5000 series integrates a robust surge protection mechanism that guards against sudden voltage spikes, a common issue in areas prone to electrical disturbances. This protection is crucial for safeguarding devices from potentially damaging surges caused by lightning strikes or power inconsistencies.

Another notable characteristic is the impressive battery backup system. The integrated high-capacity battery provides sufficient runtime during power outages, allowing users to save their work and shut down devices safely. This feature is vital for preventing data loss in critical situations and lends peace of mind for users who rely heavily on electronic equipment.

The UPS (Uninterruptible Power Supply) system in the APC 5000 is equipped with LCD display panels that provide real-time information on power conditions. Users can easily monitor load levels, battery status, and voltage output, which aids in proactive management and enhances overall operational efficiency.

Moreover, the APC 5000 series features multiple output options including USB and serial connectivity, making it compatible with various devices. Its compact design allows for easy integration into different environments, from small office setups to larger enterprise configurations.

In summary, the APC 5000 series is a versatile power protection solution characterized by its AVR technology, robust surge protection, reliable battery backup, real-time monitoring features, and compatibility with multiple devices. Whether for business or personal use, the APC 5000 series stands out as a reliable partner in ensuring uninterrupted power and protecting valuable electronic equipment.