APC 3000 installation manual System-Electrical Information, UPS ratings

Page 37

System-Electrical Information

WARNING!

All electrical power and power control wiring must be installed by a qualified electrician, and must comply with local and national regulations for maximum power rating.

UPS ratings

10 kVA

15 kVA

20kVA

30 kVA

8 kW

12 kW

16 kW

24 kW

 

 

 

 

 

 

Input voltage / Bypass voltage (V)

3-phase

3-phase

3phase

3-phase

 

208Y/

208Y/

208Y/

208Y/

 

120V

120V

120V

120V

 

 

 

 

 

Input current (nominal, per phase) (A)

24.6

36.9

49.3

73.9

 

 

 

 

 

Maximum input current per phase (continuous, at

27.1

40.6

54.2

81.3

minimum mains voltage)

 

 

 

 

 

 

 

 

 

Input current protection for mains source or single

3x35

3x60

3x80

3x125

mains supply (external to UPS, not supplied) (A)

 

 

 

 

 

 

 

 

 

Input current protection for bypass source in dual mains

35

60

80

125

configuration (external to UPS, not supplied) (A)

 

 

 

 

 

 

 

 

 

Input frequency (Hz) range

40-70

40-70

40-70

40-70

 

 

 

 

 

Output voltage (on line). (V)

120/208

120/208

120/208

120/208

Minimum and maximum values (+/- 1%)

 

 

 

 

 

 

 

 

 

Output current (nominal, per phase) (A)

27.8

43.3

55.5

83.3

 

 

 

 

 

Maximum output current

30.5

45.8

51.1

91.6

(in bypass only at 110% overload per phase)

 

 

 

 

 

 

 

 

 

Bypass input current (A)

30.5

45.8

51.1

91.6

(in bypass only at 110% overload, per phase)

 

 

 

 

 

 

 

 

 

Neutral output current (with 100% switch mode load)

48.1

74.9

96.0

144.1

(A)

 

 

 

 

 

 

 

 

 

Output current protection (external to UPS, not

40

60

80

125

supplied) (A)

 

 

 

 

 

 

 

 

 

Output frequency range (Hz)

50/60

50/60

50/60

50/60

 

 

 

 

 

DC overcurrent protection and disconnect switch for

23

35

46

69

external safety:

 

 

 

 

DC voltage rating of the battery supply

+/- 192

+/- 192

+/- 192

+/- 192

Maximum available short-circuit current

10 kA

10 kA

10 kA

10 kA

 

 

 

 

 

AIS® 3000 10-30kVA, 208V, Site Preparation and Installation Manual – 990-1957

29

Image 37
Contents AIS Page AIS 3000 10-30kVA Page Contents Electrical Installation General Charge Setting Page Introduction Environmental symbols General Safety Instructions13.85in/352mm Enclosures UPS Family Range and Components20.59in/523mm Enclosures Part number coding V T 1 0 K F 1 B 2 SConduit Box Battery ModuleFront Panel overview Stabilizing Bracket User interface Options XR Enclosure weightsBattery Module weight Part Number for Battery ModuleBattery Module Part Numbers for XR EnclosuresFloor anchoring and battery securing equipment Clearance for 20.59in/523mm Enclosures Installation Space RequirementsSpace requirements Site Preparation UPS and XR Installation Space Requirements Clearance for stand-alone 13.85in/352mm Enclosures Space requirements Drilling floor holes for floor anchoring Floor Anchoring PreparationHole positions for floor anchors stand-alone Enclosures Site Preparation UPS and XR Floor Anchoring Preparation Operating conditions Operating EnvironmentHeat dissipation Audible noiseRecommended source connections Dual/single Recommended current protectionMinimum setting of breakers for 15kVA UPS Minimum setting of breakers for 10kVA UPSOverload Mains input Bypass input Output Duration Event Minimum setting of breakers for 30kVA UPS Minimum setting of breakers for 20kVA UPSEPO switch wiring Basic Wiring Overview System components. Have you Site Preparation ChecklistRemoval Front PanelInstallation Total-Power-Off Procedure Electrical Installation Total-Power-Off Procedure UPS ratings System-Electrical InformationSource connections Wiring Wiring procedure single mains Input/Output Wiring Single Mains defaultCables Output Wiring procedure dual mains Input/Output Wiring Dual MainsElectrical Installation Input/Output Wiring Dual Mains Communication Wiring to EPO and Optional Equipment Pin connections J106 UPS to J200 XR Enclosure option Pin connections J106 XR Enclosure and J108 EPOXR Enclosure, APC MBP, and Generator Control wiring Pin connections J108 for EPO wiring options Charge setting procedure General Charge SettingLeveling Feet Setting the leveling feetFloor anchoring of stand-alone systems Floor Anchoring optionBattery securing Bypass Input for dual mains installations Wiring Verification ProcedureElectrical Installation Wiring Verification Procedure Installation Site Checklist APC product covered Terms of warrantyAssignment of warranties Drawings, descriptions Warranty claims procedureExclusions Electrical Installation Limited Factory Warranty 990-1957
Related manuals
Manual 8 pages 29.77 Kb Manual 21 pages 12.14 Kb Manual 2 pages 10.71 Kb

3000 specifications

The APC 3000 and 4000 series are advanced uninterruptible power supply (UPS) systems designed to provide reliable and efficient power protection for a variety of applications. These systems play a crucial role in safeguarding sensitive electronic equipment from power disturbances, including surges, sags, and complete power outages.

Both the APC 3000 and 4000 models come equipped with a robust set of features engineered to improve performance and optimize energy efficiency. One notable characteristic is their sine wave output, which ensures smooth and dependable power delivery, essential for maintaining the proper functionality of connected devices.

Key technologies integrated into these models include advanced battery management systems that extend the life of the batteries and enhance overall performance. The UPS units utilize high-frequency technology, which minimizes the size and weight of the system while maximizing output power. This enables both the APC 3000 and 4000 to fit seamlessly into various environments, from data centers to small offices.

In addition to their compact design, the APC 3000 and 4000 series feature easy-to-read LCD displays providing real-time information on critical parameters such as battery status, load level, and remaining runtime. This feature allows users to monitor performance and make informed decisions about power management effortlessly.

Another vital aspect of the APC 3000 and 4000 series is their expansion capabilities. Both models offer additional battery packs, allowing users to increase runtime as needed. These UPS systems also support hot-swappable batteries, making maintenance quick and efficient, minimizing downtime during service and repairs.

Furthermore, APC’s PowerChute software is compatible with the 3000 and 4000 series, allowing for easy management of power settings and the ability to configure user-defined power settings. This software also enables users to receive alerts for system status issues and performs scheduled shutdowns, ensuring data integrity during power failures.

Overall, the APC 3000 and 4000 series offer a combination of performance, reliability, and user-friendliness. These UPS systems are ideal choices for protecting critical electronic equipment and ensuring uninterrupted operations in various environments. Users looking for a dependable power solution will find that these models exceed expectations with their advanced features and robust technologies.