APC 480kW 400V manual Stop/Start UPS and Operating the External Service Bypass

Page 18

Stop/Start UPS and Operating the External Service Bypass

2.7.2 Switching Back the UPS to Normal Rarallel/Redundant Operation

Action

1.Set the input switch (Q001) and the output switch (Q002) to position 1.

2.Charge capacitors, connect battery, and start up the UPS as described in 2.4.1. Start UPS (from complete power down).

The UPS will automatically switch to normal operation and start load-sharing with the other parallelled UPS(s).

WARNING!

The system will discharge built-in capacitors.

ALWAYS check with a multimeter that the terminals contain no dangerous voltage before touching the system!

NOTICE!

With Q002 in position 0, the UPS can be operated and tested as a single system without affecting the other parallel UPS(s) if correct monitoring device has been installed. Applicable to all bypass panels.

990-4041

18

User Guide APC Silcon 480kW 400V UPS

Image 18
Contents 480kW 400V UPS User Guide Copyright 2000 APC Denmark ApSSafety Symbols used in this manual User Guide APC Silcon 480kW 400V UPSThank You Contents Introduction IntroductionDisplay Unit Stop UPS for stand-by Stop/Start UPS and Operating the External Service BypassNormal operation Load power xx% Start UPS from stand-byStop UPS for complete power down Switching off the UPSBlank Start UPS from complete power down UPS start-upSystem OFF Normal operation load power XX% Display showsOperating the External Service Bypass Switch single systems Bypassing the Single System UPSBypass operation Stop/Start UPS and Operating the External Service Bypass System OFF Normal operation Load power 0% Bypass operation Bypass operation Normal operation Load power 0%Bypassing the Parallel UPS System All UPSs Acoustic alarm sounds for 30 secs Stop/Start UPS and Operating the External Service Bypass Set input switches Q001 to position Press the green on button on all systemsPress On the keyboard Isolating one UPS in a Parallel/Redundant System Stop/Start UPS and Operating the External Service Bypass Operation OperationKeyboard Using the Remote Display Display of Measured ValuesBatt. load Batt. tank Economy Mode Parameter Settings Parameter SettingsParameter Settings Switching to Bypass Operation Programming KeysProgramming Example Load power xx% Displaying the Alarm Stack Alarms and EventsAlarms and Events Mode CommentsPossible Alarms Alarms Description ActionDisplay will show invalid UPS data Rectifying Alarm Messages Parallel Operation AlarmsCorrection of false alarm situations during service Battery Monitoring Test Maintenance & TestingMaintenance & Testing Battery Capacity TestTest Xxx Press Battery capacity TestUntil Test PressWarranty WarrantyAPC Silcon UPS Limited Factory Warranty APC Corporate How to Contact APCHow to Contact APC APC Denmark