Limitorque MX DeviceNet Field Unit FCD
5.2EDS File
The DeviceNet Limitorque Interface can be configured using Rockwell Automation RSNetWorx for DeviceNet and an
Table 5.1 Parameter List
Parameter | Access | Path to Object | |
No. | |||
|
| ||
Read/Write resp. Read Only | Channel Interface Object, Instance Attributes | ||
Read/Write resp. Read Only | Transducer Block Object, Instance Attributes | ||
79 | Read/Write | DeviceNet Object, Instance Attribute ‘MAC ID’ | |
80 | Read/Write | DeviceNet Object, Instance Attribute ‘Baud Rate’ | |
81 | Read | DeviceNet Object, Instance Attribute ‘MAC ID | |
|
| Switch Changed’ | |
83 | Read | DeviceNet Object, Instance Attribute ‘MAC ID | |
|
| Switch Value’ | |
85 | Read/Write | DeviceNet Object, Instance Attribute ‘Autobaud’ | |
86 | Read/Write | Connection Object, Poll Instance Attribute ‘Polled | |
|
| I/O Input’ | |
87 | Read/Write | Connection Object, Poll Instance Attribute ‘Polled | |
|
| I/O Output’ | |
88 | Read/Write | Connection Object, | |
|
| ||
89 | Read/Write | Connection Object, COS/Cyclic Instance Attribute | |
|
| ‘COS/Cyclic I/O Input’ |
6 Associated Documents
Quick
MX Installation and Operation Manual: Limitorque Bulletin LMAIM1306/2306
Protection, Control and Monitoring Features of MX Electric Actuators: Limitorque Bulletin LMABR1300/2300
MX Maintenance and Spare Parts Manual: Limitorque Bulletin LMAIM1314/2314 ODVA Planning and Installation Manual available from ODVA.
7 Troubleshooting
Refer to Section 10, Wiring Diagram.
1.With power off and network disconnected, verify continuity between A1, A2 and A1*, A2*.
2.With power applied and network disconnected, verify 0.2 to 0.45 VDC between A1, A1* and A2, A2*.
3.Confirm that a jumper cable is installed between the grounding lug and terminal 30.
Verify proper setup for MX DeviceNet.
4. MPC (modulating position control) must be OFF.
5.ESD must be configured for desired function and properly wired.
6.OPEN INHIBIT must be configured for desired function and properly wired.