Limitorque MX DeviceNet Field Unit  FCD LMENIM2328-00 – 11/05

The Device Heartbeat Message is triggered by the Identity Object Instance Attribute Heartbeat Interval (Attribute ID 10). For this, the Heartbeat Interval has to be set to the time interval of the Device Heartbeat Message in seconds.

4.5.1Device Shutdown Message

The DeviceNet Limitorque Interface supports the Device Shutdown Message. The DeviceNet Limitorque Interface produces this message when it transitions to the offline state. Table 4.43 shows the format of the data field of the Device Shutdown in Message.

Table 4.43 – Format of the Device Shutdown Message

Byte

7

6

5

4

3

2

1

0

Offset

 

 

 

 

 

 

 

 

0DeviceNet Protocol Specific

2Class ID

4Instance ID

6Shutdown Code

7Range 200hex – 2FFhex

For the DeviceNet Limitorque Interface, the Class ID and the Instance ID of this message depends on the originator of the Device Shutdown Message, e.g. after Reset-Service performed on the Identity Object, Class ID 1 and Instance 1, a Device Shutdown Message is sent.

For application purposes 2 Bytes of the Device Shutdown Message are reserved for the Shutdown Code. Then vendor specific range of this code is 200 – 2FF. Table 4.44 lists all Shutdown Codes of the DeviceNet Limitorque Interface.

Table 4.44 – Device Shutdown Codes

Class ID

Instance ID

Shutdown

Causes of Shutdown

Code

 

 

 

1

1

4

Remote Reset: Reset service of the identity Object

 

 

 

 

3

1

4

Remote reset: Setting of the MAC ID via Attribute 1 of the DeviceNet

 

 

 

Object

0

0

5

Internal diagnostic fault: An internal diagnostic fault has caused the

 

 

 

service to shut down. Reason for this can be an overrun of the CAN

 

 

 

transmit queue, CAN receive queue or CAN Controller receive buffer

0

0

4

DeviceNet Limitorque Interface will be reset because SMT Main Board

 

 

 

signal RESET is active.

102

1

0x201

DeviceNet Limitorque Interface will be reset because SMT Main Board

 

 

 

has changed MAC ID via LCD

102

1

0x202

DeviceNet Limitorque Interface will be reset because SMT Main Board

 

 

 

has changed Baud rate via LCD

4.6Configuration Confirmation

DNFU operation cannot be verified until the complete DeviceNet system is operational. However, routine checks can be performed to verify many functions.

4.6.1Checking Connections

Verify that all connections, including data wires, shield ground, are in accordance with MX wiring diagrams and DNFU diagrams in Section 3.1.2, Network Cable Preparation.