Limitorque MX DeviceNet Field Unit  FCD LMENIM2328-00 – 11/05

Table 1.1 – Network specifications

Network Size

Up to 63 Nodes

 

 

Network Length

Selectable end-to-end network distance varies with speed

 

125 Kbps 500 m (1,640 ft)

 

250 Kbps 250 m (820 ft)

 

500 Kbps 100 m (328 ft)

Bus Topology

Linear (trunkline/dropline); power and signal on the same network cable

Bus Addressing

Multi-Master and Master/Slave special case; polled of change-of-state

 

(exception-based)

System Features

Selectable end-to-end network distance varies with speed

Termination resistor (121 ohms) must be used at each end of the network

1.5.1.2MX Field Unit Specifications

CIP Generic Device Profile (Device Type = 00hex) extended to DNFU requirements

Group 2 Server

UCMM capable device

Predefined Master/Slave Connection Set supporting

Explicit Connection

Polled I/O Connection

Bit-Strobed I/O Connection

Change of State / Cyclic I/O Connection

Full support of fragmentation protocol

Device Heartbeat Message

Device Shutdown Message

Offline Connection Set

Galvanical Isolation: The isolation voltage for the DNFU is up to 1,500 VRMS for 1 minute (1,800 VRMS for 1 second

Power Supply: The DNFU Interface will be powered from the DeviceNet bus. A switching regulator is

used to generate the internal supply voltage: VCC nominal 5.0 V ± 5 %

Surge Suppression: The DNFU Interface is equipped with surge suppression for the DeviceNet network data and power lines. Surge suppression is compliant with IEC 61000-6-2:2001.

Environmental conditions

The DNFU environmental parameters are within the same environmental constraints as the actuator.



flowserve.com

Page 9
Image 9
Thomas & Betts Limitorque MX Device Net Field Unit manual Network specifications, MX Field Unit Specifications