Thomas & Betts Limitorque MX Device Net Field Unit Transducer Attribute Scaled values attribute

Models: Limitorque MX Device Net Field Unit

1 44
Download 44 pages 36.73 Kb
Page 28
Image 28

Limitorque MX DeviceNet Field Unit  FCD LMENIM2328-00 – 11/05

Table 4.32 – Continued

Attribute ID

Access Rule

Name

Data Type

Description

Semantics of Value

41

RW

Valve_Type

USINT

Type of valve

0

= linear moving

 

 

 

 

 

valve, sliding valve

 

 

 

 

 

(Default) 1 = rotary

 

 

 

 

 

moving valve, part-

 

 

 

 

 

turn 2 = rotary moving

 

 

 

 

 

valve, multi-turn

42

RO

Actuator_Type

USINT

Type of actuator

0

= electropneumatic

 

 

 

 

 

1

= electric (default)

 

 

 

 

 

2

= electrohydraulic 3

 

 

 

 

 

= others

43

RO

Diagnostic_ Values_0

UINT

Reserved

Engineering Use

44

RO

Diagnostic_ Values_1

UINT

Main Voltage

Engineering Use

45

RO

Diagnostic_ Values_2

UINT

Actuator Position

Engineering Use

46

 

Diagnostic_ Values_3

UINT

Analog input #1

Engineering Use

47

 

Diagnostic_ Values_4

UINT

Analog Input #2

Engineering Use

48

RW

Tag_Name

SHORT-

Tag name for

String length is limited

 

 

 

STRING

generic use

to 32 char. Default = 0

 

 

 

 

 

(empty)

49

Get/Set

Comm_Loss_

USINT

Actuator action

0

= No Action

 

(NV-RW)

Action

 

upon detection of

(Default)

 

 

 

 

communication loss

1

= Open

 

 

 

 

 

2

= Close

 

 

 

 

 

3

= Stop

 

 

 

 

 

4

= Preset Position

50

Get/Set

Comm_Loss_

UINT

Position to take

Range = 0 – 1000

 

(NV-RW)

Position

 

upon a communica-

Default = 0

 

 

 

 

tion loss

 

 

51

Get/Set

Comm_Loss_

UINT

Time to wait

Range = 0 – 4095

 

(NV-RW)

Timeout

 

after detection of

Default = 255

 

 

 

 

communication loss

 

 

 

 

until actuator action

 

 

 

 

 

 

is taken

 

 

52

Get/Set

Deadband

UINT

Deadband

Range = 0 – 1000

 

(NV-RW)

 

 

percentage to use

Default = 2

 

 

 

 

when positioning

 

 

 

 

 

 

53

Get/Set

Proportional_

UINT

Proportional band

Range = 0 – 1000

 

(NV-RW)

Band

 

percentage to use

Default = 8

 

 

 

 

when positioning

 

 

 

 

 

 

54

Get/Set

TQ_Switch_

USINT

Percentage of full

Range = 0 – 100 %

 

(NV-RW)

Adjust

 

torque to limit

Default = 0 (Disabled)

 

 

 

 

operation to

 

 

 

 

 

 

55

RW

Actuator_Control_

USINT

Configure actuator

1

= Analog

 

 

Mode

 

for open/close

(Positioning Mode)

 

 

 

 

or positioning

2

= Digital (Open/

 

 

 

 

operation

 

 

 

 

Close Mode)

 

 

 

 

 

 

 

 

 

 

Default = 2

NOTE: Attributes 49-55 are reserved for Revision 1 to DeviceNet.

Table 4.33 – Transducer Attribute – Scaled values attribute 3

Bit 7 - 5

Unused

28

Bit 4

DDC Offset 0 = 0 mA 1 = 4 mA

Bit 3

 

Bit 2

ATT Polarity

 

Analog

 

0 = high

 

Torque

value 4 mA

 

Transmitter

1 = high

 

(ATT) 0

value 20 mA

 

= ATT

 

 

Disabled 1 =

 

 

ATT Enabled

Bit 1

APT Polarity 0 = high value 4 mA 1 = high value 20 mA

Bit 0

Analog

Position Transmitter (APT) 0

=APT Disabled 1 = APT Enabled

Page 28
Image 28
Thomas & Betts Limitorque MX Device Net Field Unit manual Transducer Attribute Scaled values attribute, Bit 7