Limitorque MX DeviceNet Field Unit  FCD LMENIM2328-00 – 11/05

FailedTests

DeviceNet Limitorque Interface

One or more of the following errors have been

 

 

detected during self-test of the DeviceNet

 

 

Limitorque Interface e.g.

 

 

- FLASH Checksum Error

 

 

- RAM Memory Test Error

Activated

SMT Main Board

Is_Active-Flag is TRUE

 

 

 

Deactivated

SMT Main Board

Is_Active-Flag is FALSE OR

 

 

EEPROM Checksum Error

Minor Fault

SMT Main Board

Conditions that can cause this event are e.g.

 

 

valve jam, overtemp, overtorque and phase loss.

 

 

This event is triggered if Attribute DI_Actuator_

 

 

Faults_1_Chan in Channel Object Class is ≠

 

 

0x00

Major Recoverable Fault

SMT Main Board

Conditions that can cause this event are e.g.

 

 

communication fault, power fault or Limiguard

 

 

fault of the SMT Main Board.

 

 

This event is triggered if Attribute DI_Actuator_

 

 

Faults_3_Chan in Channel Object Class is ≠

 

 

0x00

Major Unrecoverable Fault

DeviceNet Limitorque Interface

Internal Diagnostic Fault detected e.g.

 

 

- Receive Queue Overrun

 

 

- Transmit Queue Overrun

 

 

- CAN Controller Overrun

4.4.3DeviceNet Object Instance Attributes

Table 4.37 – DeviceNet Object Instance Attributes

Attribute 

Access Rule

Name

Data

 

Description of

 

Semantics of Value

ID

Type

Attribute

 

 

 

 

 

 

 

1

Get/Set

MAC ID

USINT

Node Address

 

Range 0 – 63

 

(NV-RW)

 

 

 

 

 

 

see also

 

 

 

 

 

 

 

 

 

Chapter 5.2.1

 

2

Get/Set

Baud Rate

USINT

Baud Rate

 

Range 0 – 2

 

(NV-RW)

 

 

 

 

 

 

 

 

 

3

Get/Set

BOI

BOOL

Bus-Off Interrupt

 

 

 

 

 

(V-RW)

 

 

 

 

 

 

 

 

 

4

Get/Set

Bus-Off Counter

USINT

Number of times

 

 

 

 

 

(V-RW)

 

 

CAN went to the

 

 

 

 

 

 

 

 

bus-off state

 

 

 

 

5

Get

Allocation Information

STRUCT

 

 

 

 

 

 

 

 

(V-RO)

 

of

 

 

 

 

 

 

 

 

 

Allocation Choice Byte

BYTE

 

See [2] Chapter 3-5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Master’s MAC ID

USINT

MAC ID of Master

 

 

 

 

 

 

 

 

(from allocate)

 

 

 

 

6

Get

MAC ID Switch Changed

BOOL

The Node Address

 

0 = No Change

 

(V-RO)

 

 

Switch(es) have

 

1 = Change since

 

 

 

 

changed since last

 

last power-up

 

 

 

 

power-up/reset

 

or reset

 

7

Get

Baud Rate Switch Changed

BOOL

The Baud Rate

 

0 = No Change

 

(V-RO)

 

 

Switch(es) have

 

1 = Change since

 

 

 

 

changed since last

 

last power-up

 

 

 

 

power-up/reset

 

or reset

 

8

Get

MAC ID Switch Value

USINT

Actual Value of

 

Range 0 – 99

 

(NV-RW)

 

 

Node Address

 

 

 

 

 

 

 

 

Switch(es)

 

 

 

 

9

Get

Baud Rate Switch Value

USINT

Actual Value of

 

Range 0 – 9

 

(NV-RW)

 

 

Baud Rate

 

31

 

 

 

 

Switch(es)

100

Get/Set

Autobaud

BOOL

Enable/Disable

 

0 = Disable

 

(NV/RW)

 

 

Autobaud Detection

 

1 = Enable (default)

 

flowserve.com

Page 31
Image 31