4.2.1DI_Position_and_Bus_Mode_Chan

Table 4.12

Value

Definition

0x21

Remote + Opened

0x22

Remote + Closed

 

 

0x24

Remote + Opening

 

 

0x28

Remote + Closing

 

 

0x30

Remote + Stop

 

 

0x41

Local + Opened

 

 

0x42

Local + Closed

 

 

0x44

Local + Opening

 

 

0x48

Local + Closing

 

 

0x50

Local + Stop

 

 

0x81

Stop + Opened

 

 

0x82

Stop + Closed

 

 

0x84

Stop + Opening

 

 

0x88

Stop + Closing

 

 

0x90

Stop + Stop

 

 

4.2.2DI_Position_Chan

Table 4.13

Bit 7

 

Bit 6

 

Bit 5

Reserved

 

Reserved

 

Reserved

 

 

 

 

 

 

 

Bit 4

Stop

Bit 3

Closing

Bit 2

Opening

Bit 1

Closed

Bit 0

Opened

Table 4.14 – Possible values of DI_Position_Chan

Value

Definition

0x01

Opened

0x02

Closed

0x04

Opening

0x08

Closing

0x10

Stop

4.2.3DI_Actuator_Faults_1_Chan

Table 4.15

Bit 7

 

Bit 6

 

Bit 5

 

Bit 4

Reserved

 

Reserved

 

Motor Over

 

Phase Error

 

 

 

 

 

 

 

Temp

 

 

 

 

 

 

 

 

 

Bit 3

Over Torque

Bit 2

Manual Moved

Bit 1

Valve Jammed

Bit 0

Monitor

Relay

21