Limitorque MX DeviceNet Field Unit FCD
10 | Wiring Diagram |
|
|
|
|
|
| |||
Figure 10.1 – Typical MX DeviceNet wiring diagram |
|
|
| |||||||
|
|
|
|
|
| PE |
| NOTES |
|
|
|
|
|
|
|
| L1 | 3 PHASE |
|
| |
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
| L2 | 1.FUSES |
|
| |
|
|
|
|
|
| SUPPLY |
|
| ||
|
|
|
|
|
| L3 |
| FSI (PRIMARY) | 600V AC, 1A, 200kA Int RATING, |
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
| 5 |
| FS2 (PRIMARY) | FAST ACTING 10.3 x 38.1mm TUBE. | |
|
|
|
|
| CLOSE |
|
|
| ||
MOTOR | REVERSING |
|
| STOP | 6 |
| FS3 (SECONDARY) - 0.1A, 250V, TIME DELAY, |
| ||
| CONTACTOR |
|
| OPEN | 7 |
| 5 x 20mm, GLASS TUBE |
| ||
|
|
|
|
|
| 2.AUXILIARY INPUT |
|
| ||
|
|
|
| DIG COM | 8 |
|
|
| ||
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
| ||
|
|
| REMOTE |
| INPUT 2 | 9 |
| TO TERMINAL'S 37 AND 38. MAXIMUM CURRENT |
| |
|
|
| INPUTS |
|
| DRAW IS 1 AMP. THIS POWERS ALL CONTROLS FOR |
| |||
|
|
|
|
|
|
|
| |||
| FS1 | FS2 | SEE NOTE 4 |
| INPUT 1 | 10 |
| LOCAL INDICATION AND CONFIGURATION. ANALOG OUTPUT AND ALARM | ||
|
|
|
|
|
| RELAYS SUPPLIED WILL BE POWERED FOR UNITS MANUFACTURED | ||||
|
|
|
| DIG COM | 51 |
| SUBSEQUENT TO Q1/2003. REVERSING CONTACTOR WILL NOT |
| ||
|
|
|
|
| BE POWERED. CUSTOMER SHOULD SUPPLY EXTERNAL FUSE AS |
| ||||
|
|
|
|
|
| 21 |
| REQUIRED BY LOCAL ELECTRICAL CODES. |
| |
|
|
|
|
| INPUT 0 |
|
|
|
| |
|
|
|
| DIG COM | 52 |
| 3.MAXIMUM EXTERNAL LOAD |
| ||
|
|
|
|
|
|
|
|
| ||
|
| FS3 |
|
| 0V AC | 11 |
| TERMINALS 13 AND 14 (24V DC) - 10W MAX. EXT. LOAD |
| |
|
|
| 110V AC | 12 |
| TERMINALS 11 AND 12 (110V AC) - 0V MAX EXT. LOAD |
| |||
|
|
|
|
| SUITABLE FOR DIGITAL INPUTS |
| ||||
|
|
|
|
|
|
| ||||
|
|
| CONTROL | 24V DC +Ve | 13 |
| ONLY, PROTECTED BY FS3. |
| ||
|
|
| SUPPLY |
| 0V DC | 14 |
| 4.REMOTE INPUTS |
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
| |
|
|
| AUXILIARY INPUT | 24V DC +Ve | 38 |
| SIGNAL THRESHOLD - MINIMUM "ON" 19.2V AC/DC |
| ||
|
|
| 37 |
|
| MAXIMUM "OFF" 5.0V AC/DC |
| |||
LIMIGARD |
|
| SEE NOTE 2 |
| 0V DC |
|
| MAX LOAD - 10 mA / 110V AC |
| |
|
|
|
|
|
|
|
| 2 mA / 24V DC | ||
|
|
|
| DEFAULT SETTING |
|
| INPUTS 0,1,2 ARE FIELD CONFIGURABLE (FIRMWARE VERSION 04\08.00 OR LATER) | |||
|
| STATUS FEEDBACK |
|
| FOR CLOSE INHIBIT, OPEN INHIBIT, CLOSE/OPEN INHIBIT, USER INPUT, OR ESD. IN | |||||
|
|
|
| 1 |
| ADDITION, INPUT 2 MAY BE CONFIGURED FOR CSE REMOTE SELECTED INDICATION. | ||||
|
| OUTPUT SWITCHES |
| AS1 |
| |||||
|
| SEE NOTE 6 AND 9 | "CLOSE" |
|
| DEFAULT INPUT CONFIGURATION: INPUT 0 - ESD, INPUT 1 - OPEN INHIBIT, INPUT 2 - | ||||
|
|
| 2 |
| CLOSE INHIBIT |
|
| |||
|
|
|
| POSITION |
|
|
|
| ||
|
|
|
|
|
| SEE INSTALLATION AND OPERATION MANUAL FOR CONFIGURATION PROCEDURES. | ||||
|
|
|
|
|
|
|
| |||
|
|
|
|
|
| 3 |
|
|
|
|
| POSITION |
| TORQUE | "OPEN" | AS2 |
|
|
|
|
|
| SENSOR |
| SENSOR |
| 4 |
|
|
|
| |
|
| POSITION |
|
| 5.CONTROL SIGNAL DURATION |
| ||||
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
| 31 |
| REQUIRED CONTROL SIGNAL |
| |
|
|
|
| "CLOSE" | AS3 |
|
| DURATION = 250 - 350ms. |
|
|
|
|
|
| POSITION |
| 32 |
| 6.STATUS FEEDBACK OUTPUT SWITCHES |
| |
|
|
|
|
|
| 42 |
|
| ||
|
|
|
|
|
|
|
|
|
| |
|
|
|
| "OPEN" | AS4 |
|
| THE ACTUATOR STATUS CONTACTS (AS) AND ALARM RELAYS (AR) | ||
|
| 0% OPEN |
| POSITION |
| 43 |
| MAY BE INDIVIDUALLY CONFIGURED AS NORMALLY OPEN OR NORMALLY | ||
|
| STATUS OK | (YES) |
|
|
|
| CLOSED LATCHED CONTACTS OR AS BLINKER CONTACTS TO INDICATE | ||
| REMOTE |
| OPEN |
|
|
|
| ONE OF THE FUNCTIONS LISTED BELOW: |
| |
|
|
|
| MONITOR RELAY |
|
|
| |||
| S |
|
|
|
|
|
|
| ||
| T |
|
|
|
| 17 |
| CLOSE | LOCAL STOP/OFF | CLOSE INHIBIT |
| O |
|
| SHOWN |
| |||||
| P |
|
| 18 |
| CLOSING | MANUAL OVERRIDE | OPEN INHIBIT | ||
|
|
|
| WITH POWER |
|
| ||||
| LOCAL |
| CLOSE | SUPPLY OFF |
| 19 |
| REMOTE SELECTED | ESD SIGNAL | |
|
|
| (NO) | ANALOG INPUT |
|
| OPENING | VALVE JAMMED | NO ANALOG SIGNAL | |
|
|
|
|
|
| |||||
|
|
|
| +ve ANALOG | 39 |
| OPEN | MOTOR OVERTEMP | LOST PHASE | |
|
|
|
|
| STOPPED | |||||
|
|
|
| (MODUTRONIC) |
|
| OVERTORQUE | LIMIGARD ACTIVE | ||
|
|
|
| 28 |
| VALVE MOVING | ||||
|
|
|
|
| OPEN TORQUE SW | HARDWARE FAILURE | ||||
| CONTROL PANEL |
|
| LOCAL SELECTED | ||||||
|
|
|
| 40 |
| CLOSE TORQUE SW |
| |||
|
| +ve ANALOG |
|
|
| |||||
|
|
|
|
|
|
|
| |||
CIRCUIT SHOWN WITH VALVE IN FULLY CLOSED POSITION AND WITH POWER OFF |
|
|
| 7.CONTACT RATINGS |
|
| ||||
|
|
| AS1,2,3 AND 4 - 5.0 AMPS AT 125V AC, 30V DC (250V |
| ||||||
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| MONITOR RELAY - 5.0 AMPS AT 250V AC, 30V DC |
|
SHIELD | 48 | 8.EXACT END POSITION INDICATION |
DEVICENET |
| NETWORK DATA |
|
|
| 15 | BLU |
|
|
| ON |
| ||||||
|
|
|
|
|
|
|
|
| 16 |
|
|
|
| CONTACTS, CONFIGURED AS END OF TRAVEL LIMITS, | ||||
BOARD |
| NETWORK DATA (+) |
|
|
| WHT |
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
| 29 |
|
| SEE NOTE 11 | AUTOMATICALLY PROVIDE EXACT END OF POSITION | ||||
|
|
|
| NETWORK 0V |
|
| BLK |
|
| INDICATION. |
|
|
| |||||
|
|
|
|
|
|
|
|
|
| 41 |
|
|
|
|
|
|
| |
|
|
| NETWORK +24V |
|
| RED |
|
|
| 9.DEFAULT SETTING |
|
| ||||||
|
|
|
|
|
|
|
|
|
| 30 |
|
|
|
|
| |||
|
|
|
|
|
|
| EGND |
|
|
|
|
|
| ACTUATORS ARE NORMALLY SHIPPED WITH DEFAULT | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| SETTINGS AS SHOWN ON THIS DIAGRAM. THE "AS" | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| CONTACTS ARE SHOWN WITH VALVE IN FULLY CLOSED | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| POSITION. SEE CONTACT DEVELOPMENT BELOW. | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| OUTPUT SWITCH CONTACT DEVELOPMENT | |||
|
|
|
|
|
|
|
|
|
|
| TRANSFORMER TAPPING OPTIONS |
|
| VALVE POSITION |
| |||
|
|
| 2 | 4 | 5 |
|
|
|
|
| TYPE | TAPPING | TYPE | TAPPING | OUTPUT | FULL | FULL | FUNCTION |
|
|
|
|
|
|
|
|
|
|
|
|
|
| SWITCH | CLOSE | OPEN | ||
| 1 7 |
|
|
| 1 |
| 5 0 |
|
|
| A | 220V | B | 115V |
| |||
| 3 1 | 4 3 |
|
|
|
|
| AS1 |
|
| CLOSE LIMIT | |||||||
|
|
|
|
|
|
|
|
| 3 0 |
|
| 380V |
| 220V |
|
| ||
1 |
|
|
|
| 5 |
| 4 9 | 4 1 |
|
|
| AS2 |
|
| OPEN LIMIT | |||
1 8 | 3 2 |
|
|
|
|
| 415V |
| 525V |
|
| |||||||
|
|
| 4 4 | 2 |
|
|
|
|
|
|
| AS3 |
|
| CLOSE LIMIT | |||
2 |
|
|
|
|
|
|
| 4 0 | 2 9 | 1 6 |
| 460V |
| 575V | AS4 |
|
| OPEN LIMIT |
1 9 | 3 3 | 4 5 |
|
| 4 8 |
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
| 4 | 4 |
|
| 2 8 | 1 5 |
|
|
|
|
|
|
|
|
3 | 2 0 | 3 4 |
|
| 6 | 7 |
| 3 9 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 10.ANALOG INPUT |
|
| |||||
|
|
| 3 |
| 3 | 3 | 3 |
|
| 1 4 |
|
|
|
|
|
| ||
4 |
|
| 5 |
| 6 | 7 | 8 |
| 2 7 |
|
|
|
| STANDARD SIGNAL |
|
| ||
2 1 | 2 |
| 2 |
| 2 | 2 | 2 |
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
| 2 |
| 3 |
| 4 | 5 | 6 |
| 1 3 |
|
|
|
| INPUT IMPEDANCE = 250 OHMS |
|
| |
5 |
|
|
|
|
|
| 1 | 1 |
| 1 |
|
|
|
|
|
| ||
| 6 | 7 |
| 8 |
| 9 |
|
|
|
|
| INPUT CAPACITACNE = 0.1uf±30% |
|
| ||||
|
|
| 0 | 1 |
| 2 |
|
|
|
|
|
| ||||||
|
| L1 |
| L2 |
| L3 |
|
|
|
|
|
|
| 99% ACCURACY |
|
| ||
|
|
|
|
|
|
|
|
|
|
| CONFIGURABLE SCALING |
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
| GROUNDING |
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
| LUG |
|
|
| 11.DEVICENET |
|
|
|
VIEW OF |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
TERMINAL |
|
|
|
|
|
|
|
|
|
|
|
|
| RECOMMENDED DEVICENET CABLE IS BELDEN 3084A OR EQUAL. | ||||
BLOCK |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| 120 OHM, 1/4W TERMINATION RESISTORS MUST BE CONNECTED | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| AT EACH SEGMENT END. |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| CUSTOMER IS REQUIRED TO CONNECT WIRE BETWEEN TERMINAL 30 | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| AND CHASSIS GROUND FOR SURGE PROTECTION. PREFERRED NETWORK | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| WIRING IS TO CONNECT SHIELD TO TERMINAL 48 FOR ONLY ONE UNIT | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ON EACH SEGMENT. CONNECT REMAINING INDIVIDUAL NETWORK CABLE | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| SHIELDS TOGETHER TO ENSURE PROPER SHIELDING OF ENTIRE NETWORK. |
41