Limitorque MX DeviceNet Field Unit  FCD LMENIM2328-00 – 11/05

An output is a signal produced at the PLC and sent to the actuator via the network.

The user may select one output and one input instance.

The default assembly objects are as follows: Polled input - 105, Polled output - 100, Bitstrobe - 107,

COS - 109.

Table 4.1

Instance ID

Type

Data Component Name

Size

100

Output

Output 1 (All Control Channels)

9

101

Output

Output 2

(Analog Control and ESD only)

5

102

Output

Output 3

(Discrete Control and ESD only)

4

103

Output

Output 4

(Analog Control only)

3

104

Output

Output 5

(Discrete Control only)

3

105

Input

Input 1 (All Status Information)

16

106

Input

Input 2

(Position and Faults only)

6

107

Input

Input 3

(Position and Faults only)

8

108

Input

Input 4

(Position, User and Faults only)

11

109

Input

Input 5

(Faults and Alarms only)

6

4.2Output Assembly Instances

Table 4.2 – Output Assembly Instance 100

Assembly

Object

Instance ID

100

Data

Class

 

Instance

Attribute

 

Component

 

 

 

 

Data

ID

Name

ID

ID

Name

Name

Type

 

 

 

 

 

Output 1

100

Channel

1

20

Ctrl_Status_Chan

BYTE

 

 

Interface

 

 

 

 

 

100

Channel

1

1

AO_Ctrl_Valve_ Flow_Chan

INT

 

 

Interface

 

 

 

 

 

100

Channel

1

9

DO_Position_Chan

BYTE

 

 

Interface

 

 

 

 

 

100

Channel

1

21

DO_ESD_Poll_Cnxn

BOOL

 

 

Interface

 

 

 

 

 

100

Channel

1

11

DO_Relay_Chan

BYTE

 

 

Interface

 

 

 

 

 

100

Channel

1

18

DO_Move_Test_Chan

BOOL

 

 

Interface

 

 

 

 

 

100

Channel

1

19

AO_Analog_Output_Chan

UNIT

 

 

Interface

 

 

 

 

Table 4.3 – Output Assembly Instance 101

Assembly

Object

Instance ID

101

Data

Class

 

Instance

Attribute

 

 

Component

 

 

 

 

Data

 

ID

Name

ID

ID

Name

 

Name

Type

 

 

 

 

 

 

 

Output 2

100

Channel

1

20

Ctrl_Status_Chan

BYTE

 

 

 

Interface

 

 

 

 

 

 

100

Channel

1

1

AO_Ctrl_Valve_ Flow_Chan

INT

 

 

 

Interface

 

 

 

 

 

 

100

Channel

1

21

DO_ESD_Poll_Cnxn

BOOL

 

 

 

Interface

 

 

 

 

 

 

100

Channel

1

10

DO_Move_Test_Chan

BOOL

17

 

 

Interface

 

 

 

 

flowserve.com

Page 17
Image 17