FLUXPOWER HPS
SPECIFICATION
Model (kVA) | 400 | 500 | 600 | 800 |
Capacity rating (kVA) | 400 | 500 | 600 | 800 |
|
|
|
|
|
Dimensions W x H x D (mm) | 1990 x 1920 x 990 | 2440 x 2020 x 990 | 2440 x 2020 x 990 | 3640 x 1920 x 990 |
|
|
|
|
|
Weight (kg) | 1820 | 2220 | 2400 | 3600 |
|
|
|
| |
Input / output connection |
| Hard wired (dual input) |
| |
Battery |
| External, |
| |
INPUT |
|
|
|
|
Nominal voltage | 220 / 380, 230 / 400, 240 / 415 VAC single / | |||
|
|
|
| |
Voltage range |
|
| ||
|
|
|
| |
Frequency |
| 50 / 60 Hz (45 – 65 Hz) |
| |
|
|
|
| |
Power factor |
| 0.99 |
| |
|
|
|
| |
Current distortion (THDi) |
| <3.5 % |
| |
|
|
|
|
|
OUTPUT |
|
|
|
|
Nominal voltage | 220 / 380, 230 / 400, 240 / 415 V AC three phase | |||
Frequency |
| 50 / 60 Hz |
| |
|
| |||
Voltage regulation | ±1 % static; ±5 % dynamic 100 % load change | |||
|
|
|
| |
PF acceptable without |
| Lagging to leading 0.9 |
| |
|
| |||
Overload capacity | 101 – 125 % for 10 min | |||
|
| 1000 % for 1 cycle (bypass) |
| |
Efficiency; VFI, |
| ≤94.8 % |
| |
Efficiency; Wise ECO mode |
| 95 – 98 % (>98 %) |
| |
OPTIONS |
|
|
|
|
General | 8 x parallel capacity/redundancy, sync control, isolation transformer, external | |||
| bypass, external battery cabinets, battery switch box, battery thermal probe, | |||
| transformers / autotransformers for voltage adaption, top cable entry | |||
USER INTERFACE |
|
|
|
|
Front panel | Graphical LCD display, mimic with LED’s and keyboard | |||
|
| |||
Standard communication ports | RS232 serial, USB, Remote Emergency Power Off input, Battery Switch status | |||
| monitoring, External Manual Bypass status monitoring, Diesel Mode | |||
Optional communication | Web / SNMP, ModBus, Relay, Modem cards; Remote panel; | |||
| Monitoring, Managing and shutdown software | |||
ENVIRONMENTAL |
|
|
|
|
Operating temperature |
| 0 °C – +40 °C |
| |
|
|
|
| |
Storage temperature |
|
| ||
|
| |||
Altitude | <1000 m; 1 % power derating each 100 m above, max. 2000 m | |||
|
|
|
| |
Audible noise at 1 meter dB(A) |
| <60 |
| |
|
|
|
|
|
STANDARDS AND CERTIFICATION |
|
|
|
|
Marking and certification |
| CE, GOST, ECA ETL |
| |
|
|
|
| |
Safety |
| IEC EN |
| |
|
|
|
| |
EMC |
| IEC EN |
| |
|
|
|
| |
Test and Performance |
| IEC EN |
| |
|
| |||
Quality, environment, health and safety | ISO9001:2008, ISO 14001:2004, BS OHSAS 18001:2007 | |||
|
|
|
|
|
AEGPS - Fluxpower HPS - EN - 08/2013 V1 - Technical data in this document does not contain any binding guarantees or warranties. Content only serves for information purposes and can be modified at any time. We will make binding commitments only upon receipt of concrete enquiries and customer notification of the relevant conditions. Due to the
AEG Power Solutions
Approach your local AEG Power Solutions representative for further support. Contact details can be found on:
www.aegps.com