Toshiba VF-S9 manual External input trip stop mode selection, External trip stop via terminals

Page 128

E6580757

6.15.4 External input trip stop mode selection

: External input trip stop mode selection : Emergency DC braking time

Function

These parameters set the method of stopping the inverter in external trip stop mode. When the inverter is stopped, the trip detection function (" " display) and the FL relay are activated. If

is set to " " (Emergency DC braking), also set

(DC braking current) and

(Emergency DC braking time).

 

1) External trip stop via terminals

The external trip stop function can be executed via the a-contact. Proceed as follows to assign an external stopping terminal and select the stopping method:

 

Input terminal

6

CC

a-contact

[Parameter setting]

Title

Function

Adjustment range

 

Default setting

 

 

 

 

 

 

External input trip stop mode selection

0: Coast stop

 

0

 

1: Slowdown stop

 

 

 

2: Emergency DC braking

 

 

 

Emergency DC braking time

0.0 20.0 (s)

 

1.0

 

DC braking current

0100 (%)

 

30

 

 

 

 

 

(Example of terminal assignment): Assigning the trip stop function to the RST terminal

 

 

Title

Function

Adjustment range

 

Setting

 

 

 

 

 

Input terminal selection (RST)

0 51

11

 

(External trip stop)

 

 

 

Notes:

 

 

 

 

1)Emergency stopping via the specified terminal is possible, even during panel operation.

2)If is set to "2" (Emergency DC braking) and DC braking is not required for normal stopping, set

the DC braking time ( ) to 0.0 (sec).

F-44

Image 128
Contents Tosvert VF-S9 Contents E6580757 Iii Safety precautions Meanings of symbolsSafety precautions Explanation of markingsGeneral operation Transportation ‚ Installation WiringOperations When retry function is selected inverter Maintenance and inspectionDisposal Attach warning labelsFeatures II. IntroductionMandatory Read firstCheck product purchase Contents of the product code Names and functions Outside viewCharge lamp Terminal board coverE6580757 Main circuit and control circuit terminal boards 2022PL2015PM VFS9-2022PM/2037PM VFS9-4007PL ∼ 4037PLVFS9-2055PL/2075PL 4055PL/4075PL How to open the front terminal board cover See 2.3.2 for details on all terminal functionsMotors Braking a motor when cutting off power supply Extremely low loads and low inertia loadsOccurrence of instability Loads that generate negative torquePower factor improving capacitors InvertersProtecting inverters from overcurrent Inverter capacityWhat to do about leak current Effects of leak current across groundCircuit interupting fuse MCCBn+1 INVnPower RemediesFfects of leak current across lines SupplyUse the electronic thermal built into the inverter Installation Installation environmentContinuous operation this may result in fire Not examples for resistance to fire or explosionConsult with Toshiba about these measures How to install Installation locationCabinet must be ventilated and cooled Inverter TypeInstalling more than one unit in a cabinet Connection equipment Preventing radio noise Control and main power supplyWiring Standard connections Standard connection diagram 1 sink common CC This diagram shows a standard wiring of the main circuitStandard connection diagram 2 source common P24 VF-S9Power supply and motor connections Description of terminalsMain circuit terminals Connections with peripheral equipmentControl circuit terminals sink logic Main circuitInput Standard default setting 0~10Vdc input Internal imped ~60Hz60Hz setting frequencyPut. Standard default setting output cur 1mA full-scale dc By jumper JP302 switching Full scale DC amMultifunction programmable relay contact = 1, 30Vdc-1A, 250Vac-1A cos φ = At resistance loadOutput Detects the operation of the inverters 30Vdc-1A During protection function operationInput Common Output Logic switching/voltage-current output switching jumper Operations How to operate the VF-S9 WiringMotor Main circuitE6580757 Mccb Motor Monitor display selection Is set to Adjustment rangeSimplified Operation of the VF-S9 How to start and stop How to set the frequencySetting the frequency using the operation panel Example of operating a run from the panelMoves the frequency down PotentiometerE6580757 Setting monitor mode Mode for setting inverter parameters Status monitor mode Mode for monitoring all inverter statusBasic VF-S9 operations VF-S9 has the following three monitor modesHow to set parameters Setting monitor modeHow to set the basic parameters Press the Enter key to save the changed maximum frequencyHow to set extended parameters Key and the key to selectKey to change the dynamic braking selection from Search and resetting of changed parametersExample of parameter setting How to search and reprogram parameters How to program setup parameters Parameters that cannot be changed while running Returning all parameters to standard default settingCommand mode selection Set , and and can Pressing the Enter key displays Key operated LED display OperationKey or the key to change the set value. To return to Setting acceleration/deceleration time Basic parametersAutomatic acceleration/deceleration Set automatic acceleration/deceleration to orManually setting acceleration/deceleration time Parameter setting Title Function Adjustment rangeAcceleration time Seconds Deceleration time SecondsIncreasing starting torque Automatic torque boostAutomatic torque boost and V/F control mode selection Set V/F control mode selection to 0 V/F constantIf auto-tuning error Appears, see 6.13 AutoSetting environmental protection Setting parameters by operating methodAutomatic environment setting Automatic function settingVIA/II UP/DOWN Selection of operation mode Command mode selection Frequency setting mode selectionCommand mode selection Title Function Adjustment rangeMeter selection Meter adjustment Meter setting and adjustmentPreset-speed operation Adjustment scale with meter adjustment parameter ResolutionExample of 4-20mA programmed output for details, see Connect meters as shown belowStandard default setting Adjusting the meter in inverter stop stateDefault setting Tion Is set toSetting values Parameter settingSelecting forward and reverse runs operation panel only Forward/reverse run selectionMaximum frequency Upper limit and lower limit frequenciesMaximum frequency Upper limit frequency Lower limit frequencyBase frequency 25 ∼ 400 Hz Base frequencyBase frequency Selecting control mode Control mode selectionTime SelectionConstant torque characteristics general method of use Setting for fans and pumpsSetting V/F control selection Automatic torque boost Increasing starting torqueMotor constant must be set This gives steady torque for stable runsPrecautions on vector control Energy-savingSorless vector control Somewhat lowerTorque boost Setting the electronic thermalManual torque boost increasing torque at low speeds Title Function Adjustment range Default setting OverloadProtection Stall Motor electronic thermal proSetting of motor electronic thermal protection level Default setting 100% Press Key to change the parameter toSetting the motor electronic thermal protection level Setting value Overload protection Overload stallPreset-speed operation speeds in 15 steps Inverter over load characteristicsPreset-speed operation frequencies 1~7 Preset-speed operation frequencies 8~15Preset-speed S3-CCTerminal functions are as follows Terminal S1 =6 SS1Using other speed commands with preset-speed command Example of 7-step speed operationLow-speed signal Low-speed signal output frequencyLow-speed signal output frequency ∼ Hz Extended parametersSpeed reach detection band Output of designated frequency reach signalParameter setting of output terminal selection Output of set frequency speed reach signal Speed reach setting frequency Speed reach detection bandParameter setting of set frequency and detection band Title Function Adjustment range SettingST standby signal selection Input signal selectionChanging the standby signal function Setting the reset signal Terminal function selection Keeping an input terminal function always active onModifying input terminal functions Always-active function selectionSetting of contact input terminal function Terminal Title Function Adjustment range Default settingInput terminal selection 3 RST Reset Connection method Contact input Sink logicExample of application ... Three-wire operation Case of three-wire operation Set toSink logic/source logic input Input terminal selectionSetting of output terminal function Modifying output terminal functionsExamples of application Output terminal selectionBasic parameters Switching motor characteristics via terminal inputSetting of switching terminals Automatic frequency switching Frequency priority selectionExternal switching Fchg enabled Set frequency is cleared automatically after power-offExternal contact UP/DOWN Contact input. SeeSetting frequency command characteristics 10Vdc voltage input adjustment VIA, VIB 20mAdc current input adjustmentSample sequence diagram 1 Adjustment with continuous signals Adjustment with pulse signals Parameter-setting exampleSample sequence diagram 2 Adjustment with pulse signals Frequency adjustment rangeMinimum unit of frequency adjustment Simultaneous inputStarting frequency setting Operation frequencyStarting frequency Function Frequency set with the parameterDC braking 2 Run/stop control with frequency setting signalsDC braking DC braking time 20.0 sec Jog run modeJog run frequency Jog run stopping pattern Jog run setting Jump frequency jumping resonant frequencies Jump frequency Jumping width Jump frequency 3 Jumping widthPreset-speed operation frequency 8 to ∼ Preset-speed operation frequency 8 toRandom mode PWM carrier frequencyAuto-restart control selection Trip-less intensificationAuto-restart Restart during coasting Restarting motor during coasting Motor speed search function DC braking during restartRegenerative power ride-through control Regenerative power ride-through controlIf momentary power failure occurs ApplicationRetry selection Canceling conditionsRetry function Dynamic regenerative braking Dynamic braking selection Braking resistor operation rateSeparate-type optional resistor with thermal fuse Connecting an external braking resistor optionalParameter setting Title Function Setting the braking resistor operation rate Overvoltage limit operation 12.5 Avoiding overvoltage trippingMinimum resistances of connectable braking resistors Output voltage adjustment/Supply voltage correction To the base frequency So that noOutput voltage unlimited Conducting PI control External connection100.0 Integral gain 100.0Setting PI control Adjusting the PI control gain levelGain adjustment parameter Types of PI control interfacesAdjusting analog command voltages Setting motor constants Selection 1 Setting by automatic torque boostSet the auto-tuning parameter to See .2 for details of the setting methodRameters Auto-tuning Application of individual settings Perform adjustments according to the actual operation To the actual operationDeceleration time 3600 s Acceleration time 3600 sAcceleration/deceleration patterns Linear acceleration/decelerationSwitching to acceleration/deceleration Selection using parametersSetting motor electronic thermal protection Protection functionsSetting current stall Inverter trip retentionStall prevention level Inverter trip retention selectionExternal input trip stop mode selection External trip stop via terminalsIs set to Emergency DC braking, also set Emergency DC braking timeOutput phase failure detection Output phase failure detection mode selectionFailure detection signal generated FL relay deactivated Emergency stopping from the operation panelInput phase failure detection mode selection Input phase failure detectionControl mode for small current Specified time Title Function Adjustment range Disabled Enabled Over-torque trip/alarm level ∼ 250 %Over-torque trip Level flows for more thanDetection signal No trip Over-torque detection Pre-alarm signalOutput terminal function 12 OT Over-torque detection No trip Over-torqueUndervoltage trip 15.10 4-20mA dc calibrationUndervoltage trip selection Meter biasProhibition of change of parameter settings Examples of settingProhibition of change of parameter settings Setting methodsResetting method Changing the display unit to A/V/min-1Unit selection Free unit selectionDisplay in percentage terms Display in amperes/volts Changing the display format while power is on Standard monitor mode ⇒ Standard monitor display selectionChanging the status monitor display format Standard monitor display selectionCommunication function Common serial Using the RS232C/RS485 Setting the communication functionsTransmission specifications Communication function parameters Common serial optionsCommand by communicating independently Example of connection for RS485-communicationNext data Use the terminal board to branch the cable Number, to the host computerApplied operation Setting the operation frequencyOperation panel key setting S1 UP S2 Down S3 CLR Preset-speed setting Switching between external contact UP/DOWN VIA inputTo switch to VIA/II setting, use the external PNL/TB S1FCHGSwitching between analog setting and preset-speed setting Signal Voltage signalSetting by means of a remote input device Operation is controlled in accordance with SettingSetting the operation mode Terminal board operationCase of three wire operation Set to Enable to run at HD onEration holding S1 terminal set to Operation, inverter stopS2 PNL/TB VIA VIB Operation from an external input deviceOFF LED Display of trip information Display of trip informationExample of call-up of trip information E6580757 About the EMC directive How to cope with the CE directiveTaking measures to satisfy the CE/UL directive Measures to satisfy the EMC directive Example of wiring Single-phase 200V classAbout the low-voltage directive Measures to satisfy the low-voltage directiveInverter satisfies the low-voltage directive Plate. Refer to the .1 for earth cable sizesSelection of wiring materials and devices Peripheral devicesSelection of wiring devices Magnetic contactor in the secondary circuit Installation of a magnetic contactorMagnetic contactor in the primary circuit Installation of an overload relay Optional external devicesEffect Reactor type Power factor Harmonics Suppression 200V-3.7kW Improvement Other modelOr less Input AC reactor DC reactor Actor effective for external surge suppressionWard/reverse switch Model CBVR-7B1 Parameter writerModel PWU001Z Extension panel UP/DOWN key, Monitor key, and Enter key Model RKP001ZDevices Input AC re ActorDCL Devices External dimensions and connections Foot Mounted Noise filterDevices External dimensions and connections Braking Resistor Devices External dimensions and connections Parameter Writer ExtenSion panel CommunicaTable of parameters and data User parametersFour automatic functions Other Basic parametersExtended parameters Input/output parametersFrequency parameters VIB, VIA/II0213 VIB input point 400 Frequency Frequency Down Operation mode parameters Protection parameters Torque boost parametersAcceleration/deceleration time parameters Operation panel parameters Communication parametersDefault settings by inverter rating Table of input terminal functions 1/3Table of input terminal functions 2/3 ST+PNL/TBTable of input terminal functions 3/3 Table of output terminal functions 1/2Table of output terminal functions 2/2 POLOrder of precedence of combined functions Standard specifications SpecificationsModels and their standard specifications Specification Outside dimensions and mass Outside dimensions and massFig.A PlateBefore making a service call Trip information and remedies Trip causes/warnings and remediesProblem Possible causes Remedies Overvoltage during Problem Possible causes Remedies Small-current opera Process of initializa Values Restoring the inverter from a trip If the motor does not run while no trip message is displayed How to determine the causes of other problems How to cope with parameter setting-related problems Inspection and maintenance Regular inspectionPeriodical inspection Check pointsCheck items Call the local sales agencyReplacement of expendable parts Keeping the inverter in storage Standard replacement cycles of principal partsMaking a call for servicing Warranty Disposal of the inverter Toshiba Corporation