RELAYS
Three on board multipurpose relays are provided by the
If the relay is to function as a driver for a remote totalizer or as a flow sampler contact, the totalizer multiplier (P32) will be factored by the setpoint . Note that parameters P16, P19, and P22 will default to zero. When a relay is set to totalizer (P32), you must have the applicable parameter (P16 for relay 1, P19 for relay 2, or P22 for relay 3) set to something other than zero (normally 1).
Example: For relay 1
Relay totalizer factor = totalizer factor (P32) relay 1 setpoint (P16)
=100 (P32=5)
2 (P16)
=50 units/pulse
The status of each relay is shown in the display. Refer to \ Flow and Total Display.
For battery operation, have relays energizing on alarm.
mA OUTPUT
The
Normal scaling for representation of flow, head or velocity is:
» 0 or 4 mA | = 0 |
|
» 20 mA | = maximum measurement value for: | » P6*: flow rate |
|
| at maximum head |
|
| » P7: maximum head |
|
| » P10: velocity |
|
| at maximum head |
Normal scaling for representation of temperature is:
» 0 or 4 mA = – 40 °C
» 20 mA = 60 °C
If custom scaling is required, the 20 mA corresponding value (other than 0) can be entered into P25. The range (0 to 20 or 4 to 20 mA) and damping (see Damping) are set via P26 and P27 respectively.
7ML19985AB01 | OCM III | 30 |