Siemens TPS3 user manual Maintenance

Page 14

VCAUTION

CONDUCTING DIELECTRIC AND/OR

HI-POTENTIAL TESTING WILL CAUSE

INTERNAL DAMAGE TO TPS3 UNIT.

Do not perform dielectric or high potential

tests with the TPS3 unit installed.

Maintenance

SPDs require minimal maintenance. Periodic inspection of diagnostic LED indicators ensures proper operation. Clean SPD as appropriate.

Troubleshooting & Service

Please contact TPS Technical Support at 1.888.333.3545 for service related issues.

Quality SPDs are designed and tested to withstand severe duty. However, there are various electrical anomalies against which SPDs cannot protect. These are generally Sustained Overvoltages also known as Temporary Overvoltages (TOVs). In this context, Sustained Overvoltages may be only a few cycles. Failed SPDs tend to be symptoms, not root causes. There may be larger issues at play. Regardless of cause, SPDs attempt to protect their load until failure.

Bonding or reference to ground problems are the root cause of many SPD problems. If the SPD shows problems on startup, there is reasonable chance of bonding/grounding/misapplication issue. Such problems permanently damage the SPD. If not corrected, SPD problems will reoccur.

Tip: Visually confirm N-G bonding. Be aware that a voltmeter measuring N-G can be misleading. For example, N-G voltage could read 0V because neutral and ground are at the same potential purely by happenstance, not because they are bonded. Visually confirm bonding.

Tip: Experience indicates that regulation-challenged generators can cause Sustained Overvoltages, as well as ungrounded generators, and/or usual load transfer systems.

Abnormal N-G Voltage Indicators

This SPD include N-G voltage indicators. If the SPD detects excessive N-G voltage, the Red Service LED will blink and the Audible Alarm will cycle. This condition requires immediate attention as the SPD will fail.

VDANGER

Hazardous voltage.

Will cause death or serious injury.

Keep Out.

Qualified personnel only.

Disconnect and lock off all power before working on this equipment.

Incorrectly bonded distribution systems damage SPDs. If the XO or N-G bonding jumper is not installed, the electrical system has no reference to ground. It becomes an ungrounded system. Please see previous section regarding SPDs on ungrounded systems. Such systems are known to eventually produce abnormally high L-G voltages. SPDs will attempt to chase this system-level overvoltage abnormality until the SPD fails. This effect is accelerated on Wye systems where SPDs are designed for grounded systems. (SPDs for ungrounded systems generally have higher MCOV to allow for L-G voltage fluctuations.) Failures of this nature are not defects in the SPDs workmanship or material. This is an installation error and is not covered by warranty.

A differential voltage circuit monitors neutral to ground voltage. When N-G voltage becomes excessive, an amplifier energizes a resistor. Eventually, that resistor will overheat and cause thermally sensitive shrink wrap to shrink around the resistor. This does not occur on transient or instantaneous N-G overvoltages. When the SPD is deenergized, the shrink wrap covered resistor can be accessed by qualified personnel under the display plate cover.

Module Replacement & Service

The module is field replaceable. Service should only be performed by qualified persons. Deenergize SPD, confirm with appropriate measurement equipment and discharge internal capacitance to ground. Mark locations and carefully disconnect diagnostic cables, contacts, connecting conductors, etc. Unbolt module from backplane. Reinstall in reverse.

There are no user serviceable parts inside the module. Disassembly is not permitted.

Modules may be returned to the factory for factory service, qualification and return. Please contact factory at 1.888.333.3545 for assistance.

11

Image 14
Contents TPS3 Internal Manual Bonding and Grounding Hazard Table of Contents Introduction Do Not Hi-Pot Test SPDsNEC Art 285 & UL TPS3 L1 General Information Dead Front Modification InstructionHazardous voltage Will cause death or serious injury Replace deadfront and trim Page TPS3 05 and TPS3 06 Module Replacement Instructions TPS3 01 and TPS3 06 Module Installation Instructions MCC TPS3 Control and Diagnostic Display Panel OperationMaintenance Page 10 #8171

TPS3 specifications

Siemens TPS3 is a sophisticated technology advancement that has significantly impacted the field of industrial automation. As part of Siemens’ portfolio of control systems, TPS3 is designed to enhance process efficiency, improve accuracy in operations, and ensure greater reliability and flexibility across various industrial sectors.

One of the key features of the Siemens TPS3 is its modular architecture. This modularity allows users to customize the system according to their specific needs and operational requirements. Each module can be added or removed with ease, facilitating the scalability of operations. This flexibility is critical for businesses aiming to adapt their capacity based on fluctuating market demands.

The TPS3 employs state-of-the-art control technologies, integrating advanced algorithms for real-time data processing and control. This capability enables operators to achieve precise control over processes, ensuring that production runs smoothly and meets quality standards. Advanced predictive maintenance features are also embedded within the system, allowing for the minimization of downtime and optimization of maintenance schedules through data analytics.

Another significant characteristic of the TPS3 is its user-friendly interface. The intuitive design allows operators to easily monitor and manage processes through graphical displays and straightforward navigation. This usability reduces the learning curve for new staff and increases overall operational efficiency.

Siemens emphasizes connectivity in the TPS3, with robust support for Industry 4.0 principles. The system can seamlessly integrate with IoT devices and other digital platforms, enabling extensive data collection and analytics. This connectivity enhances decision-making by providing insights into process performance and resource utilization.

Security is also a critical aspect of the TPS3, with built-in features that protect against cyber threats. These security measures include encrypted communication protocols and robust firewall systems to safeguard sensitive operational data.

Overall, the Siemens TPS3 stands out for its modular design, real-time control capabilities, user-friendly interface, strong connectivity features, and commitment to security. These characteristics make it a potent tool for modern industries seeking to optimize their processes, reduce costs, and adapt to the ever-evolving technological landscape. With its comprehensive feature set, the TPS3 is poised to drive greater efficiency and innovation in the realm of industrial automation.