Page 2

V WARNING-Hazardous Voltage & Shock Hazard

Failure to Follow These Instructions Could Result in Death or Serious Injury

Only qualified licensed electricians should install or service SPDs

Hazardous voltages exist within SPDs

SPDs should never be installed or serviced when energized

Use appropriate safety precautions including Personal Protection Equipment

Failure to follow these instructions can result in death, serious injury, and/or equipment damage.

This manual shall be read in entirety prior to installing

Bonding and Grounding Hazard

Verify that the neutral conductor in the service entrance equipment is bonded to ground in accordance with the National Electrical Code (NEC®) and all applicable codes.

Verify that the neutral terminal (XO) on the secondary side of distribution transformers are grounded to the system ground in accordance with the NEC® and all applicable codes.

During installation into an electrical system the SPD must not be energized until the electrical system is completely installed, inspected and tested. All conductors must be connected and functional including the neutral (if required). The voltage rating of the SPD and system must be verified before energizing the SPD.

Failure to follow these guidelines can lead to abnormally high voltages at the SPD. This may cause the SPD to fail. The warranty is voided if the SPD is incorrectly installed and/or if the neutral conductor in the service entrance equipment or downstream of separately derived systems is not bonded to ground in accordance with the NEC®.

Do Not Hi-Pot Test SPDs

Any factory or on-site testing of power distribution equipment that exceeds normal operating voltage such as high-potential insulation testing, or any other tests where the suppression components will be subjected to higher voltage than their rated Maximum Continuous Operating Voltage (MCOV) must be conducted with the SPD disconnected from the power source. For 4-wire systems, the neutral connection at the SPD must also be disconnected prior to performing high- potential testing and then reconnected after test completion.

Failure to disconnect SPD and associated components during elevated voltage testing will damage the SPD and will void the warranty.

2

Image 2
Contents TPS3 Internal Manual Bonding and Grounding Hazard Table of Contents Introduction Do Not Hi-Pot Test SPDsNEC Art 285 & UL TPS3 L1 General Information Dead Front Modification InstructionHazardous voltage Will cause death or serious injury Replace deadfront and trim Page TPS3 05 and TPS3 06 Module Replacement Instructions TPS3 01 and TPS3 06 Module Installation Instructions MCC TPS3 Control and Diagnostic Display Panel OperationMaintenance Page 10 #8171

TPS3 specifications

Siemens TPS3 is a sophisticated technology advancement that has significantly impacted the field of industrial automation. As part of Siemens’ portfolio of control systems, TPS3 is designed to enhance process efficiency, improve accuracy in operations, and ensure greater reliability and flexibility across various industrial sectors.

One of the key features of the Siemens TPS3 is its modular architecture. This modularity allows users to customize the system according to their specific needs and operational requirements. Each module can be added or removed with ease, facilitating the scalability of operations. This flexibility is critical for businesses aiming to adapt their capacity based on fluctuating market demands.

The TPS3 employs state-of-the-art control technologies, integrating advanced algorithms for real-time data processing and control. This capability enables operators to achieve precise control over processes, ensuring that production runs smoothly and meets quality standards. Advanced predictive maintenance features are also embedded within the system, allowing for the minimization of downtime and optimization of maintenance schedules through data analytics.

Another significant characteristic of the TPS3 is its user-friendly interface. The intuitive design allows operators to easily monitor and manage processes through graphical displays and straightforward navigation. This usability reduces the learning curve for new staff and increases overall operational efficiency.

Siemens emphasizes connectivity in the TPS3, with robust support for Industry 4.0 principles. The system can seamlessly integrate with IoT devices and other digital platforms, enabling extensive data collection and analytics. This connectivity enhances decision-making by providing insights into process performance and resource utilization.

Security is also a critical aspect of the TPS3, with built-in features that protect against cyber threats. These security measures include encrypted communication protocols and robust firewall systems to safeguard sensitive operational data.

Overall, the Siemens TPS3 stands out for its modular design, real-time control capabilities, user-friendly interface, strong connectivity features, and commitment to security. These characteristics make it a potent tool for modern industries seeking to optimize their processes, reduce costs, and adapt to the ever-evolving technological landscape. With its comprehensive feature set, the TPS3 is poised to drive greater efficiency and innovation in the realm of industrial automation.