TOSHIBA G8000 Series UPS
Installation Planning Guide for 150kVA UPS
Standard System: 480V Input, 480Y/277V Output
General Mechanical Information
| Dimensions |
|
| Weight |
|
| (W x D x H) |
|
|
| |
|
|
|
|
| |
| Inches |
| Lbs. | ||
| 55.1 x 31.5 x 78.75 | 2,756 |
|
Approximate
Heat Loss
Btu/Hr
37,914
Primary AC Input (480V 3-Phase / 3-Wire)
Maximum Input Power | Suggested External | Suggested Minimum Feeder | Suggested Maximum Feeder Length | |||
| Demand |
| Overcurrent Protection | Wire Size Per Phase | For Min. Wire Size in Steel Conduit | |
kVA | PF |
| Amps | Amps | AWG or kcmil at 75º C Temp. Rating | Feet |
150 | >0.98 |
| 180 | 225 AT | (1) x 4/0 | 480 |
Alternate (Bypass) AC Input (480V 3-Phase / 4-Wire)
Maximum Input Power | Suggested External | Suggested Minimum Feeder | Suggested Maximum Feeder Length | |||
| Demand |
| Overcurrent Protection | Wire Size Per Phase / Neutral | For Min. Wire Size in Steel Conduit | |
kVA | PF |
| Amps | Amps | AWG or kcmil at 75º C Temp. Rating | Feet |
150 | 0.8 |
| 180 | 225 AT | (1) x 4/0 / (2) x 3/0 | 380 |
Battery Input (360VDC Nominal)
| Battery Capacity Required | Maximum Discharge | Suggested External |
| Suggested Minimum Feeder |
|
| for Full Load Output | at Full Load Output | Overcurrent Protection |
| Wire Size Per Phase |
|
| kWB | Amps DC | Amps |
|
|
|
|
| AWG or kcmil at 75º C Temp. Rating | ||||
127.7 | 448 | 500 AT |
| (2) x 4/0 |
Suggested Maximum Feeder Length For Min. Wire Size in Steel Conduit
Feet
70
AC Output (480/277V 3-Phase / 4-Wire)
| Rated Output Power |
|
| Suggested External |
|
| Suggested Minimum Feeder |
|
| Suggested Maximum Feeder Length |
| ||
|
|
| Overcurrent Protection |
|
| Wire Size Per Phase / Neutral |
|
| For Min. Wire Size in Steel Conduit |
| |||
|
|
|
|
|
|
|
|
|
|
| |||
| kVA | PF | Amps |
|
| Amps |
|
| AWG or kcmil at 75º C Temp. Rating |
|
| Feet |
|
150 | 0.8 | 180 |
|
| 225 AT |
| (1) x 4/0 / (2) x 3/0 | 380 |
|
Important Notes:
1.Maximum Current required at Primary AC Input based on full load output and maximum battery charging current.
2.Output load conductors are to be installed in separate conduit from input conductors.
3.Control wires and power wires are to be installed in separate conduits.
4.Recommended AC input and output overcurrent protection based on continuous full load current per NEC.
5.Wiring shall comply with all applicable national and local electrical codes.
6.Grounding conductors to be sized per NEC Article
-Primary AC Input: 3φ,
-Alternate AC Input: 3φ,
-AC Output: 3φ,
-DC Input:
7.Nominal battery voltage based on the use of VRLA type batteries (2.0 volts/cell nominal).
8.Maximum battery discharge current based on lowest permissible discharge voltage of 1.6 VPC.
9.DC wires should be sized to allow not more than a
10.Weights do not include batteries or other auxiliary equipment external to the UPS.
11.Sizing calculations based on the following assumptions:
-Not more than 3
-Temperature rating of conductors and terminals: 90 deg. C.
-Feeder distance calculations based on NEC Tables 8 and 9 data, allowing for 2% AC voltage drop.
-Reference: 2002 NEC Handbook. Consult latest edition of applicable national and local codes for possible variations.
12.Ratings of wires and overcurrent devices are suggested minimums. Consult with a registered Professional Engineer within your local area for proper size selections.