Siemens LU01 instruction manual Relays P100 to P119, P072 Failsafe Level Advance, Relay reaction

Page 45

Relay reaction

The way in which relay programming reacts to the failsafe level depends on P129 Relay Failsafe (page 46). By default:

Alarm relays have P129 = OFF and so react to the Failsafe Material Level.

Control relays have P129 = dE and so de-energize the relay when the unit enters Failsafe mode regardless of the Failsafe Material Level.

P072 Failsafe Level Advance

Sets the speed the SITRANS LU01 advances to and returns from the Failsafe Material Level.

 

1

*

Restricted

Advances to/from Failsafe Material Level as set by

 

P003, P700 and P701.

 

 

 

 

Values

 

 

 

 

2

 

Immediate

Failsafe Material Level assumed immediately

 

 

 

 

 

 

3

 

Fast Back

Failsafe Level Advance is restricted, return is

 

 

immediate

 

 

 

 

 

P003 Maximum Process Speed

 

P070 Failsafe Timer

Related

P071 Failsafe Material Level

 

P700 Max Fill Rate

 

P701 Max Empty Rate

 

 

 

 

 

Relays (P100 to P119)

The SITRANS LU01 has four relays (or digital outputs) used to control devices and alarms. While the number of devices is limited by the relays, all control functions are accessible through software and each parameter is indexed to the relays.

The SITRANS LU01 makes standard application programming easier by providing an extensive list of presets in P100 (Preset Applications).

Standard alarms are set from P101 to P104. In the RUN mode, when the material level:

rises to a High or High High Alarm value, the associated Alarm and Relay Status indicators are displayed and the allocated relay(s) de-energize.

falls 5% of Span (P007) below the High or High High Alarm value, the associated Alarm and Relay Status indicators extinguish, and the allocated relay(s) energize.

falls below the Low or Low Low Alarm value, the associated Alarm and Relay Status indicators are displayed and the allocated relay(s) de-energize.

rises 5% of Span (P007) above the Low and Low Low Alarm value, the associated Alarm and Relay Status indicators extinguish, and the allocated relay(s) energize.

Note: Enter all standard alarm material level values in Units (P005) or percent of Span (P007) as referenced to Empty (P006).

To display the current value (or enter a new value) in percent of Span, press as required to display the % symbol.

Control functions allow each relay to be configured independently to take advantage of the SITRANS LU01’s advanced features and flexibility. Start with a preset application and then change the required parameters to make the task more efficient.

7ML19985BE02

SITRANS LU01 – INSTRUCTION MANUAL

Page 39

Parameters

Image 45
Contents Sitrans This document is available in bound version Technical data subject to changeManual for agreement with Instrumentation described, variationsTable of Contents Independent Relay Setpoints 100 Page Introduction IntroductionRS-232 or Local SmartLinxProgrammable Features Sitrans LU01 FeaturesUnits ManualSpecifications SpecificationsAmbient temperature Installation categoryOutputs ProgrammerOptions TransducerCable Refer to associated product documentationManual On Product Description Safety marking symbolsInstallation InstallationLocation Cable/Conduit Entry RequirementsTransducer Mounting Transducer TypesM 1.65 ft Switchterminal blockboard B RJ-11 port Communication Mode LEDInterconnection AC ModelTB1 DC ModelOptional SmartLinx Module LCD CardBoard a Transducer System DiagramRelays Temperature SensorMA Outputs To TS-3SmartLinx CommunicationLevel System Synchronization SerialAC Supply Wiring PowerDC Supply Wiring Position. SelectProgrammer Communications AccessUse the hand programmer to change individual parameters RJ-11 port RJ-11 cableDisplay ProgrammingDisplay Segment DescriptionKeypad ProgrammingFunction keys Changing Parameters Program Mode EntryParameter Reset Features Parameters TypesProgramming Security Display in RUN Mode OperationOperation Operation Key Description BerP731 System Performance Evaluation Point Alarm Indicator RelayPerformance Test Results Operation Level Space or DistanceOperation Parameter Reference Program modeHelpful Hints ParametersSecures the Sitrans LU01 from changes P000 Lock1954 OFF programming permitted Lated levelP001 Operation Quick Start P001 to P007P002 Material P003 Maximum Process SpeedSpecifies measurement units used for dimensional values P004 TransducerP005 Units P006 Empty P007 SpanSets the range level to be measured P050 Tank Shape Application Parameters Volume P050 to P055Examples P051 Maximum VolumeP053 Tank Dimension L P052 Tank Dimension aUniversal Volume Calculation Dimension a as used in P050 Tank ShapeTypical volume calculations Entering a Volume BreakpointEntering a Level Breakpoint Display and Reading P060 to P062 P060 Decimal Position P061 Convert Reading P070 Failsafe Timer Failsafe P070 to P072P062 Offset Reading P071 Failsafe Material Level Material level reported when a Failsafe State is initiatedOnce activated, the Failsafe State initiates the following Selecting HI, LO, or HOLdRelays P100 to P119 P072 Failsafe Level AdvanceRelay reaction Option Relay # Point # Standard Alarm as % of Span, P007 P100 Preset ApplicationsP102 Low Alarm P101 High AlarmP103 High High Alarm P104 Low Low AlarmP111 Relay Control Function Custom Relays P111 to P113Function Sets the control algorithm used to trip the relayIndependent Relay Setpoints Values For P111 Control Type Relay ControlRelays are energized and de-energized Action When P112 Relay on Setpoint Distance above and below the bound alarm setpointsP113 Relay OFF Setpoint P116 Dead BandIndependent Relay Failsafe P129 Relay Function P111 Preset P129P129 Relay Failsafe To select an independent Relay Failsafe valueP200 mA Output Range MA Output P200 to P219P201 mA Output Function P203 mA Output Value / TransducerMA Output Limits P212 and P213 Independent mA Setpoints P210 and P211P210 0/4 mA Output Setpoint P211 20 mA Output SetpointP213 mA Output Max Limit MA Output Trim P214 to P215P214 4 mA Output Trim P215 20 mA Output TrimP300 Temperature, Transducer Maximum Record Temperatures P300 to P303MA Output Failsafe P219 Standard Data Logging P300 to P321Profile Records P330 to P337 P302 Temperature, Sensor MaximumP330 Profile Record Code DescriptionP331 Auto Record Enable P333 Auto Record IntervalAuto Record on and OFF Setpoints P334 to P337 P335 Auto Record OFF Setpoint P334 Auto Record on SetpointP336 Auto Record Filling / Emptying P337 Auto Record LOE TimeRange Calibration P650 to P654 Installation Records P340 to P342Using Sound Velocity Calibration Condition for use of this featureP651 Sound Velocity Calibration Offset CalibrationP652 Offset Correction Value altered when an Offset Calibration is performedP653 Velocity P654 Velocity at 20CP664 Temperature Temperature Compensation P660 to P664View the transducer temperature in C P660 Temp SourceP700 Max Fill Rate Rate P700 to P707P701 Max Empty Rate P003 Value Meters/MinuteP702 Filling Indicator P703 Emptying IndicatorP704 Rate Filter P706 Rate Update Distance P705 Rate Update TimeMeasurement Verification P710 to P713 P707 Rate ValueP711 value P712 preset value P711 Echo LockP712 Echo Lock Sampling Transducer Scanning P725 to P729 P727 Scan DelayP713 Echo Lock Window P726 Level System SyncDisplay P730 to P733 P728 Shot DelayP729 Scan Time P730 Auxiliary ReadingP733 Scroll Access P732 Display DelayAdjusts the Point Number display scroll speed P731 Auxiliary Reading KeySmartLinx Reserved 750 to Peripheral Communication Support Parameters P740 to P749P740 Peripheral Communications P748 RS-485 TerminationP790 Hardware Error SmartLinx Hardware TestingCommunications P772 P772 Baud RateP792 Bus Error Count P791 Bus ErrorEcho Processing P800 to P807 P794 SmartLinx Module Type P795 SmartLinx ProtocolP801 Range Extension P803 Shot / Pulse ModeP802 Transducer with Submergence Shield Determines what type of ultrasonic shots are firedP805 Echo Confidence P804 Confidence ThresholdDisplay Description Determines which echoes are evaluated by softwareP806 Echo Strength Advanced Echo Processing P810 to P825P807 Noise Anatomy of an Echo ProfileP810 Scope Displays Display SymbolScrolling ValuesP816 Echo Time Raw Profile Pointer P817 to P825P817 Profile Pointer Time P818 Profile Pointer DistanceP820 Algorithm P819 Profile Pointer AmplitudeP822 Narrow Echo Filter P821 Spike FilterP823 Reform Echo Dampens spikes in the echo profile to reduce false readingsP825 Echo Marker Trigger Advanced TVT Adjustment P830 to P835P830 TVT Type Selects the TVT Curve usedAllows manual adjustment of the TVT curve P832 TVT Shaper AdjustP831 TVT Shaper To change a breakpointP834 TVT Start Duration P833 TVT Start MinP835 TVT Slope Min Range -30 toAdjust the short shot transmit pulse frequency in kHz Advanced Shot Adjustment P840 to P852P840 Short Shot Number P841 Long Shot NumberP844 Short Shot Width P843 Long Shot FrequencyP845 Long Shot Width P850 Short Shot BiasP851 Short Shot Floor Test P900 to P913P852 Short Shot Range P900 Software Revision NumberP903 Display P902 WatchdogP904 Keypad P905 Transmit PulseP913 Sensor Temperature P912 Transducer TemperatureP907 Programmer Interface P910 RelayP920 Reading Measurement Measurement P920 to P927P921 Material Measurement P922 Space MeasurementMaster Reset P999 P924 Volume MeasurementThis feature resets all parameters to original values P927 Distance PercentTransmit Pulse Technical ReferenceEcho Processing Technical ReferenceSound Velocity Distance CalculationEcho Processing Displays Scope Displays, P810 Dolphin Plus DisplayVolume Calculation Volume LevelUniversal, Linear P050 = Universal, Curved P050 = Maximum Process SpeedApplication Examples Ment P728 Shot Delay s P803Parameter P003 ValueMaterial Level Example 1 Level MeasurementWhen satisfied with system performance and programming NumberInstructions P051 Max Volume Enter 1457 for 1457 m Material VolumeExample 2 Space Measurement Description InstructionsNo entry required. preset for 20 mA = low level, P001 = P001 P002 P003 P004 P005 P006 P007 P070P200 MA Range P213 MA Max Limit P219 MA Failsafe Application Assistance Communication SupportReference Number TechnicalMT-00 Measurement Message Technical Reference Field NameDefinition MT-01 Hold Message # # = rate alarm = band alarmTemp Percent End Of Message Start of message Message typeStart of message MT-03 Point Not ScannedMessage Type Point # End Of Message STX $02Maintenance MaintenanceUnit Repair and Excluded Liability Troubleshooting Guide Symptom Cause ActionTroubleshooting To update the value displayed after each aiming adjustment To display Echo Confidence in the RUN modeMeasurement Difficulties Flashing LOE DisplayFixed Reading Wrong Reading Troubleshooting Programming Charts Programming ChartsName P000 Lock GP330 Profile Record P331 Auto Record Enable G P332 P116 Bound Alarm Deadband P129 Relay FailsafeP200 MA Range P201 P202 MA Allocation P203Programming Charts Parameter Advanced Echo Processing 7ml19985BE02