Liebert Interceptor® II Surge Suppression 160kA - 1000kA.

Connection Type

Parallel Connected

Agency Listings

UL1449, UL1283, cUL, FCC Part 15 Class B

 

 

 

Operating Voltage Range

+ / - 15%

 

Fault Current Rating (AIC)

200kAIC

 

 

 

Operating Frequency Range

47 - 63 Hertz

50 ohm EMI/RFI Attenuation

100kHz

41 dB

 

1MHz

31 dB

 

10MHz

35 dB

 

100MHz

53 dB

Protection Modes

All applicable modes standard (Line to Neutral, Line

 

to Ground, Neutral to Ground and Line to Line)

Response Time

<0.5 nanoseconds

 

 

Temperature

-40 to +60 degrees C

Operating Humidity

0% to 95% noncondensing

 

 

Status Indication

LEDs, Dry Contacts, Audible Alarm

Enclosure

NEMA 4 standard

 

 

Altitude

0 to 18,000 feet

Audible Noise

Less than 45 dBa

 

 

Warranty

10-Years Parts and 5-Years On-Site Labor

 

 

 

NEMA LS 1 Test Data (without disconnect/with disconnect)

System

 

B3

6kv/500A

B3/C1

C3

Voltage

Mode

Ringwave

Comb.Wave

Comb.Wave

Comb.Wave

120/208

L-N

328/344

308/312

376/376

452/536

 

 

 

 

 

 

120/208

L-G

340/348

320/316

364/368

444/584

120/208

L-L

464/448

576/568

680/652

792/832

 

 

 

 

 

 

120/208

N-G

344

284

344

468

277/480

L-N

520/536

532/528

800/800

912/952

277/480

L-G

736/760

688/688

760/776

840/896

277/480

L-L

736/776

720/728

1480/1416

1656/1600

 

 

 

 

 

 

277/480

N-G

736

648

760

896

 

 

 

 

 

 

UL 1449 Clamping Data (Second Edition)

System Voltage

L-N

L-G

N-G

L-L

120/240

330V

400V

400V

600V

120/208

 

 

 

 

 

 

 

 

 

240

N/A

800V

N/A

800V

230/400

700V

800V

600V

1200V

277/480

 

 

 

 

 

 

 

 

 

480

N/A

1200V

N/A

1500V

 

 

 

 

 

How To Specify The Appropriate Model:

All Liebert Interceptor II model numbers begin with the SI prefix. Use Chart A to build your Liebert Interceptor II starting with the Surge Rating column. Moving left to right, choose the correct configurations from each column for your application. Your completed model number should look similar to the example below or SI016120YARDE. Refer to Chart B for Liebert Interceptor II dimensional data.

Chart A – Liebert Interceptor® II Model Selection

 

 

 

 

 

 

 

 

EXAMPLE

 

 

 

 

 

 

 

 

SI

 

0 1 6

 

1 2 0

 

Y

 

A

 

 

R

 

D

 

 

E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Interceptor

Choose

 

Choose

 

Choose

 

Choose

 

Choose

 

Choose

 

Choose

Series

Surge Current

 

Voltage

 

Voltage

 

Modes of

 

Type of

 

Monitoring

Enclosure

 

Rating

 

(L-G)

 

Configuration

 

Protection

Connection

 

Option

 

Type

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Code

Code

 

 

Code

 

Code

 

 

Code

 

Code

 

Code

 

Code

 

SI

016

 

160kA

 

120

120V

N

1 Phase L-N 2+W+GND

 

A

All

N

Wire Lugs

S

Standard Monitoring

E

 

NEMA 4

 

025

 

250kA

 

208

208V

L

1 Phase L-L 2W +GND

 

*Other modes

R

Disconnect

 

LEDs, Audible Alarm,

N

 

Caseless

 

 

 

 

 

 

 

 

 

 

of protection

 

 

 

Form C Contacts

 

 

 

 

032

 

320kA

 

220

220V

S

Split Phase 3W+GND

 

 

 

 

*Other enclosure

 

 

 

 

available; Call

 

 

C

Standard Monitoring

 

040

 

400kA

 

230

230V

Y

3 Phase Wye 4W+GND

 

 

 

options available;

 

 

 

 

factory.

 

 

 

 

 

 

 

 

 

 

 

Plus Single Surge

Call factory.

 

050

 

500kA

 

240

240V

D

3 Phase Delta 3W+GND

 

 

 

 

 

 

Counter

 

 

 

 

060

 

600kA

 

277

277V

X

3 Phase Wye 3W+GND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D

Standard Monitoring

 

 

 

 

075

 

750kA

 

480

480V

H

3 Delta Hi-Leg 4W+GND

 

 

 

 

 

 

Plus Dual Surge and

 

 

 

 

100

 

1000kA

 

 

 

 

 

 

 

 

 

 

 

Swell Counters

 

 

 

Chart B – Liebert Interceptor® II Dimensional Data

Surge

Connection

A

B

C

D

E

F

Weight

160kA

Wire lugs

16

12

9

17.25

9.5

0.44

35

250kA

Disconnect

16

16

9

17.25

10

0.44

45

 

 

 

 

 

 

 

 

 

320kA

Wire lugs

16

12

9

17.25

9.5

0.44

45

500kA

Disconnect

16

16

9

17.25

10

0.44

55

600kA

Wire lugs

20

16

9

21.25

10

0.44

55

750kA

Disconnect

20

20

9

21.25

14

0.44

85

1,000kA

Wire lugs

20

20

9

21.25

14

0.44

85

Disconnect

20

24

9

21.25

18

0.44

95

 

 

 

 

 

 

 

 

 

F

A D

E

 

B

C

3

Image 3