SP-6TVN Specifications
AC Power Protection
Nominal Operating Voltage |
| 120 VAC, Single Phase |
|
Operating Voltage Range |
| 120 VAC +/- 10% |
|
Operating Frequency Range |
| 47 – 63 Hz |
|
Rated Output (Amps) |
| 15 Amperes |
|
ANSI/IEEE C62.41 Category |
| Category A & B |
|
Connection Type |
| (6) 5- 15R Receptacles and 5- 15P Plug |
|
Phase Configuration |
| 2 Wire + Gnd |
|
Size |
| 7.5 x 4.75 x 1.75 (Inches) |
|
Enclosure |
| High Impact Plastic |
|
Weight |
| 2.0 lbs. (0.9 kgs.) |
|
Modes Of Protection |
| L – N, L – G, N – G |
|
Indication of Suppression Status |
| Status Indicator |
|
Response Time |
| < .5 ns Normal mode |
|
Certifications |
| UL 1449 Listed |
|
Warranty |
| 5 Year |
|
Maximum Continuous Operating Voltage (MCOV) |
|
| |
Line to Neutral |
| 130 VAC |
|
Peak Surge Current (8 x 20ms) |
|
|
|
Line to Neutral |
| 13,000 Amps |
|
Line to Ground |
| 13,000 Amps |
|
Neutral to Ground |
| 13,000 Amps |
|
Total |
| 39,000 Amps |
|
ANSI/IEEE C62.41 Cat A Ringwave (6 kV, 200A, 100 kHz) |
|
| |
Normal Mode |
| 265 V |
|
Common Mode |
| 290 V |
|
ANSI/IEEE C62.41 Cat B Ringwave (6 kV, 500A, 100 kHz) |
|
| |
Normal Mode |
| 275 V |
|
Common Mode |
| 290 V |
|
Frequency Response |
|
|
|
Normal Mode | 60 dB Maximum, forward/reverse, 100 kHz to 50 MHz |
| |
Common Mode | 40 dB Maximum, forward/reverse, 5 MHz to 50 MHz |
| |
Low Voltage Protection | Video 1 & 2 | Phone | Network |
Connection Type | Type “F” | Type RJ11 | Type RJ45 |
Cables Provided | 6’ (2x) Type “F” ends | 6’ RJ11 Male Ends | 6’ RJ45 Male Ends |
Peak Surge Current | 5kA (8x20us) | 2kA (10x1000us) | 3kA (8x20us) |
Capacitance | <12pf | <50pf | <70pf |
Protection Level | |||
Clamping Voltage (DC) | 145V | 30V | |
Attenuation | 1db @ 2Ghz | N/A | N/A |
The
Headquarters
Surge Protection
328 Water Street
Binghamton, NY 13901
T:
T:
F:
1805 N.E. 19th Avenue
Ocala, FL 34470
T:
T:
F:
10020 E. Knox Avenue
Suite 50
Spokane Valley, WA 99206
T:
T:
F:
Technical Support
800 288 6169 Toll-Free
607 721 8865 Phone
607 722 8713 Fax
While every precaution has been taken to ensure accuracy and completeness in this literature, Emerson Network Power assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
© 2008 Emerson Network Power. All rights reserved throughout the world. Specifications subject to change without notice.
All names referred to are trademarks or registered trademarks of their respective owners.
Emerson Network Power.
The global leader in enabling
Business-Critical Continuity™.
AC Power
Connectivity
DC Power
Embedded Computing
Embedded Power
Monitoring
Outside Plant
Power Switching & Controls
Precision Cooling
Racks & Integrated Cabinets
Services