C6097A,B PRESSURE SWITCHES
| Table 2. Switch Ratings (Amperes) | ||
|
| ||
| 120/240 Vac, 50/60 Hz | ||
|
|
|
|
Inductive |
| Full Load | 3.0 |
|
|
|
|
|
| Locked Rotor | 18.0 |
|
|
|
|
Resistive |
|
| 5.0 |
|
|
|
|
Table 3. Alternate Electrical Ratings when used with
Honeywell Flame Safeguard Programmers.
Device | Rating | |
Ignition Transformer | 540 VA | |
Pilot Valve | 50 VA | |
Main Valve | 400 VA with | |
27/32 (22) HOLE | ||
| ||
| (57) | |
| ||
| (32) | |
5/8 (16) | ||
1/32 | ||
| ||
(1) | ||
PRESSURE INLET | INDICATOR | |
| 2 | |
| (52) |
TERMINAL DIAGRAM |
|
|
|
| 2 (52) |
|
|
|
|
| |||||||
|
|
|
|
| |||||||||||||
|
|
|
|
|
|
|
|
| |||||||||
| 1 | 2 |
|
|
| 3 |
|
|
|
|
|
|
|
|
|
|
|
|
| NO |
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
| COM |
|
|
|
|
|
|
|
|
| ||
|
| NC |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| P |
|
|
|
|
|
|
| M17124 | |||||||
|
|
|
|
|
|
|
|
|
|
|
Fig. 2. C6097 Flange Mount dimensions in in. (mm).
INSTALLATION
When Installing this Product...
1.Read these instructions carefully. Failure to follow them can damage the product or cause a hazardous condition.
2.Check the ratings given in the instructions and on the product to make sure that the product is suitable for your application.
3.Installer must be a trained, experienced service technician.
4.After installation is completed, check out product operation as provided in these instructions.
WARNING
Electrical Shock Hazard.
Can cause serious personal injury or death.
Disconnect power supply before beginning installation. More than one disconnection can be involved.
Mounting
NOTE: On flange models, remove the label holding the
The C6097 models allow NPT or flange (directly to valve) mounting. The NPT models have a hexagonal fitting with a 1/4 in. NPT tapping, which is the high pressure connection, in differential applications. The bleed fitting is 1/8 in. NPT tapped. In differential pressure control applications using air only, connect the lower pressure to the bleed fitting. See Fig. 1 and Table 1. In applications using combustible gases, vent the bleed tapping according to applicable standard code or jurisdictional authority.
C6097 models with flange mount can be fitted directly to Honeywell Integrated Valve Train (model specific). See Fig. 2 and Table 1. The flange mount models vent internally, with no external tap.
Mount the C6097A,B in any position.
Leak Check
After installation, perform a leak check on the pressure switch:
1.Turn on main gas. Make sure gas has reached the pressure switch (e.g., high gas pressure switch)
2.Check installation for gas leaks using a gas leak detector or a soap solution.
WARNING
Explosion or Fire Hazard.
Can cause severe personal injury, death or property damage.
Observe all safety requirements each time a control is installed on a burner.
4 |