C6097A,B PRESSURE SWITCHES

 

Table 2. Switch Ratings (Amperes)

 

 

 

120/240 Vac, 50/60 Hz

 

 

 

 

Inductive

 

Full Load

3.0

 

 

 

 

 

 

Locked Rotor

18.0

 

 

 

 

Resistive

 

 

5.0

 

 

 

 

Table 3. Alternate Electrical Ratings when used with

Honeywell Flame Safeguard Programmers.

Device

Rating

Ignition Transformer

540 VA

Pilot Valve

50 VA

Main Valve

400 VA with 2-1/2 times inrush.

27/32 (22) HOLE

2-21/32 (68)

 

2-1/4

 

(57)

 

1-1/4

 

(32)

5/8 (16)

2-23/32 (69)

1/32

 

2-23/32 (69)

(1)

PRESSURE INLET

INDICATOR

 

2

 

(52)

TERMINAL DIAGRAM

 

 

 

 

2 (52)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COM

 

 

 

 

 

 

 

 

 

 

 

NC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P

 

 

 

 

 

 

 

M17124

 

 

 

 

 

 

 

 

 

 

 

Fig. 2. C6097 Flange Mount dimensions in in. (mm).

INSTALLATION

When Installing this Product...

1.Read these instructions carefully. Failure to follow them can damage the product or cause a hazardous condition.

2.Check the ratings given in the instructions and on the product to make sure that the product is suitable for your application.

3.Installer must be a trained, experienced service technician.

4.After installation is completed, check out product operation as provided in these instructions.

WARNING

Electrical Shock Hazard.

Can cause serious personal injury or death.

Disconnect power supply before beginning installation. More than one disconnection can be involved.

Mounting

NOTE: On flange models, remove the label holding the O-ring in place and make sure O-ring seal is in place before mounting the pressure switch on the valve.

The C6097 models allow NPT or flange (directly to valve) mounting. The NPT models have a hexagonal fitting with a 1/4 in. NPT tapping, which is the high pressure connection, in differential applications. The bleed fitting is 1/8 in. NPT tapped. In differential pressure control applications using air only, connect the lower pressure to the bleed fitting. See Fig. 1 and Table 1. In applications using combustible gases, vent the bleed tapping according to applicable standard code or jurisdictional authority.

C6097 models with flange mount can be fitted directly to Honeywell Integrated Valve Train (model specific). See Fig. 2 and Table 1. The flange mount models vent internally, with no external tap.

Mount the C6097A,B in any position.

Leak Check

After installation, perform a leak check on the pressure switch:

1.Turn on main gas. Make sure gas has reached the pressure switch (e.g., high gas pressure switch)

2.Check installation for gas leaks using a gas leak detector or a soap solution.

WARNING

Explosion or Fire Hazard.

Can cause severe personal injury, death or property damage.

Observe all safety requirements each time a control is installed on a burner.

65-0237—1

4

Image 4
Contents Features Application ContentsSpecifications Ordering InformationPressure Switch Model Selection Installation When Installing this ProductSwitch Ratings Amperes MountingSettings and Adjustments WiringPressure Setpoint Adjustment Manual Resetting Operation and CheckoutOperation Checkout65-0237-1 Home and Building Control