Siemens PCS 7 manual Basic cabinet, Mechanical design, Options for the mechanical design

Page 3

SIMATIC PCS 7 cabinet design

Basic cabinet

Overview

The Siemens standard cabinet 8MC is the preferred basic cabi- net. The Siemens standard cabinet 8MC is a sheet-steel cabinet with rear panel and front door which can be assembled individ- ually or also in rows with further cabinets of this type.

Side walls and partitions are optional, thus permitting variable adaptation of the cabinet to different installation possibilities.

Up to four system units or six I/O units can be fitted in a cabinet in conjunction with a DC 24 V or AC 230 V power supply assem- bly. System and I/O units can also be combined together within a cabinet. The cables are introduced into the cabinet from be- low.

Mechanical design

Each delivered cabinet contains:

19-inch mounting frame

Rear panel

Door

Transport lugs

Clips for routing of process cables

Cable duct for cabinet-internal wiring

Options for the mechanical design

When ordering the basic cabinet, the following options are avail- able for the mechanical design of the cabinet:

Plinth: a cabinet plinth should be used if cables cannot be con- nected through the floor. The plinths are preassembled, and available with a height of 100 or 200 mm

Pocket for documents

Trim

Side walls/partitions: the basic cabinets are suitable for individ- ual assembly or in rows. Therefore side walls and/or partitions can be selected when ordering.

Electrical design

Each delivered cabinet contains:

Power supply assembly AC 230 V or DC 24 V

Cable clamps and screen bars for I/O and bus cables

Prewiring of power supply cables for central and I/O units

Wiring of PROFIBUS-DP fieldbus

Connector board for cabinet earth

Options for the electrical design

AC 230 V socket (installed in power supply assembly)

I & C monitoring (2 versions):

-I & C monitoring via cabinet lamp. A blown fuse is signalled by a lamp in the cabinet door. OLM failure can be additionally displayed on the cabinet lamp

or

-I & C monitoring via AS 488/TM and cabinet lamp. Tempera- ture violations in the cabinet, an open door contact, a blown fuse and an OLM failure can be recorded by the IF 961-DIO interface module and additionally signalled by a lamp in the cabinet door

-Single/redundant design of power supply assembly, option- ally with 6 or 14 circuit-breaker receptacles

Cabinet illumination

Preparation of quotation, consulting and ordering

Siemens AG

D-76187 Karlsruhe

Tel.: +49 721 595-3776

Fax: +49 721 595-4711

E-mail: helmut.heib@siemens.com

Technical Specifications

Siemens standard cabinet

Dimensions (H x W x D) in mm

2000 x 800 x 400

Framework, completely welded

Sheet-steel, 2 mm,

 

frame profile with 10 edges,

 

cross-member profile with 5

 

edges

 

 

Rear panel

Sheet-steel, 1.5 mm, canted

 

 

Roof

Sheet-steel, 1.5 mm, canted

 

 

Side wall (option)

Sheet-steel, 1.5 mm, canted

 

 

Partition (option)

Sheet-steel, 1.5 mm, canted

 

 

Single-leaf door on front of cabinet

Sheet-steel, 1.5 mm,

with hinge on right

opening angle approx. 180°;

 

including rod lock with 3 mm lock

 

insert and double-barb key

 

DIN 43 668

 

 

Degree of protection to EN 60 529

IP 40, with single installation or

 

together with cabinets of the

 

same type

 

 

Color

Ergo gray to

 

SN 30 920-C611-B13

 

 

Permissible ambient temperature

Max. 40 °C

 

 

Permissible temperature inside

Max. 55 °C

cabinet

 

 

 

Permissible heat dissipation with-

350 W, referred to maximum val-

out fan

ues of ambient temperature and

 

temperature inside cabinet

Siemens PLT 112 · 2002

6/3

Image 3
Contents Introduction Simatic PCS 7 cabinet designCabinet packaging system Electrical design Basic cabinetMechanical design Options for the mechanical designHot swapping Power supplyLoad power supply for I/O modules ET 200M I/O unitAS 488/TM system unit Simatic PCS 7 cabinet design
Related manuals
Manual 23 pages 35.78 Kb