SIMATIC PCS 7 cabinet design
Basic cabinet
■Overview
The Siemens standard cabinet 8MC is the preferred basic cabi- net. The Siemens standard cabinet 8MC is a
Side walls and partitions are optional, thus permitting variable adaptation of the cabinet to different installation possibilities.
Up to four system units or six I/O units can be fitted in a cabinet in conjunction with a DC 24 V or AC 230 V power supply assem- bly. System and I/O units can also be combined together within a cabinet. The cables are introduced into the cabinet from be- low.
Mechanical design
Each delivered cabinet contains:
•
•Rear panel
•Door
•Transport lugs
•Clips for routing of process cables
•Cable duct for
Options for the mechanical design
When ordering the basic cabinet, the following options are avail- able for the mechanical design of the cabinet:
•Plinth: a cabinet plinth should be used if cables cannot be con- nected through the floor. The plinths are preassembled, and available with a height of 100 or 200 mm
•Pocket for documents
•Trim
•Side walls/partitions: the basic cabinets are suitable for individ- ual assembly or in rows. Therefore side walls and/or partitions can be selected when ordering.
Electrical design
Each delivered cabinet contains:
•Power supply assembly AC 230 V or DC 24 V
•Cable clamps and screen bars for I/O and bus cables
•Prewiring of power supply cables for central and I/O units
•Wiring of
•Connector board for cabinet earth
Options for the electrical design
•AC 230 V socket (installed in power supply assembly)
•I & C monitoring (2 versions):
-I & C monitoring via cabinet lamp. A blown fuse is signalled by a lamp in the cabinet door. OLM failure can be additionally displayed on the cabinet lamp
or
-I & C monitoring via AS 488/TM and cabinet lamp. Tempera- ture violations in the cabinet, an open door contact, a blown fuse and an OLM failure can be recorded by the IF
-Single/redundant design of power supply assembly, option- ally with 6 or 14
•Cabinet illumination
Preparation of quotation, consulting and ordering
Siemens AG
Tel.: +49 721
Fax: +49 721
■Technical Specifications
Siemens standard cabinet
Dimensions (H x W x D) in mm | 2000 x 800 x 400 |
Framework, completely welded | |
| frame profile with 10 edges, |
| |
| edges |
|
|
Rear panel | |
|
|
Roof | |
|
|
Side wall (option) | |
|
|
Partition (option) | |
|
|
with hinge on right | opening angle approx. 180°; |
| including rod lock with 3 mm lock |
| insert and |
| DIN 43 668 |
|
|
Degree of protection to EN 60 529 | IP 40, with single installation or |
| together with cabinets of the |
| same type |
|
|
Color | Ergo gray to |
| SN 30 |
|
|
Permissible ambient temperature | Max. 40 °C |
|
|
Permissible temperature inside | Max. 55 °C |
cabinet |
|
|
|
Permissible heat dissipation with- | 350 W, referred to maximum val- |
out fan | ues of ambient temperature and |
| temperature inside cabinet |