Canon 2000 manual Retrotec Gauge and System Calibration, Gauge calibration procedure

Page 47

Retrotec Gauge and System Calibration

All Retrotec Gauges are calibrated against a Master Reference Calibrator (MRC) that has an accuracy of +/-0.1 Pa or 0.1 %. The concept Retrotec equipment uses is that all of Retrotec’s products are now calibrated against the same reference. When a blower is built, it is calibrated against the MRC for pressure and an ASTM flow chamber for holes. A correction formula is derived for that blower to eliminate all the error. Each gauge used in a system, is calibrated against the MRC also and correction equations are derived that will allow for correction over the entire range. The Retrotec software will have the correction equations for each gauge and blower embedded in the software so all readings are corrected automatically.

For every door fan reading, three calibration corrections occur in the software;

1.the room gauge reading,

2.the flow gauge reading and

3.the blower itself.

Additional corrections:

4.Each flow pressure reading is corrected when the flow is towards the operator to reduce the flow pressure by the room pressure to properly reference the reading.

5.Each flow reading is corrected for temperature.

6.Barometric pressure is not corrected for because to do so would reference the reading to local ambient conditions at the time of the test. Rather, flows are referenced to STP conditions which are: 101,325 KPa, 50% relative humidity and 20C. Humidity can be ignored because its effect is negligible.

Gauge calibration procedure

When the Retrotec CA2001 software is created, a calibration certificate records all correction formula that are then used in the software. Only Retrotec can compile these certificates but it is possible to have local instrument companies perform the calibration. Retrotec will then take their data and create the calibration certificate that can be emailed or mailed in a small text file. This file is imported into the Retrotec software to allow CA2001 to perform all the corrections automatically. The software allows the operator to select the certificate that can be used for any particular test. Normally the operator would use the latest calibration certificate but there are two cases where another certificate may be used:

1.Change back to an old certificate to rework or rerun old data in the form of a new test. Old tests will retain the calibration information along with the test so no change would have to be made unless a new test was run.

2.If different blower and/or gauge combinations were used, a different calibration certificate can be utilized by using the “Change” button on the Home tab. Each one of these combinations requires a separate certificate that can be sent by Retrotec upon request.

2000 Fire Door-Fan Manual

updated 2002-05-28

Page 47 of 58

Image 47
Contents Fire Door-Fan Manual Fire Door-Fan ManualRun from CA2001 Single Blower Panel Set Up Fire Door-Fan Manual Fire Door-Fan Manual Power to console comes from Set up Model N digital consoleFire Door-Fan Manual OR, Model L digital control panel for Models L64 and L63 Screwdriver supplied. Do not turn more than 3 turns OR, Model E analog gauge clipOR, DM-1 digital gauge for models J64 Fire Door-Fan Manual Fire Door-Fan Manual Fire Door-Fan Manual Fire Door-Fan Manual Large room testing with 2 Blowers Or, E43 Aluminum Frame Set Up Fire Door-Fan Manual Leak Check Smoke test & measure static pressure Changing Ranges Select Blower RangePrinciples of Infiltrometer Air Flow Measurement Cannot Achieve Desired Room Pressure with Plate Off Range Selection ProcedureRange Selection When Conducting a Single Point Nfpa Test Range Selection When Conducting a Multi-Reading TestFlow Range Diagram Updated Gauge Reading Rules Room and Flow Pressure ReadingsAnalog Gauge Readings Tubing ConnectionsTaking Readings from Two Blowers Gauge readingsFor models N64, N63, L64, L63, J64, J63 Model DM-1 Digital GaugeTips Time AveragingFire Door-Fan Manual Updated View from outdoors Windy ConditionsUse averaging on digital gauge to reduce the effect of wind Deluxe Wind Damping System to Stop Gauge Needles Moving Fire Door-Fan Manual Increase agent quantity? Enclosures with excessive leaksEnclosures with excessive upper leaks Reduce the Minimum Protected Height Improper training of testing technicianEliminate Static pressure during retention Reduce High Static Pressures if presentFlex duct installation for ceiling neutralization Ceiling tile is removed to allow the flex duct to be mounted Lower leak tests using Plastic-on-Ceiling procedure Fastest Way to Seal the Ceiling or Register Grilles Conducting the TestLower leak Estimates using Leak audit Field calibration check with calibration plate Fire Door-Fan Manual Tall doorways Packing up and moving equipment Fire Door-Fan Manual Large building Testing Recalibration of Retrotec Infiltrometer Retrotec Gauge and System Calibration Gauge calibration procedureAscending pressure Descending Pressure Final pressure Pa Analog Room gauge target pressuresFire Door-Fan Manual BJ30 Self Test Print Troubleshooting, Maintenance, RepairFire Door-Fan Manual BJ30 Print Head Cleaning Balancing Indoor/Outdoor Temperature Readings Fire Door-Fan Manual Possible Mechanical Problems Fire Door-Fan Manual Repairs, Warranty and Customer Support Possible Electrical ProblemsCleaning Customer Support Returning Items for Factory Service
Related manuals
Manual 4 pages 7.79 Kb Manual 6 pages 43.98 Kb Manual 11 pages 16.03 Kb

2000 specifications

The Canon EOS 2000D, also known as the Rebel T7 in some regions, is an entry-level DSLR that caters to beginners and amateur photographers looking to explore the world of digital photography. Launched as a successor to the EOS 1300D, the 2000D brings a host of features and technologies that make it an appealing choice for those stepping up from smartphone photography.

One of the standout characteristics of the Canon 2000D is its 24.1-megapixel APS-C CMOS sensor. This high-resolution sensor enables users to capture stunningly detailed images with vibrant colors and rich tonal range. Coupled with the DIGIC 4+ image processor, the camera delivers improved performance in terms of image quality, low-light capability, and overall processing speed.

The Canon 2000D features a 9-point autofocus system that includes one cross-type point, helping users achieve accurate focus on subjects. While this autofocus system may not be the most advanced in the market, it is sufficient for general photography tasks, including portraits, landscapes, and even some action shots.

The camera boasts a 3-inch LCD screen, which provides a clear interface for composing shots and navigating settings. Although it lacks a touchscreen, it offers straightforward usability that appeals to novice photographers learning the ropes of DSLR operation. The optical viewfinder with approximately 95% coverage allows users to view scenes through the lens for precise framing.

For those interested in videography, the 2000D offers Full HD 1080p video recording at 30 frames per second. While it may not excel in advanced video features, it provides a solid entry point for hobbyists looking to experiment with video content. The presence of built-in Wi-Fi and NFC capabilities allows for easy sharing of images and remote control of the camera via a smartphone app, enhancing the overall user experience.

Additionally, the Canon 2000D supports a range of Canon's EF and EF-S lenses, providing users with the flexibility to explore various photography styles. Its compact and lightweight design makes it highly portable, making it a great companion for travel and everyday photography.

Overall, the Canon 2000D is a versatile and user-friendly DSLR that strikes a balance between image quality, functionality, and ease of use, making it an excellent choice for those embarking on their photographic journey.