Rockwell Tools 1756-M03SE, 1756-M08SE manual Specifications, Description Value

Page 15

ControlLogix SERCOS interface Module 15

Specifications

Description

Value

 

 

Power Dissipation

5.0W

 

 

Backplane

760 mA @ 5.1V dc

Current

 

 

2.5 mA @ 24V dc

 

 

 

Operational

IEC 60068-2-1 (Test Ad, Operating Cold),

Temperature

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

 

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

 

0 to 60°C (32 to 140°F)

 

 

Storage

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),

Temperature

IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),

 

IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal Shock):

 

-40 to 85°C (-40 to 185°F)

 

 

Relative Humidity

IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp Heat):

 

5 to 95% non-condensing

 

 

Vibration

IEC 60068-2-6 (Test Fc, Operating):

 

2g @ 10-500Hz

 

 

Operating Shock

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

 

30g

 

 

Non-Operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

Shock

50g

 

 

Emissions

CISPR 11:

 

Group 1, Class A

 

 

ESD Immunity

IEC 61000-4-2:

 

4kV contact discharges

 

8kV air discharges

 

 

Radiated RF

IEC 61000-4-3:

Immunity

10V/m with 1kHz sine-wave 80%AM from 80MHz to 2000MHz

 

10V/m with 200Hz 50% Pulse 100%AM at 900Mhz

 

10V/m with 200Hz 50% Pulse 100%AM at 1890Mhz

 

 

Enclosure Type

None (open-style)

Rating

 

 

 

 

 

Publication 1756-IN572G-EN-P - May 2005

Image 15
Contents Before You Install the Module To control up to this many drivesTorque Important User Information ControlLogix Sercos interface ModuleSee Publication Number DocumentationInstall the Module How to Handle ControlLogix ComponentsPower Connect the Fiber Optic Cables ControlLogix Sercos interface Module Interpret the LED Indicators State DescriptionState Description Recommended Action Flashing Module Health and Communication Status OK Indicator Remove the Module from the Chassis, If Required Plastic cable Inches Fiber Optic Cables For use Use this type Allen-BradleyLength in meters inches Allen-Bradley Catalog Number Alcohols Aliphatics Other Care and Handling of Fiber Optic CablesDescription Value SpecificationsCycle time Data rateCertification Description CertificationsEnvironment and Enclosure Environment and Enclosure InformationExplosion Hazard North American Hazardous Location ApprovalRockwell Automation Support Installation Assistance