Checking Operation of Fire
Turn on the gas supply at the meter and to the appliance at the isolating cock. Purge the air from the appliance. Press and turn the gas control
To check the gas pressure at the appliance, allow the coals and the coal bed to cool and turn off the gas supply at the isolating cock, remove the hexagon headed screw and connect a manometer to the pressure test point. Turn on the gas and ignite the fire, allow to heat up and check that the gas pressure is 20 +/- 1 mbar any appreciable drop may indicate losses through pipework. The pressure test point may also be used to check for leakage of the joints to the appliance. Turn ‘OFF’ the gas supply to the fire, remove the pressure gauge, replace the screw and then turn the gas supply 'ON'. Fit the fire front.
Turn the gas control to the OFF position, wait for 90 seconds, fully depress the gas control, turn to the ignition position and release the control. Attempt to light the pilot with an already prepared match or taper. If the plot lights the FSD is faulty.
Spillage Check
The appliance should be run on high setting for at least 5 minutes prior to the test with the front and fret located in position. The test must be carried out with all windows and doors of the room closed, if an extractor fan is situated in the room, this test should be repeated with the fan running. If there is a connected room with an extractor fan, the test should be repeated with all the doors to that room opened and the extractor fan running. All smoke must be drawn into the flue. If spillage occurs, allow a further 10 minutes. Should spillage still occur examine the chimney for the fault and rectify.
Check for satisfactory clearance of products by positioning a lighted smoke match central to the opening 120mm down from the canopy and level with the rear edge of the front simulated coal. See Fig. 6A.
Demonstrate the lighting and extinguishing procedures to the user.
Advise that:
The curing effect of heating the coals will cause an initial odour which, although not harmful, may require additional ventilation until the odour has disappeared.
Any debris or soot is cleaned from the appliance. Advise the customer that they should read their Users Instructions before operating the fire and always follow the advice in the section headed `Removal of Debris or Soot Deposits'. The appliance must be serviced annually by a competent person in accordance with these instructions.
Advise that the appliance is fitted with an
Complete the section in the enclosed registration leaflet. Advise that any component part of this appliance be guaranteed against defective workmanship or faulty materials for a period of twelve months from the date of purchase.
Any such part will be replaced free of charge on receipt of the purchaser’s address at the cost of postage only, provided that:
•It is accompanied by the registration section cut out of the booklet, together with the original purchase receipt, which will be returned with the replacement part.
•Any installation, repairs or adjustments have been carried out by a competent person, such as the supplier’s representative or a CORGI registered installer.
Page 8