Desa (V)TC36N, (V)TC36P Venting Installation Instructions, Installation Precautions

Page 7

VENTING INSTALLATION INSTRUCTIONS

Installation Precautions

7

VENTING INSTALLATION INSTRUCTIONS

NOTICE: Read these instructions completely before attempting installation.

These models are tested and approved for use with DESA (direct- vent) pipe components and terminations.

The venting system must terminate on the outside of the structure and can not be attached to a chimney or flue system serving a separate solid fuel or gas burning appliance. A direct-vent appliance must have its own venting system. DO NOT common vent this appliance.

These models are approved to be vented either horizontally through an outside wall or vertically through a roof or chase enclosure using the following guidelines:

When venting system terminates horizontally on an outside wall, you may install a standoff if the termination cap is to be installed directly on a combustible finish such as vinyl, wood, stucco, etc.

Never run the vent downward as this may cause excessive tem- peratures which could cause a fire.

Vent pipe air space clearances to combustibles are 1" on all sides except on the horizontal sections, which requires 2" clearance from the top of the pipe. Where the termination cap penetrates a combustible wall, 1" air space clearance is required.

Snorkel terminations are required when minimum clearance to grade cannot be met (see Figure 16 on page 11).

Have fireplace and selected vent components on hand to help determine the exact measurements when elbowing or offsetting. Always use wall firestops when penetrating walls and firestops when penetrating ceilings or attic spaces.

Install horizontal venting with a 1/4" rise for every 12" of run toward the termination.

WARNING: Read all instructions completely and thoroughly before attempting installation. Failure to do so could result in serious injury, property damage or loss of life.

NOTICE: Failure to follow these instructions will void the warranty.

NOTICE: Do not seal termination cap to vent pipe. Cap must be removable for vent inspection and maintenance.

INSTALLATION PRECAUTIONS

Wear gloves and safety glasses for protection

Use extreme caution when using ladders or when on roof tops

Be aware of electrical wiring locations in walls and ceilings

The following actions will void the warranty on your venting system:

Installation of any damaged venting component

Unauthorized modification of the venting system (Do not cut or alter vent components)

Installation of any component part not manufactured or approved by DESA

Installation other than as instructed by these instructions

WARNING: This gas fireplace and vent assembly must be vented directly to the outside. The venting system must NEVER be attached to a chimney serv- ing a separate solid fuel burning appliance. Each direct-vent gas appliance must use a separate vent system. Do not use common vent systems.

WARNING: Vent pipe air space clearances to com- bustibles are 1" on all sides except on the horizontal sections, which require 2" clearances from the top of the pipe. Where the termination cap penetrates a com- bustible wall, 1" air space clearance is required.

116192-01C

www.desatech.com

Image 7
Contents For Your Safety What to do if YOU Smell GAS For Your SafetySave this manual for future reference Safety Information Table of ContentsLocal Codes Safety Information Product Identification PRE-INSTALLATION Preparation Product Features Location and Space Requirements Framing and Finishing ClearancesTermination CAP AIR Supply Inlet GAS Meter Location of Termination CAPInstallation Precautions Venting Installation InstructionsHorizontal Termination Installation Installation PlanningInstalling Siding Standoff Combustible Vertical Horizontal H Horizontal Termination ConfigurationsCorner Installation Venting with Two 90 Elbows Horizontal System Installation Using TWO ElbowsFlat Ceiling Installation Installation for Vertical TerminationVenting with One 90 Elbow Vertical Termination ConfigurationsVertical Venting High Altitude InstallationCheck GAS Type Venting InstallationFireplace Installation Installing Optional Blower AccessoriesBlower see Figure Model BKT InstallationBlower Wiring Diagram Installing GAS Piping to Fireplace LocationInstallation Items Needed Checking GAS Connections Connecting Fireplace to GAS SupplyOr servicing. Correct all leaks at once Pressure Testing Fireplace Gas Connections Installing Optional Wall Mount Switch GWMS2REMOVING/REPLACING Glass Door Installing Remote ReceiverRemoving Louver Panels Cleaning Glass Door Installing Lava Rock and Glowing EmbersRemoving Glass Doors Lighting Instructions Installing Brick Liner Models BL36DASA and BL36DHASAFor Your Safety Read Before Lighting Operating FireplaceShutting Off Burners Only pilot stays lit Manual Lighting ProcedureTo Turn OFF GAS Optional HAND-HELD Remote OperationON/OFF Series Model Ghrcb Safety FeaturesManual Mode Auto Thermostatic ModeOperating Optional GWMT1 Wall Mounted Thermostat Operating Optional Blower AccessoryPilot Assembly Inspecting BurnersLogs Cleaning and MaintenanceGlass Door Pilot and BurnersObserved Problem Possible Cause Remedy TroubleshootingTions see Vent Installation Instruc Above Gas leak. See Warning statementSpecifications Replacement PartsService Hints Technical ServiceModels TC36N, VTC36N, TC36P and VTC36P Illustrated Parts BreakdownKEY Part Number TC36N/P VTC36N/P Description QTY Parts ListBurner Assembly for Models TC36N, VTC36N, TC36P and VTC36P KEY Part Number Description QTY Accessories Owners Registration Form Postage Required 116192-01C Warranty Information