11. Operation Control

11.1 Cooling Operation

11.1.1Outdoor fan control

šWhen cooling operation is enabled, based on outdoor ambient temperature, fan motor control will be adjusted according to figure below:

11.1.2Annual Cooling control

šThis control is to enable cooling operation when outdoor ambient temperature is low.

šControl start conditions:

o Cooling operation is activated with compressor ON. o Outdoor ambient temperature is less than 59°F

šControl contents:

o When the above conditions are fulfilled, based on outdoor pipe temperature, the outdoor fan motor will operate according to figure below:

šTo improve the judgment accuracy during annual cooling control, outdoor ambient temperature sampling for 2 minutes will be activated every 35 minutes under designated fan speed.

šControl stop conditions:

o When either one of the start conditions are not complied.

20

Image 20
Contents CU-2E18NBU Disassembly and Assembly Instructions Safety Precautions Page Specifications CU-2E18NBUš Multi split combination possibility Volume Dimensions Refrigeration Cycle Diagram Block Diagram Wiring Connection Diagram Electronic Circuit Diagram Printed Circuit Board Main Printed Circuit BoardPage Installation Information Check PointsOutdoor Unit Installation InstructionSelect The Best Location Install The Outdoor Unit Connect the PipingEvacuation of the Equipment Cutting and Flaring the PipingConnect The Cable To The Outdoor Unit Heat InsulationOperation Control Cooling OperationOutdoor fan control Annual Cooling controlPowerful Operation Heating OperationOperation mode priority control Simultaneous Operation ControlElectronic Parts Temperature Rise Protection 1 Cool Electronic Parts Temperature Rise Protection 2 CoolProtection Control Freeze Prevention control CoolCooling overload control Cool Heating overload control HeatTime Delay Safety Control Restart Control IPM power transistor Protection ControlDeice Control 13.10 30 seconds Force OperationCompressor discharge high pressure protection control Compressor Protection Control Gas leak detection controlValve close detection control Servicing Mode 14.1 CU-2E18NBUPump down operation SW1 Test Run operationWiring Error check Power Save ModeMode priority function Cooling only functionTroubleshooting Guide Self Diagnosis FunctionPage Page Disassembly and Assembly Instructions Outdoor Unit Removal ProcedureRemoving the Cabinet Top Plate and Cabinet Front Plate Remove the Control Board Cover and Particular PlatesRemoving the Control P.C. Board Removing the Propeller Fan and Fan MotorPage One Indoor Unit Operation Technical DataOperation Characteristics 133.000 128.000 100 105 110 115 Outdoor Air Temperature F š Piping Length Characteristic Cooling š Piping Length Characteristic Cooling š Heating Characteristic š Heating Characteristic š Piping Length Characteristic Heating š Piping Length Characteristic Heating Two Indoor Unit Operation CapacitykW š Cooling Characteristic š Piping Length Characteristic Cooling š Piping Length Characteristic Cooling š Piping Length Characteristic Cooling š Heating Characteristic š Heating Characteristic š Heating Characteristic š Piping Length Characteristic Heating š Piping Length Characteristic Heating š Piping Length Characteristic Heating Exploded View and Replacement Parts List REF. no Description & Name ’TY CU-2E18NBU Remark Accessory CO. Drain Elbow

CU-2E18NBU specifications

The Panasonic CU-2E18NBU is a highly efficient outdoor unit designed for residential and commercial applications, providing reliable heating and cooling year-round. This unit is part of Panasonic's extensive range of HVAC solutions, known for their innovation and energy efficiency.

One of the standout features of the CU-2E18NBU is its advanced inverter technology. This technology allows the system to adjust the compressor speed based on the temperature demand, resulting in reduced energy consumption and enhanced comfort. By continuously varying the output, the inverter system maintains a consistent indoor climate without the frequent on/off cycles typical of conventional systems. This not only saves energy but also extends the lifespan of the unit.

The CU-2E18NBU is designed to operate efficiently in a wide range of conditions, showcasing excellent performance in harsh climates. With a capacity of 18,000 BTU, it can efficiently cool or heat spaces effectively, making it suitable for medium-sized rooms or multiple areas when paired with compatible indoor units.

Another significant characteristic of this Panasonic model is its environmentally friendly refrigerant, R32. This refrigerant has a lower impact on global warming and ozone depletion compared to older options, making the CU-2E18NBU a smart choice for eco-conscious consumers. R32 also enhances the system's efficiency, further contributing to lower energy costs.

The unit features a robust construction, allowing it to withstand outdoor conditions while promoting durability. Its compact design allows for flexible installation options, making it easier to fit in various environments without compromising aesthetic appeal.

Moreover, the CU-2E18NBU incorporates advanced air filtration and purification technologies, improving indoor air quality. The filters are designed to capture dust, allergens, and other particulates, ensuring cleaner, healthier air.

In summary, the Panasonic CU-2E18NBU stands out for its efficient inverter technology, environmentally friendly refrigerant, and compact, durable design. With its ability to provide consistent temperature control and improve indoor air quality, this unit is a reliable solution for anyone looking to enhance their heating and cooling systems.