PC-Only Programmable Transmitter
Introduction
Models TX787 and TX788 are
Quick Start
Before beginning the process of setting up the transmitter, it is important to understand the difference between calibration and configuration. The transmitter’s precision references (4 and 20 milliamps out; resistance, voltage and current as appropriate; and a thermal reference) are calibrated at the factory and may be adjusted later if necessary. Configuration is the process of defining the sensor type and range in engineering units. Configuration is performed by connecting the transmitter to a PC and running the configuration software. Because the Communications Adapter provides power to the transmitter’s microprocessor, it is not necessary to provide any external power to the transmitter in order to configure it.
1.Install the Configuration and Calibration software
Run “setup.exe” on the distribution diskette and follow the
Note: the software contained on the distribution diskette runs under Windows 95 and Windows NT. If you are running Windows v3.1, contact Omega Engineering.
2.Connect the Communications Adapter to the computer and transmitter.
3.Identify the serial port to which the Adapter is connected.
Select “Options” from the menu bar, then click “Communications” and select the correct COMM port from the pull-
down menu. Note that if you change the serial port you must exit the software and restart | it with the correct setting. |
4. Configure the transmitter.
What you will need:
CalibrationConfiguration
• PC | • PC | |
• Communications Adapter | ||
• Communications Adapter | ||
• Transmitter | ||
• Transmitter | ||
• Multimeter | ||
| ||
• 24VDC power supply |
|
Calibration
To calibrate the transmitter, connect a 24VDC power supply, a 250Ω load and
1.Upload
2.Click on the Calibration Icon
3.Output Calibration: Select "Output 4mA", enter the mA reading from the meter into the dialog box and click "Send to Device." Repeat for 20mA calibration.
4A. Input Calibration Models
4B. Input Calibration Models
5.To calibrate the cold junction compensation reference, select “Tem- perature,” enter the nominal ambient temperature in the dialog box, set the input simulation type to match the input simulator (i.e., type J thermo- couple), verify that the simulator is set to the proper value, then click “Send to Device.”
6.Click “Close.” A message in the lower left corner of the screen will indicate the progress of the download and finally that the download has been successfully completed.
Configuration
Configuration may be performed with a transmitter
1.Upload Current configuration from the transmitter
2.Configure
•If the current “Sensor Type” does not match the application, click on the “Sensor Selection” box then select the appropriate “tab” at the top of the “Input Sensor Selection” screen.
•Make one selection from the “Input Connection” and “Type” boxes (if offered) for the selected sensor type. Leave the “Mode” as “Stan- dard” or the “Transfer Function” as “Linear” for now. Click the “OK” button to return to the Configuration Screen.
•Select the Engineering Units (from the pull down menu), enter the “Zero Scale” and “Full Scale” values and the “Burnout” mode (transmitter to go above full scale or below zero scale upon input failure).
•Click the "Set to Optimal" button to optimize the
transmitter's filtering.
3. Download New configuration to the transmitter.