Panasonic 6296 manual Fixed temperature alarm level, Latching, Atex classification, Label holder

Page 1

Fire alarm systems

Enclosed heat

detectors 6295, 6296,

6297 and 6298

Fixed temperature alarm level

ATEX compliance

Waterproof (IP67)

Fixed temperature alarm level

The detectors are conventional fixed temperature heat detectors, i.e. they will give an alarm within a response temperature range in accordance with EN54-5:2000.

The sensing element is a heat pick-up shield and a bimetal switch.

An LED on the detector (not on 6298) will light up when the detector goes into alarm. The detector also has an output for an external LED 2216 / 2217.

The following types are available (static response temperature, class & EN54-5 temp. range):

6295, 57°C, class A2 S (54 to 70°C).

6296, 72°C, class B S (69 to 85°C).

6297, 87°C, class C S (84 to 100°C).

6298, 117°C, class E S (114 to 130°C).

Latching

The detectors are latching, i.e. they will not be automatically reset if the temperature, after the alarm, falls below the detector's static response temperature. The detector's LED and a connected ext. LED will be lit until the detector is reset via the c.i.e.

ATEX classification

The detectors 6295 and 6296 complies with the ATEX classification Ex II 3GD EEx nA

IIT5. See also the opposite side of this page.

Waterproof connection box

The heat pick-up shield, the LED, all electronics, etc. are mounted in a grey water- proof detector housing, to be mounted on the attached connection box, which has three cable inlets. Three compression glands and a silicon gasket for IP67 are also attached.

Label holder

A label holder intended for a label showing "zone number", can be mounted in the connection box.

Miscellaneous

The detectors 6295-6298 are provided with three pairs of flying leads with female push- on connectors, see figure on the opposite side of this page. (Zone line cables (in / out) and an external LED.)

Product applications

The detectors can be used in the systems EBL500 / 512 / 128 / 1000 / 2000 provided with some zone line inputs for the system respectively (e.g. an 8 zones expansion board 1580 / 4580 input, an addressable zone interface 2226 / 2335 input, an addressable multi purpose I/O unit 3361 input, etc.).

Heat detectors are normally used in rooms where the temperature can be expected to rise rapidly in case of a fire or places where smoke detectors can not be used.

The detectors are intended for outdoor use or indoor use in high humidity premises.