Panasonic Explore the Features and Specifications of the 6295 Smoke Alarm

Page 2

 

 

Type numbers

 

 

6295

Enclosed heat detector, 57°C, class A2 S (54 to 70°C).

 

 

 

 

 

 

 

6296

Enclosed heat detector, 72°C, class B S (69 to 85°C).

 

 

 

 

 

 

 

6297

Enclosed heat detector, 87°C, class C S (84 to 100°C).

 

 

 

 

 

 

 

6298

Enclosed heat detector, 117°C, class E S (114 to 130°C).

 

 

 

 

 

 

 

 

3390

Label holder (100 holders per packet, excl. labels).

 

 

 

 

 

 

 

3391

Labels for 3390 (10 sheets à 132 labels)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Detector mounting holes, 2x(4x7 mm) c/c = 70 mm. E+/E- = Ext. LED. A/B = zone line in/out (or end-of-line device). Connectors for wire diameter 0.6 - 1.2 mm (approx. 0.3 - 1.13 mm2). Connection box mounting holes, 2x(5 mm) c/c = 108 mm. The connection box is prepared for required number of compression glands, one, two or three. A gland is approx. 30 mm high.

 

 

 

 

 

Technical data

 

 

 

 

 

Voltage (V DC)

 

 

 

 

 

 

 

 

 

 

 

 

 

rated

24

 

 

 

 

 

 

 

 

 

 

allowed

12-30

 

 

 

 

 

 

 

 

normal

24 (zone line voltage)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Current consumption at nom.

 

 

 

 

 

 

 

 

 

 

 

 

 

voltage, quiescent (mA)

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Current limitation required, when

6295-6297: Must be min. 6 and max. 40

 

 

 

 

active (mA)

6298: Must be min. 6 and max. 30

 

 

 

 

 

(EBL equipment has current limitation.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ext. LED output

 

 

 

 

 

 

 

 

 

 

 

 

 

voltage (V)

Zone line voltage minus 2 V

 

 

 

 

 

current output (mA)

Max. 10

(no internal current limiter)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Alarm resistance (Ω)

For 6295-6297: approx. 400. For 6298: approx. 680

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Internal capacitance (nF)

For 6295-6296: max. 50

 

 

 

 

 

Internal inductance

For 6295-6296: 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ambient temperature (°C)

6295 (A2 S):

6296 (B S):

6297 (C S):

6298 (E S):

operating

(Min. / Typical / Max.)

-40 /+25 /+50

-40 /+40 /+65

-40 /+55 /+80

-40 /+85 /+110

 

storage

-45 to +70

-45 to +70

-45 to +70

-45 to +70

 

 

 

 

 

 

 

 

 

Ingress Protection rating

IP67 (attached conn. box, silicon gasket and compression glands required)

 

 

 

 

 

 

 

 

Static response temperature

57, 72, 87, or 117°C depending on detector / class. See text.

 

 

 

 

 

 

 

 

 

 

 

 

Size ∅ x h (mm)

Detector: 95 x 42

Connection box: 100 x 35

 

 

 

Detector + Connection box: 100 x 75

(excl. compression glands)

 

 

 

 

 

 

 

 

 

 

Weight (g)

Detector:

82

Connection box (incl. 3 glands): 134

 

 

 

 

 

 

 

 

 

 

 

 

 

Construction

Body (6295, 6296): ABS

 

 

 

 

 

 

Body (6297, 6298): Modified Polycarbonate.

 

 

 

 

Protector (on the body) & Connection box: Modified Polycarbonate.

Colour

Grey (N8, Munsell colour code)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Approvals

 

 

 

 

05 EC Certificate no. 0845-CPD-232.1192

(6295);

EN54-5

 

 

 

 

 

 

 

 

 

05 EC Certificate no. 0845-CPD-232.1193

(6296);

EN54-5

 

 

 

 

 

 

 

 

 

 

05 EC Certificate no. 0845-CPD-232.1194

(6297);

EN54-5

 

 

 

 

 

 

 

 

 

 

05 EC Certificate no. 0845-CPD-232.1195

(6298);

EN54-5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ATEX classification (for 6295 &

6295:

 

II 3GD EEx nA II T5 (T100°C),

-40°C Ta 50°C

 

6296 only)

 

6296:

 

II 3GD EEx nA II T5 (T100°C),

-40°C Ta 65°C

 

 

 

 

 

All technical features and data are subject to changes without notice, resulting from continuous development and improvement.

Product Leaflet

Date of issue

Revision / Date of revision

MEW00132

2001-10-19

9 / 2008-10-10

 

 

 

Image 2
Contents Atex classification Fixed temperature alarm levelLatching Waterproof connection boxType numbers