Fire alarm systems
Enclosed
addressable manual
call point
3339
•Attractive design compliant with
•Test key for routine testing without breaking the glass element
•Protection against accidental operation
General
The call point has an attractive design compliant with
Test key
Routine testing is made with a supplied test key, without breaking the glass element. Inserting the test key simulates the breaking of the glass element. The call point is automatically reset when the test key is removed. The test key is also used to release the security clips for the front cover.
Protective cover
To protect the call point against accidental operation, a transparent polycarbonate cover has to be lifted to get access to the glass element.
Encapsulated circuit
All electronics are encapsulated. Only the terminal block is accessible from the rear. Mounted in the supplied red backbox and the tightening gasket on place (see the opposite page), the IP rating is IP67.
LED indicator
An LED on the front cover indicates fire alarm generated by the call point.
Flashing LED: The LED will flash each time the c.i.e. communicates with the call point, until the call point is operated and the LED is switched on.
Connections / Settings
The COM loop is connected directly to the call point via a
•NORMAL mode: (EBL512 SW version >2.0 / EBL128). M.c.p. type 3339. (Flashing or
•2330 mode: M.c.p. type 2339, flashing LED.
•2312 mode: M.c.p. type 2339, non-
flashing LED.
Two flying leads (wires) are connected to the terminal block, for connection of the 3314 address setting tool's connection cable. The wires are to be disconnected before the COM loop wires are connected.
Product applications
Used in the systems EBL512 / 128 / 1000 / 2000 and is intended for indoor use in premises where IP67 rating is required.