Panasonic 3339 manual General, Test key, Protective cover, Encapsulated circuit, LED indicator

Page 1

Fire alarm systems

Enclosed

addressable manual

call point

3339

Attractive design compliant with EN54-11. IP rating IP67

Test key for routine testing without breaking the glass element

Protection against accidental operation

General

The call point has an attractive design compliant with EN54-11, and is surface mounted in the supplied red backbox. It has a clip retained front cover that makes it easy to replace the glass element and adds security since the clips are concealed. The frangible element is a glass element with a protective plastic film. To operate the call point, the glass element is pressed until it is broken. This will activate the built-in microswitch, which will generate a fire alarm in the c.i.e.

Test key

Routine testing is made with a supplied test key, without breaking the glass element. Inserting the test key simulates the breaking of the glass element. The call point is automatically reset when the test key is removed. The test key is also used to release the security clips for the front cover.

Protective cover

To protect the call point against accidental operation, a transparent polycarbonate cover has to be lifted to get access to the glass element.

Encapsulated circuit

All electronics are encapsulated. Only the terminal block is accessible from the rear. Mounted in the supplied red backbox and the tightening gasket on place (see the opposite page), the IP rating is IP67.

LED indicator

An LED on the front cover indicates fire alarm generated by the call point.

Flashing LED: The LED will flash each time the c.i.e. communicates with the call point, until the call point is operated and the LED is switched on.

Non-flashing LED: The LED is switched off until the call point is operated and the LED is switched on.

Connections / Settings

The COM loop is connected directly to the call point via a 4-way terminal block. For COM loop address setting is the address setting tool 3314 used. 3314 is also used to set the call point type and the LED mode:

NORMAL mode: (EBL512 SW version >2.0 / EBL128). M.c.p. type 3339. (Flashing or non-flashing LED is set via Win512 / Win128.)

2330 mode: M.c.p. type 2339, flashing LED.

2312 mode: M.c.p. type 2339, non-

flashing LED.

Two flying leads (wires) are connected to the terminal block, for connection of the 3314 address setting tool's connection cable. The wires are to be disconnected before the COM loop wires are connected.

Product applications

Used in the systems EBL512 / 128 / 1000 / 2000 and is intended for indoor use in premises where IP67 rating is required.

Panasonic Electric Works Fire & Security Technology Europe AB Jungmansgatan 12, SE-211 19 Malmö, Sweden

Tel: +46 (0)40 697 70 00 • Fax: +46 (0)40 697 70 99 info-fste@eu.pewg.panasonic.comwww.panasonic-fire-security.com

Image 1
Contents Connections / Settings LED indicatorGeneral Test keyType numbers Technical data