Goodman Mfg IO-431 Electric Heat, HKR Installation, Electrical Supply Wire and MOP

Page 4
=.96 (230 Supply Volts) =.92 (220 Supply Volts) =.87 (208 Supply Volts)

Return Ductwork

DO NOT TERMINATE THE RETURN DUCTWORK IN AN AREA THAT CAN INTRODUCE TOXIC, OR OBJECTION- ABLE FUMES/ODORS INTO THE DUCTWORK. The return ductwork is to be introduced into the air handler bottom (upflow configuration).

Return Air Filters

Each installation must include a return air filter. This filtering may be performed at the air handler or externally such as a return air filter grille. Air handlers mounted in the downflow orientation, including “B” series, require external filtering. A washable filter is available as an accessory. To ensure opti- mum performance frequent filter cleaning is advised. Refer to Table 1 for the appropriate filter.

ASPF

Filter Number

Qty Required

 

 

 

1830

FIL 36-42

1

 

 

 

3137

FIL 48-61

1

4260

 

 

 

Table 1

 

Electric Heat

Refer to this manual in combination with the instructions pro- vided with the heat kit for the correct installation procedure.

The air handlers listed in this manual do not have factory installed electric heat. Electric heat is available as an acces- sory. If installing this option, the ONLY heat kits that can be used are the HKR series.

NOTE: The Amana® brand EHK, ECB, EDB, and EDK kits are NOT approved for use with these air handlers.

The heating mode temperature rise is dependent upon the system airflow, the supply voltage, and the heat kit size (kW) selected. Use Tables 2, 3, and 4 to determine the tempera- ture rise (ºF).

CFM

 

 

HEAT KIT NOMINAL kW

 

 

 

 

 

 

 

 

 

 

 

 

3

5

6

8

10

15

 

20

21

600

18

28

35

41

 

 

 

 

 

800

13

21

26

31

42

 

 

 

 

1000

11

17

21

25

34

50

 

 

 

1200

9

14

18

21

28

42

 

56

62

1400

8

12

15

18

24

36

 

48

53

1600

7

10

13

15

21

31

 

42

46

1800

6

9

12

14

19

28

 

37

41

2000

5

8

11

12

17

25

 

34

37

Table 2

230/1/60 Supply Voltage - Temperature Rise Table °F

CFM

 

 

HEAT KIT NOMINAL kW

 

 

3

5

6

 

8

 

10

15

 

20

21

 

 

 

 

600

17

27

34

 

39

 

 

 

 

 

 

800

13

20

25

 

30

 

40

 

 

 

 

1000

10

16

20

 

24

 

32

48

 

 

 

1200

8

13

17

 

20

 

27

40

 

53

59

1400

7

11

14

 

17

 

23

34

 

46

51

1600

6

10

13

 

15

 

20

30

 

40

44

1800

6

9

11

 

13

 

18

27

 

36

39

2000

5

8

10

 

12

 

16

24

 

32

35

 

 

 

 

Table 3

 

 

 

 

 

220/1/60 Supply Voltage - Temperature Rise Table °F

 

 

 

 

 

 

CFM

 

 

HEAT KIT NOMINAL kW

 

 

3

5

6

 

8

 

10

15

 

20

21

 

 

 

 

600

16

25

32

 

37

 

 

 

 

 

 

800

12

19

24

 

38

 

38

 

 

 

 

1000

10

15

19

 

22

 

30

46

 

 

 

1200

8

13

16

 

19

 

25

38

 

51

56

1400

7

11

14

 

16

 

22

33

 

43

48

1600

6

9

12

 

14

 

19

28

 

38

42

1800

5

8

11

 

12

 

17

25

 

34

37

2000

5

8

10

 

11

 

15

23

 

30

34

Table 4

208/1/60 Supply Voltage - Temperature Rise Table °F

NOTE: For installations not indicated above the following formula is to be used:

TR = (kW x 3412) x (Voltage Correction) x 1.08 / CFM

Where: TR

= Temperature Rise

kW

= Heater Kit Actual kW

3412 = Btu per kW Voltage Correction

1.08= Constant

CFM = Measured Airflow

NOTE: The Temperature Rise Tables can also be used to determine the air handler airflow delivery. When using these tables for this purpose set the room thermostat to maximum heat and allow the system to reach steady state conditions. Insert two thermometers, one in the return air and one in the supply air. The temperature rise is the supply air temperature minus the room air temperature.

Use HKR specification sheets to determine the HKR avail- able for a given air handler.

HKR Installation

Follow instructions listed in Installation and Operating Instruc- tions shipped with the heat kit.

Electrical Supply Wire and MOP

FIRE HAZARD!

To avoid the risk of property damage, personal injury or fire, use only copper conductors.

4

Image 4
Contents Aspf Important Safety Instructions Important Note to the Owner regarding Product WarrantyReplacement Parts Pre-Installation InstructionsShipping Inspection Codes & RegulationsElectrical Supply Wire and MOP HKR InstallationElectric Heat Maximum Allowable Length in Feet To Limit Voltage Drop to 2% Refrigerant Lines Low Voltage ConnectionsDownflow Conversion Horizontal ConversionCondensate Removal Aspf Model Insulation KitRegular Maintenance Start-Up ProcedureAchieve 2% Low Leakage Rate Aspf MotorAspf Thermostat Connections Cooling Unit with Optional Heat Kits of 10 kW and belowRoom Thermostat with TWO Stages of Heat Heat Pump Unit with Optional Heat Kits of 15 kW and Above Aspf Wiring Diagram G W1 W2 Y1 Y2 O DH 1 2 3 4This page Left Intentionally Blank Split Systems 2007 2012 Goodman Manufacturing Company, L.P