Installation Procedures
5.INSTALL THE DRAIN HOSE
Select whether the drain hose will be connected to the left or right side.(Fig.3)
Insert the drain hose into the drain pan, then secure the drain hose with a nylon fastener.(Fig.6)
Wrap the insulation (drain hose)around the drain hose connection.(Fig.7)
Be sure to arrange the drain hose correctly so that it is leveled lower than the drain hose connecting port of the indoor unit.(Fig.18)
Fig. 18
Remove the hole cover.
Arrange the drain hose |
|
|
|
| Drain hose |
|
|
|
| ||
|
|
|
|
| |
lower than this portion |
|
|
|
|
|
OK
OUTDOOR UNIT INSTALLATION
CONNECTING THE PIPING
1.FLARE PROCESSING
(1)Cut the connection pipe with pipe cutters so that the pipe is not deformed.
(2)Holding the pipe downward so that cuttings cannot enter the pipe, remove the burrs.
(3)Remove the flare nut from the indoor unit pipe and outdoor unit and assemble as shown in (Table1) and insert the flare nut onto the pipe, and flare with a flaring tool.
(4)Check if the flared part "L" (Fig.20)is spread uniformly and that there are no cracks.
| Table 1 |
|
|
Pipe | Flare nut |
|
|
Small pipe | Small (width across flats 22mm) |
|
|
Large pipe | Large (width across flats 24mm) |
|
|
NO
Fig. 19 | Piping hole |
|
Base (Bottom)
VT wire hole
Intake grill
Pass the drain hose through here | Cut the grill |
VT wire |
Drain hose
Fig. 20
Width across flats
|
| L dimension | ||
| L |
|
| |
|
| Diameter of pipe Dimension A (mm) | ||
For series 142, 182 | Liquid pipe | 6.35mm (1/4”) | 1.0~1.2 | |
Gas pipe | 12.7mm (1/2”) | |||
|
| |||
For series 242 | Liquid pipe | 9.52mm (3/8”) |
| |
Gas pipe | 15.88mm (5/8”) | 1.4~2.2 | ||
|
|
2. BENDING PIPES
The pipes are shaped by your hands. Be careful not to collapse them.
Fig. 21
OK | NO |
Extend the pipe by unwinding it
12