TX802RTD Specifications.

RTD Input

 

CU10 RTD (3 Wire Type) Standard.

 

 

Sensor Current = 0.8mA.

 

 

Lead Wire Resistance = 10Ω/Wire Max.

 

 

Field Programmable Zero: -200C (-400F) to 200C (400F). (TX802RTD Only.)

 

 

Field Programmable Span: 20C (40F) to 400C (800F). (TX802 RTD Only.)

 

 

Suitable for 2 Wire Connection. (Offset Calibration needed.)

 

 

Other Types of RTD Available. JIS Pt100, Pt250, Pt500,

 

 

Pt1000, CU10, CU100, Ni100 or specify.

Output

-mA

2 wire 4~20mA. (Loop Powered.)

 

-mV

40~200mV µ 4~20mA. (Indicative Test Signal Only.)

 

 

Other Output Voltages Available. e.g. 1~5V.

Power Supply

 

8~40Vdc.

Supply Voltage Sensitivty

<±0.005%/V FSO.

Input Programming Pt100 only

If the input range is not listed in the programming table, use the following formulae to work out the Zero and Span DIP switch settings for gain.

deg C Span Gain =

1200

 

deg C High - deg C Low

deg C Zero Gain =

deg C Low

 

5

If Zero Gain is 1/ +ve Put S3-1 OFF (Positive Offset) 2/ -ve Put S3-1 ON (Negative Offset)

Note: Enter the Zero or Span gain value into the appropriate Zero or Span DIP switch.

deg F Spain Gain =

 

 

2400

 

 

 

 

 

 

 

deg F High - deg F Low

 

deg F Zero Gain =

 

 

deg F Low

 

 

 

 

 

 

 

10

 

 

 

 

 

Gain Value

1

2

4

 

8

16

32

 

 

DIP Switch No.

1

2

3

 

4

5

6

 

 

 

 

 

 

 

 

 

 

So if a gain value of 28 is required, put DIP switch No's 3, 4, 5 OFF (ie, gains of 4 + 8 + 16 = 28) and all the other DIP switches ON. Dip switches are accessed by seperating the two halves of the enclosure

Output Load Resistance

800W @ 24Vdc. (50W/V Above 8Vdc.)

 

Maximum Output Current

Limited to <28mA.

 

Sensor Fail

-Upscale

23mA Min.

 

 

-Downscale

3.6mA Max.

 

 

 

 

Accurate to

 

<±0.1% FSO Typical.

 

Linearity & Repeatability

<±0.1% FSO Typical.

 

Ambient Drift

 

<±0.02%/C FSO Typical.

 

Noise Immunity

 

125dB CMRR Average. (2.0kVac RMS Limit.)

 

R.F. Immunity

 

<1% Effect FSO Typical.

 

Isolation Voltage

 

2.0kVac\dc Input to Output for 60sec.

 

Response Time

 

200msec Typical. (10 to 90% 50msec Typical.)

 

Operating Temperature

0~70C.

 

Storage Temperature

-20~80C.

 

Operating Humidity

90%RH Max. Non-Condensing.

 

Construction

 

6.6 Polyamide Thermoplastic Rail Mount Enclosure.

Note 1. Specifications based on Standard Calibration Unit, unless otherwise specified.

Note 2. Due to ongoing research and development, designs, specifications, and documentation are subject to change without notification. No liability will be accepted for errors, omissions or amendments to this specification.

Examples of Input Connection.

 

 

 

40~200mV Test Signal

Terminations.

 

Input

 

Input

Output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

A

1

A

 

T 6

 

+

mV

-

I n p u t 1

A

 

 

 

 

 

 

 

 

 

 

 

2

B

2

B

2

B

 

-

5

+

E.g. Loop Indicator,

3

B

 

 

 

 

 

Link 2 & 3

B

 

 

 

 

 

-

With 4~20mA Input.

O u t p u t 4

+mA

3

3

B ZERO

SPAN

+

4

 

 

 

 

5

-mA

 

 

 

 

8~40Vdc

 

 

 

2000V

Isolation Barrier

-

 

6

mV TEST

2 Wire RTD

OR

3 Wire RTD

Power Supply

 

 

 

 

 

 

+

 

 

 

 

 

 

 

 

 

(Typ. 24Vdc.)

 

 

Plan View of TX802RTD Adjustments (Pt100 only)

OFF

ON

1

S1

Input Terminals

 

 

 

 

Gain = 1

Gain = 0

 

 

 

Gain = 2

Gain = 0

2

Zero

 

 

 

Gain = 4

Gain = 0

3

 

 

 

 

4

 

 

 

 

Gain = 8

Gain = 0

 

 

OFF

ON

Gain = 16

Gain = 0

5

S3

1

- Ve Offset

+ Ve Offset

6

Gain = 32

Gain = 0

Function

2

Celsius

Fahrenheit

ON

 

 

 

3

Upscale Break

Downscale

OFF

ON

 

 

 

S2

4

Break

 

Gain = 1

Gain = 0

1

 

ON

25 Turn Trimpot for ZERO ±10%

Gain = 2

Gain = 0

2

Span

 

25 Turn Trimpot for SPAN ±10%

Gain = 4

Gain = 0

3

 

 

Gain = 8

Gain = 0

4

 

 

 

 

Gain = 16

Gain = 0

5

 

 

 

 

Gain = 32

Gain = 0

6

 

 

 

 

 

 

 

 

 

 

ON

LED Indication of Loop Current.

Power Supply Terminals

Input Range Programming Table Pt100 only.

Notes:1/ Switch status 1 = ON, 0 = OFF, X = DON'T CARE.

2/ Input ranges with '*' beside them require more adjustment by the Span trimpot.

 

Input Range C

Input Range F

 

 

 

S1-Zero

 

 

 

 

 

S2-Span

 

 

 

S3-Function

 

(Put S5-2 OFF)

(Put S5-2 ON)

 

1

2

 

3

4

 

5

6

 

1

2

 

3

4

 

5

6

 

1

2

3

4

 

0~20C

0~40F

 

1

1

 

1

1

 

1

1

 

1

1

 

0

0

 

0

0

 

X

 

 

 

 

 

0~25C

0~50F

 

1

1

 

1

1

 

1

1

 

1

1

 

1

1

 

0

0

 

X

 

TO '1' FOR FAHRENHEIT.

'1' for DOWNSCALE Sensor Break.

'0' for DOWNSCALE Sensor Break.

 

0~30C

0~60F

 

1

1

 

1

1

 

1

1

 

1

1

 

1

0

 

1

0

 

X

 

 

0~40C

0~80F

 

1

1

 

1

1

 

1

1

 

1

0

 

0

0

 

0

1

 

X

 

 

0~50C

0~100F

 

1

1

 

1

1

 

1

1

 

1

1

 

1

0

 

0

1

 

X

 

 

0~60C

0~120F

 

1

1

 

1

1

 

1

1

 

1

1

 

0

1

 

0

1

 

X

 

 

0~70C*

0~140F*

 

1

1

 

1

1

 

1

1

 

0

1

 

1

1

 

0

1

 

X

 

 

0~75C

0~150F

 

1

1

 

1

1

 

1

1

 

1

1

 

1

1

 

0

1

 

X

 

 

0~80C

0~160F

 

1

1

 

1

1

 

1

1

 

0

0

 

0

0

 

1

1

 

X

 

 

0~90C*

0~180F*

 

1

1

 

1

1

 

1

1

 

0

1

 

0

0

 

1

1

 

X

 

 

0~100C

0~200F

 

1

1

 

1

1

 

1

1

 

1

1

 

0

0

 

1

1

 

X

 

 

0~110C

0~220F

 

1

1

 

1

1

 

1

1

 

0

0

 

1

0

 

1

1

 

X

 

 

0~120C

0~240F

 

1

1

 

1

1

 

1

1

 

1

0

 

1

0

 

1

1

 

X

 

 

0~125C*

0~250F*

 

1

1

 

1

1

 

1

1

 

1

0

 

1

0

 

1

1

 

X

 

 

0~150C

0~300F

 

1

1

 

1

1

 

1

1

 

1

1

 

1

0

 

1

1

 

X

 

 

0~200C

0~400F

 

1

1

 

1

1

 

1

1

 

1

0

 

0

1

 

1

1

 

X

 

 

0~250C*

0~500F*

 

1

1

 

1

1

 

1

1

 

0

1

 

0

1

 

1

1

 

X

 

 

0~300C

0~600F

 

1

1

 

1

1

 

1

1

 

1

1

 

0

1

 

1

1

 

X

 

 

0~400C

0~800F

 

1

1

 

1

1

 

1

1

 

0

0

 

1

1

 

1

1

 

X

 

TO '0' FOR CELCIUS. SET

for UPSCALE Sensor Break. Set to

for UPSCALE Sensor Break. Set to

 

0~600C

0~1200F

 

1

1

 

1

1

 

1

1

 

1

0

 

1

1

 

1

1

 

X

 

 

-10~10C

-20~20F

 

1

0

 

1

1

 

1

1

 

1

1

 

0

0

 

0

0

 

1

 

 

-10~20C

-20~40F

 

1

0

 

1

1

 

1

1

 

1

1

 

1

0

 

1

0

 

1

 

 

-10~40C

-20~80F

 

1

0

 

1

1

 

1

1

 

1

1

 

1

0

 

0

1

 

1

 

 

-20~20C

-40~40F

 

1

1

 

0

1

 

1

1

 

1

0

 

0

0

 

0

1

 

1

 

 

-20~30C

-40~60F

 

1

1

 

0

1

 

1

1

 

1

1

 

1

0

 

0

1

 

1

 

 

-25~25C

-50~50F

 

0

1

 

0

1

 

1

1

 

1

1

 

1

0

 

0

1

 

1

 

 

-25~50C

-50~100F

 

0

1

 

0

1

 

1

1

 

1

1

 

1

1

 

0

1

 

1

 

 

-30~20C

-60~40F

 

1

0

 

0

1

 

1

1

 

1

1

 

1

0

 

0

1

 

1

 

 

-50~50C

-100~100F

 

1

0

 

1

0

 

1

1

 

1

1

 

0

0

 

1

1

 

1

 

 

-50~100C

-100~200F

 

1

0

 

1

0

 

1

1

 

1

1

 

1

0

 

1

1

 

1

 

 

-50~150C

-100~300F

 

1

0

 

1

0

 

1

1

 

1

0

 

0

1

 

1

1

 

1

 

 

-100~100C

-200~200F

 

1

1

 

0

1

 

0

1

 

1

0

 

0

1

 

1

1

 

1

 

 

-100~200C

-200~400F

 

1

1

 

0

1

 

0

1

 

1

1

 

0

1

 

1

1

 

1

 

 

-200~200C

-400~400F

 

1

1

 

1

0

 

1

0

 

0

0

 

1

1

 

1

1

 

1

 

 

-200~400C

-400~800F

 

1

1

 

1

0

 

1

0

 

1

0

 

1

1

 

1

1

 

1

 

 

 

 

 

 

 

 

 

 

SET

 

 

 

20~40C

40~80F

 

1

1

 

0

1

 

1

1

 

1

1

 

0

0

 

0

0

 

0

 

to '0'

to '1'

 

50~100C

100~200F

 

1

0

 

1

0

 

1

1

 

1

1

 

1

0

 

0

1

 

0

 

 

50~150C

100~300F

 

1

0

 

1

0

 

1

1

 

1

1

 

0

0

 

1

1

 

0

 

 

 

 

 

 

 

 

 

 

 

Set

Set

 

100~200C

200~400F

 

1

1

 

0

1

 

0

1

 

1

1

 

0

0

 

1

1

 

0

 

 

 

100~500C

200~1000F

 

1

1

 

0

1

 

0

1

 

0

0

 

1

1

 

1

1

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Image 4
Contents Temperature PRESSURE, Strain and ForceFLOW/LEVEL Data AcquisitionOmega.comTM OmegaProper Installation & Maintenance FeaturesGraph Of Maximum Load Versus Power Supply Enclosure DimensionsTX802RTD only