Nordyne T3BN installation instructions Accessories

Page 14

PHYSICAL AND ELECTRICAL SPECIFICATIONS / OUTDOOR UNITS 10.1 EER —High Efficiency — Three Phase

Model No. T3BN-

 

 

 

 

090C

090W

120C

120W

 

 

 

 

 

 

 

 

 

 

 

Volts-Phase-Hz

 

280/230-3-60

460-3-60

280/230-3-60

460-3-60

 

 

 

 

380/420-3-50

 

380/420-3-50

 

 

 

 

 

 

 

 

 

Voltage Range (Min-Max)

187-253

414-506

187-253

414-506

 

 

 

 

 

 

 

 

 

 

 

Total Amps

 

32.1

16.4

33.4

17.2

Electrical Data

 

 

 

 

 

 

 

 

 

Min Circuit Ampacity

41.4

21.7

43

22.7

 

 

 

 

 

 

 

 

 

 

 

 

Delay Fuse Max. (1)

60

35

70

35

 

 

 

 

 

 

 

 

 

 

Wire Size/Max Length (AWG 60°C Cu)

4/100

8/100

4/100

8/100

 

 

 

 

 

 

 

 

 

 

Wire Size/Max Length (AWG 75°C Cu)

6/100

8/100

4/100

8/100

 

 

 

 

 

 

 

 

 

 

 

 

 

Area (ft^2)

31.94

31.94

31.94

31.94

 

 

 

 

 

 

 

 

 

 

 

Coil

 

Rows-FPI

2-16

2-16

2-18

2-18

 

 

 

 

 

 

 

 

 

 

 

 

 

Tube Dia.

3/8” OD

3/8” OD

3/8” OD

3/8” OD

 

 

 

 

 

 

 

 

 

 

 

 

 

Volts-Phase-Hz

280/230-3-60

460-3-60

280/230-3-60

460-3-60

 

 

 

 

 

380/420-3-50

 

380/420-3-50

 

 

 

 

 

 

 

 

 

Fan Motor

 

Qty

1

1

1

1

 

 

 

Horsepower

3/4

3/4

3/4

3/4

 

 

 

 

 

 

 

 

Full Load Amps

3.3

1.7

3.3

1.7

Component Data

 

Fan Blade

 

Dia./Pitch/#Blades

30/19/3

30/19/3

30/26/3

30/26/3

 

 

 

RPM/CFM (Max-Total)

825/7500

825/7500

825/8500

825/8500

 

 

 

 

 

 

 

 

Volts-Phase-Hz

280/230-3-60

460-3-60

280/230-3-60

460-3-60

 

 

 

 

Qty./Type

1 / Scroll

1 / Scroll

1 / Scroll

1 / Scroll

 

 

Compressor

 

RLA

28.8

14.7

30.1

15.5

 

 

Data

 

LRA

195

95

225

114

 

 

 

 

Stages/Percent

1 / 100

1 / 100

1 / 100

1 / 100

 

 

 

 

Crankcase Heater Qty./Type

1 / Band

1 / Band

1 / Band

1 / Band

Refrigerant Suction Line-Length/O.D.

 

0 - 15 ft.

1 1/8”

1 1/8”

1 1/8”

1 1/8”

(Liq. Line All Lengths

- 5/8” O.D.)

 

16 - 25 ft

1 3/8” (3)

1 3/8” (3)

1 3/8” (3)

1 3/8” (3)

Circuits (Qty) - 1

 

 

 

26 - 75 ft.

1 3/8” (3)

1 3/8” (3)

1 3/8” (3)

1 3/8” (3)

Refrigerant Charge

 

Holding Charge

 

56

56

90

90

R-22 Ounces

 

Total System with 15’ Line Set (2)

374

374

486

486

Weight

 

 

 

Net

413

413

423

423

Approximate (lbs.)

 

 

 

Ship

425

425

435

435

(1)HACR Type Circuit Breakers may be used.

(2)Add 9.0 oz. of refrigerant per 5 feet of additional line set.

(3)Requires a 1-3/8” to 1-1/8” reducer line to unit.

ACCESSORIES —

Condensing Unit

Low Ambient Kit 913549A- Maintains system pressures during low ambient conditions.

COPPER WIRE SIZE — AWG

(1% Voltage Drop)

Supply Wire Length-Feet

Supply Circuit

200

150

100

50

Ampacity

 

 

 

 

 

6

8

10

14

15

4

6

8

12

20

4

6

8

10

25

4

4

6

10

30

3

4

6

8

35

3

4

6

8

40

2

3

4

6

45

2

3

4

6

50

2

3

4

6

55

1

2

3

4

60

14

Image 14
Contents User’s Information and Installation Instructions Defrost To Operate Your Heat Pump For HeatingEmergency Heat To Operate the Indoor Blower Continuously To Operate Your Heat Pump for Automatic Cooling and HeatingTo Shut OFF Your Heat Pump To Maintain Your Heat PumpGeneral Information Safety ConsiderationsRead Your Warranty Site PreparationElectrical Connections Installing the Outdoor UnitInstalling the Indoor Unit Copper Wire Size AWG Startup and CheckoutThermostat Typical Heat Pump with Standard Air HandlerDefrost Control Board Operation and Testing Defrost Test Procedure for Refrigerant Charging Charts Refrigerant Charging Charts Procedure for Charging 10-TON Heat Pump in Heating Mode Outdoor Temperature DEG. FGram Split System Heat PumpAccessories Page ¢708538G¤