Heat Controller HTD SERIES, HTH SERIES, HTV SERIES manual Auxiliary Electric Heat

Page 27

Heat Controller, Inc.

HTV/HTD/HTH SERIES

Engineering Design Guide

 

 

 

Heat ControllerTwoGeoMaxStage Geothermalrmal2Heat PumpHeatSystemsPump Systems

Auxiliary Electric Heat

Auxiliary Heat Ratings

Auxiliary Electric

 

 

HT

 

 

kW Rating

Btuh Rating

Minimum

 

 

 

 

 

 

 

 

 

CFM

Heat Model

024

036

048

060

070

230V

208V

230V

208V

Required

 

 

 

 

 

 

 

 

 

 

 

 

HGM5A

 

 

 

 

 

4.8

3.6

16300

12300

500

AGM5A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HGM8A

 

 

 

 

 

7.6

5.7

25900

19400

650

AGM8A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HGM10A

 

 

 

 

 

9.6

7.2

32700

24600

650

AGM10A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HGM12A

 

 

 

 

 

11.4

8.6

38900

29200

750

 

 

 

 

 

 

 

 

 

 

 

HGL10A

 

 

 

 

 

9.6

7.2

32700

24600

1300

AGL10A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AGL15AHGL15A

 

 

 

 

 

14.4

10.8

49100

36900

1350

 

 

 

 

 

 

 

 

 

 

 

HGL20A

 

 

 

 

 

19.2

14.4

65500

49200

1350

 

 

 

 

 

 

 

 

 

 

 

Grey area denotes compatibility

Note: Horizontal units rated for zero clearance unit and 1” clearance for the first three feet of duct,

Note: Vertical units rated for zero clearance for both unit and duct.

Auxiliary Heat Electrical Data

 

 

 

 

 

 

 

Heater Amps

 

Minimum

Maximum Fuse

Supply Wire

 

Auxiliary Electric

Supply

 

 

Circuit Amps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat Model

Circuit

 

230V

 

208V

 

230V

208V

230V

208V

Min

Max Ft

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HGM5A5A

 

 

 

Single

 

20.0

 

17.3

 

25.0

21.6

25

25

10

70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HGM8A8A

 

 

Single

 

31.7

 

27.5

 

39.6

34.4

40

35

8

70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HGM10A10A

 

Single

 

40.0

 

34.7

 

50.0

43.4

50

45

6

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Single

 

47.5

 

41.2

 

59.4

51.5

60

60

6

70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HGM12A

 

Dual - L1/L2

 

31.7

 

27.5

 

39.6

34.4

40

35

8

70

 

 

 

 

 

Dual - L3/L4

 

15.8

 

13.7

 

19.8

17.1

20

20

12

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AGL10AHGL10A

 

Single

 

40.0

 

34.7

 

50.0

43.4

50

45

6

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Single

 

60.0

 

52.0

 

75.0

65.0

80

70

6

50

 

HGL15A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AGL15A

 

Dual - L1/L2

 

40.0

 

34.7

 

50.0

43.4

50

45

6

80

 

 

 

 

 

Dual - L3/L4

 

20.0

 

17.3

 

25.0

21.6

25

25

10

70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Single

 

80.0

 

69.3

 

100.0

86.6

100

90

2

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HGL20A

Dual - L1/L2

 

40.0

 

34.7

 

50.0

43.4

50

45

6

80

 

 

 

 

 

 

 

 

 

 

 

 

 

Dual - L3/L4

 

40.0

 

34.7

 

50.0

43.4

50

45

6

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

All heaters rated single phase 208-230V 60Hz

 

 

 

Wire length based on one way measurement with 2% voltage drop

Wire size based on 60°C (90*C)copper conductor

 

 

 

 

 

 

 

 

All models 12kW or larger feature internal circuit breakers

All Fuses UL Class K general purpose

 

 

 

26

Image 27
Contents Engineering Design Guide HTH Two Stage Geothermal Heat Pump Systems ‡£äÊV…ÀVÌiÀˆÃ̈VÃÊÀi\ ‡£äʈÃÊʘœ˜‡V…œÀˆ˜iÊLÃi`Ê ‡£äʈÊÊÌʈÃÊÃii˜ÊÃÊÌ…iÊvÕÌÕÀiʏÊ ÀivÀˆiÀ˜ÌÃÊÕÃi`ÊÜœÀ`܈`iE7J?HE?B HT Series Ratings HT Physical Data Dimensions Vertical Upflow 0489 Discharge Connection Return Connection0246 14.0 22.2 26.2 0368Dimensions Vertical Downflow 334 ReturnWidth Depth Return 10.4 175 210 265Dimensions Ve tical Downflow SwivelSwivel Electrical Knockouts Dimensions Ve tical DownflowDischarge Connection HTV024,&HTD024&PartHTH024Load Part Load Performance DataHTV024,&HTD024 &FullHTH024Load Full Load HTH036 Part Load HTV036,/6äÎÈÊ*ÀÌÊ&HTD036œPart`LoadHTV036, HTD036 & HTH036 Full Load /6äÎÈÊ & HTD036ՏÊœ Full` LoadHTD048 & HTH048 Part Load HTV048/6änÊ*ÀÌÊ& HTD048œPart`LoadOperation Not Recommended TV/6änÊ048,&HTD048ՏÊœ&Full`HTH048Load Full LoadHTH060 Part Load HTV060,/6äÈäÊ*ÀÌÊ&HTD060œPart`LoadHTV060,/6äÈäÊ&HTD060ՏÊœ&Full`HTH060Load Full Load HTV070,&HTD070&PartHTH070Load Part Load PERfoRmaNcE DataCFM Rated Airflow HTV070, HTD070& HTH070 Full LoadÄÇÓx Än™x ÄnÇÈ  £Ó™Ó ÄnÓ™Blower Performance Data 060070 H7DGK?B?JO W EDJHEB!7JKHI Auxiliary Electric Heat Typical Wiring Diagram 08/2011