Heat Controller HTD SERIES, HTH SERIES, HTV SERIES manual HT Series Ratings

Page 6

Engineering Design Guide

HTV/HTD/HTH SERIES

Heat Controller, Inc.

 

 

 

Heat ControllerTwoGeoMaxStage Geothermal2 n GeothermalHeat PumpHeatSystemsPump Systems

HT Series Ratings

ARI/ASHRAE/ISO 13256-1

at EWT (Entering Water Temperature)

HTV/HTD/HTH024

HTV/HTD/HTH036

HTV/HTD/HTH048

HTV/HTD/HTH060

HTV/HTD/HTH070

Heating capacities based upon 68°F DB, 59°F WB entering air temperature.

HT Electrical Data

 

Voltage

 

Min/Max

 

Compressor

 

Fan Motor

Total Unit

 

 

Model

Code

Voltage

Voltage

QTY

 

RLA

 

LRA

FLA

FLA

MCA

Max/Fuse

024

1

208/230-60/1

197/254

1

 

10.3

 

52.0

3.9

18.6

21.2

30

 

 

 

 

 

 

 

 

 

 

 

 

 

036

1

208/230-60/1

197/254

1

 

16.7

 

82.0

3.9

25.0

29.2

45

 

 

 

 

 

 

 

 

 

 

 

 

 

048

1

208/230-60/1

197/254

1

 

21.2

 

96.0

6.9

32.5

37.8

50

 

 

 

 

 

 

 

 

 

 

 

 

 

060

1

208/230-60/1

197/254

1

 

25.6

 

118.0

6.9

36.9

43.3

60

 

 

 

 

 

 

 

 

 

 

 

 

 

070

1

208/230-60/1

197/254

1

 

27.2

 

150.0

6.9

38.5

45.3

70

 

 

 

 

 

 

 

 

 

 

 

 

 

Min/Max Voltage of 197/254

HACR circuit breaker in USA only

All fuses Class RK-5

Wire size based on 60°C copper conductor and Minimum Circuit Ampacity.

Wire length based on one way measurement with 2% voltage drop

5

Image 6
Contents Engineering Design Guide HTH Two Stage Geothermal Heat Pump Systems ÀivÀˆiÀ˜ÌÃÊÕÃi`ÊÜœÀ`܈`i ‡£äʈÃÊʘœ˜‡V…œÀˆ˜iÊLÃi`Ê ‡£äʈÊÊÌʈÃÊÃii˜ÊÃÊÌ…iÊvÕÌÕÀiʏÊ ‡£äÊV…ÀVÌiÀˆÃ̈VÃÊÀi\E7J?HE?B HT Series Ratings HT Physical Data Dimensions Vertical Upflow 0368 Discharge Connection Return Connection0246 14.0 22.2 26.2 0489Dimensions Vertical Downflow 10.4 175 210 265 ReturnWidth Depth Return 334Dimensions Ve tical Downflow SwivelSwivel Electrical Knockouts Dimensions Ve tical DownflowDischarge Connection Performance Data HTV024,&HTD024&PartHTH024Load Part LoadHTV024,&HTD024 &FullHTH024Load Full Load HTV036,/6äÎÈÊ*ÀÌÊ&HTD036œPart`Load HTH036 Part Load/6äÎÈÊ & HTD036ՏÊœ Full` Load HTV036, HTD036 & HTH036 Full LoadHTV048/6änÊ*ÀÌÊ& HTD048œPart`Load HTD048 & HTH048 Part LoadTV/6änÊ048,&HTD048ՏÊœ&Full`HTH048Load Full Load Operation Not RecommendedHTV060,/6äÈäÊ*ÀÌÊ&HTD060œPart`Load HTH060 Part LoadHTV060,/6äÈäÊ&HTD060ՏÊœ&Full`HTH060Load Full Load PERfoRmaNcE Data HTV070,&HTD070&PartHTH070Load Part LoadHTV070, HTD070& HTH070 Full Load CFM Rated AirflowÄnÓ™ ÄnÇÈ  £Ó™Ó ÄÇÓx Än™xBlower Performance Data 060070 H7DGK?B?JO W EDJHEB!7JKHI Auxiliary Electric Heat Typical Wiring Diagram 08/2011