Heat Controller EKTC15-1G, EKTH15-1G, EKTH12-1G, EKTH09-1G, EKTH12-2G, EKTH09-2G Protective Features

Page 23

Heat Controller

Service Manual

Packaged Terminal A/C

 

 

 

F. Protective Features

1. Frost Protection Mode (heat pump):

When the compressor is running under wired controller’s heating signal. If T outer tube ≤ 28°F (-2°C) is detected for 1 min- ute successively, the compressor and outdoor fan will stop running. Then indoor fan will run normally according to the wired controller’s signal. If the heating is required then the heat pump operation will stop the compressor and run the electric heater solely. However, if T outer tube ≥ 40°F (5°C) is detected for 10 minutes, it will stop the frost protection mode.

2. High temperature protection for evaporator:

When the compressor is running under wired controller’s heating signal, if T inner tube ≤ 136°F (58°C) is detected for 1 minute successively, the compressor and outdoor fan will stop running and the indoor fan will run normally according to the wired controller’s signal. If heating is required the heat pump operation will stop the compressor and run the electric heater solely after 15 seconds.

3. Antifreezing protection for evaporator:

Whe the compressor is running under wired controller’s heating signal, if T inner tube ≤ 28°F (-2°C) is detected for 1 minute successively, the compressor and outdoor fan will stop running and the indoor fan will run normally according to the wired controller’s signal. (Before the protection, if there isn’t a signal for indoor fan, it will run at medium fan speed. After entering the protection mode, it will run at the preset fan speed before protection) until T inner tube ≤ 40°F (5°C) is detected for 2 minutes, the the system will quit the antifreezing protection mode.

4. Higher temperature protection for outdoor condenser:

Under the wired controller’s signal, the compressor is running. If T outer tube ≤ 149°F (65°C) is detected for 1 minute suc- cessively, the high temperature resistant protection mode will be enabled. The compressor will stop running, the indoor fan will run normally according to the signal of wired controller and the outdoor fan will run constantly until T outer tube ≤131°F (55°C) is detected for 2 minutes successively then the protection mode will stop.

22

Image 23 Contents
Packaged Terminal Air Conditioners & Heat Pumps Model Revision Dimensional DataUnit nomenclature BTU/HUnit components EKTC07-1G EKTH07-1G Specification and Technical ParametersFunction G4C085IUBJP Refrigerant Charge oz. kg 410A 33.5 oz G4C085YUAJPG4A110IUBJP EKTH12-1GG4A110YUAJP EKTH12-2GEKTC15-1G EKTH15-1G EKTC15-2G EKTH15-2G Extended Cooling Performance Extended Performance DataRating Point System Basic Function Controller Functions and Operating MethodsButton and Displays Controller Function and Operating MethodEnergy Management Input Special Functions and FeaturesAWG Wire Size no Wall Thermostat Connections Typical Wiring Diagram Temp Control Unit controlsKeypad Configuration DIP Switches Protective Features Electric Circuit Diagram Power Connection Options Preventative Maintenance Cooling Heating Trouble Shooting Guide