Heat Controller VMC24SB-1/VMH24SB-1 service manual Test Run Detail, Settlement of outdoor unit

Page 33

Part 3 Test Run

3. Test RunDetail

1.Check that all tubing and wiring have been properly con- nected.

2.Check that the gas and liquid side service valves are fully open.

Settlement of outdoor unit

Anchor the outdoor unit with a bolt and nut Ø0.39 inch tightly and horizontally on a concrete or rigid mount.

When installing on the wall, roof or rooftop, anchor the mounting base securely with a nail or wire assuming the influence of wind and earthquake possibilities.

When vibration of the unit is conveyed through the hose, secure the unit with an anti-vibration bushing.

Bolt

Tubing connection

Evaluation of the performance

Operate unit for 15~20 minutes, then check the system refrigerant charge:

1.Measure the pressure of the gas side service valve.

2.Measure the temperature of the intake and discharge air.

3.Ensure the difference between the intake temperature and the discharge is more than 8˚C(46˚F) (Cooling or Heating).

NOTE: If the actual pressure is higher than shown, the system is most likely over-charged, and charge should be removed.

If the actual pressures are lower than shown, the system is most likely undercharged, and charge should be added.

The air conditioner is now ready for use.

PUMP DOWN

This is performed when the unit is to be relocated or the refrigerant circuit is serviced.

Pump Down means collecting all refrigerant in the outdoor unit without loss in refrigerant gas.

CAUTION:

Be sure to perform Pump Down procedure with the unit in cooling mode.

Pump Down Procedure

1.Connect a low-pressure gauge manifold hose to the charge port on the gas side service valve.

2.Open the gas side service valve halfway and purge the air from the manifold hose using the refrigerant gas.

3.Close the liquid side service valve(all the way in).

4.Turn on the unit's operating switch and start the cooling operation.

5.When the low-pressure gauge reading becomes 1 to 0.5kg/cm2 G(14.2 to 7.1 P.S.I.G.), fully close the gas side valve stem and then quickly turn off the unit. At that time, Pump Down has been completed and all refrigerant gas will have been collected in the outdoor unit.

5.Check operating current.

Intake temperature

Discharge air

Discharge temperature

4.For reference; the gas side pressure of optimum condition is as below.(Cooling)

6.Change from cooling mode to heating mode (if heat pump model) and check all operations.

Refrigerant

Outside ambient

The pressure of the gas side

 

TEMP.

service valve.

R22

35°C (95°F)

4~5kg/cm2G(56.8~71.0 P.S.I.G.)

R410A

35°C (95°F)

8.5~9.5kg/cm2G(120~135 P.S.I.G.)

- 33 -

Only for training and service purposes

Image 33
Contents Heat CONTROLLER, INC Contents Part 1 General Information Be sure not to do Be sure to follow the instruction Safety PrecautionsPart 1 General Information Inspections after Repair Part 2 Functions & Controls Category Function Description Remark List of Functions & ControlsBasic Mode Controls Cooling ModeHeating Mode Heatpump Only Intake air Temp Setting Temp Healthy Dehumidification operationAuto changeover operation Heatpump Only Energy saving operation in cooling mode Special Mode ControlsJet Cool operation Jet Heat operation Heatpump OnlyUtility Functions Auto cleaning operationForced operation Heat/pump Model Cooling/only ModelSleep mode Auto control Air volume controlSleep timer operation for cooling cycle Natural Air ControlAuto WindAuto restart Sleep timer operation for heating cycle Heatpump OnlyFive Seconds Stand-by fan Protection Functions & ControlsTwo Minutes Stand-by comp Hot start Heatpump OnlyCompressor Preheating Heatpump Only Outdoor Temperature Running Time secSump Heater Control 9, 12kBtu/h Model Only Heatpump Only 1 9,12kBtu/h ModelAutomatic defrost Heatpump Only 2 18,24,30kBtu/h Model Starting the defrosting operationControl algorithm of defrost completion Defrosting Control AlgorithmInverter Power Relay ControlOverheating Protection Power Module Heat sink sensor failure error Heat sink temperature controlFunction CT1 control Total Current Control Over Current ProtectionCT2 control Model KBtu/h Cooling Heating11A 12A 14A 15.5A Discharge Pipe Temp Control DC Peak controlInverter Compressor 18,24,30kBtu/h Model Constant Compressor only 30kBtu/h Model There can be two situationsCompressor working 12.1 9,12kBtu/h Model Low Ambient control12.2 18, 24, 30kBtu/h Model Model Mode-in Condition Mode-out ConditionOil equalizing control30kBtu/h Model Oil return control30kBtu/h Model Heatpump OnlyOperating Contion Operation ProcessPart 3 Test Run Check before Test Run Test Run Flow chart Test Run DetailCheck before Test Run Start Test Run Flow chartTest Run Detail Pump Down ProcedureSettlement of outdoor unit Evaluation of the performancePart 4 Trouble Shooting Way Valve Liquid Side Way, 3-Way ValvePumping Down ProcedureAir purging of the charge hose Set the 2-way valve to the closed positionEvacuation Gas Charging After Evacuation Mount the valve stem nuts and the service port nutConnect the charge hose to the charging cylinder Purge the air from the charge hoseTrouble analysis Cycle Troubleshooting GuideProcedure Specification Remedy Electronic Parts Troubleshooting GuideTrouble Compressor/Outdoor Fan does not operate 9, 12kBtu/h Model Trouble When indoor Fan does not operate.9~30kBtu/h Model Error Indicator Self-diagnosis Function12kBtu/h Model Outdoor Error 18,24,30kBtu/h Model Indoor ErrorError code Descrition Red Green StatusCode ErrorTroubleshooting Guide9,12kBtu/h Model Description Cause of error Heat-sink Temp. is over Description Cause of error DC Peak Error Description Cause of error Over current Error Description Cause of error Indoor fan is locked Description Cause of error Discharge pipe temp. is Check Point Troubleshooting CH01, CH02, CH06Troubleshooting CH05, CH53 Part Trouble ShootingTroubleshooting CH21 CompCopper Comp pipe Troubleshooting CH21, CH22 Troubleshooting CH23, CH28 Troubleshooting CH24, CH25 ‘B’ Troubleshooting CH26, CH27Troubleshooting CH32, CH33, CH40 Troubleshooting CH41, CH44, CH45, CH46, CH47, CH65 Troubleshooting CH51, CH60 Inverter/ConstantCondenser/Suction Pipe Troubleshooting CH61, CH62 Heat CONTROLLER, INC

VMC12SB-1/VMH12SB-1, VMC18SB-1/VMH18SB-1, VMC24SB-1/VMH24SB-1, VMC09SB-1/VMH09SB-1, VMC30SB-1/VMH30SB-1 specifications

The Heat Controller VMC30SB-1/VMH30SB-1, VMC09SB-1/VMH09SB-1, VMC24SB-1/VMH24SB-1, VMC18SB-1/VMH18SB-1, and VMC12SB-1/VMH12SB-1 are versatile and efficient HVAC systems designed for residential and commercial applications. These units stand out due to their innovative technologies, user-friendly features, and reliable performance, making them an excellent choice for heating and cooling needs.

One of the most significant features of these units is their Energy Efficiency Rating (EER). Each model has been engineered to provide optimal energy savings, thus minimizing operating costs and environmental impact. Utilizing advanced inverter technology, the systems adjust their cooling and heating output according to the room's demand, ensuring that energy is used only when necessary. This results in quieter operation, less energy consumption, and enhanced comfort.

The VMC and VMH models are equipped with high-performance compressors that provide rapid heating and cooling capabilities. This feature allows users to attain their desired temperatures more quickly compared to traditional systems, ensuring a comfortable environment throughout the year. In addition, the systems maintain consistent temperatures and reduce temperature fluctuations, contributing to a more enjoyable living or working space.

Another key characteristic of the Heat Controller units is their comprehensive filtration systems. These include multi-stage filters designed to trap dust, allergens, and other particulate matter, contributing to improved indoor air quality. This aspect is particularly important for those who suffer from allergies or respiratory issues, as the units help to create a cleaner, healthier living environment.

The compact design of these models allows for easy installation in various spaces, including small apartments or tight commercial setups. They feature an intuitive control panel that offers user-friendly programming options, enabling users to schedule operations according to their daily routines. Additionally, many models include smart connectivity features, allowing remote access and adjustments via mobile apps.

Finally, the aesthetic design of the VMC and VMH series complements modern interior decors, ensuring that these units not only perform well but look good while doing so. With a combination of reliability, energy efficiency, and user-centric features, the Heat Controller VMC and VMH series stand out as an excellent investment for any heating and cooling requirement. These units promise comfort, convenience, and cost-effective operation.