Part 4 Trouble Shooting

7. Self-diagnosisFunction

Error Indicator

The error indicator assists with self-diagnoisis of the air conditioner and identifies if there is any trouble.

The error indicator location is near the ON/OFF button by the LED on the evaporator and will signal as shown in the table below.

If more than two errors occur simultaneously, primarily the highest severity error code is displayed.

After error an occurrence, the error is cleared, the error LED is also cleared, simultaneously.

To operate again on the occurrence of error code, be sure to turn off the power and then turn on.

The error codes are different for various models

9, 12kBtu/h Model

Error

 

 

 

 

 

 

 

Error Indicator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cause of Error

Display

Indoor

Code

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor

Outdoor

Operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

1 time

 

1time

 

 

1time

 

 

 

 

 

1time

 

 

1time

• Indoor Temp. sensor error

O

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 sec

 

 

3 sec

 

 

 

3 sec

 

 

 

 

 

 

 

3 sec

 

 

 

- Sensor open or short

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 times

 

 

 

 

 

2 times

 

 

 

 

 

 

 

 

2 times

 

 

2 times

• Outdoor Temp. sensor error

O

O

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

3 sec

 

 

 

 

 

 

3 sec

 

 

 

 

 

 

 

 

 

 

3 sec

 

 

 

- Sensor open or short

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4 times

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4 times

• Heat Sink sensor error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- Sensor open or short

O

O

ON

 

 

 

 

 

 

 

 

 

 

 

 

3 sec

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 sec

- Heat Sink temp is over 95˚C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(203˚F)

 

 

 

5

 

 

 

 

 

 

 

 

 

 

 

5times

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5times

• Communication error

O

O

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 sec

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 sec

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6times

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6times

• DC Peak error

O

O

SHUT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 sec

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DOWN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7times

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7times

• Over current error (CT2)

O

O

SHUT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DOWN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 sec

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8times

 

 

 

 

 

8times

• Indoor fan lock error

O

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 sec

 

 

 

 

 

 

 

 

 

 

(BLDC fan model only)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9times

 

 

 

 

 

9times

• Outdoor fan lock error

O

O

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(BLDC fan model only)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 sec

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10 times

 

 

10 times

• Discharge pipe thermistor is

O

O

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 sec

 

 

 

short or open.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(4 LED Model)

- 45 -

Only for training and service purposes

Image 45
Contents Heat CONTROLLER, INC Contents Part 1 General Information Be sure not to do Be sure to follow the instruction Safety PrecautionsPart 1 General Information Inspections after Repair Part 2 Functions & Controls Category Function Description Remark List of Functions & ControlsBasic Mode Controls Cooling ModeHeating Mode Heatpump Only Intake air Temp Setting Temp Healthy Dehumidification operationAuto changeover operation Heatpump Only Energy saving operation in cooling mode Special Mode ControlsJet Cool operation Jet Heat operation Heatpump OnlyUtility Functions Auto cleaning operationForced operation Heat/pump Model Cooling/only ModelSleep mode Auto control Air volume controlSleep timer operation for cooling cycle Natural Air ControlAuto WindAuto restart Sleep timer operation for heating cycle Heatpump OnlyFive Seconds Stand-by fan Protection Functions & ControlsTwo Minutes Stand-by comp Hot start Heatpump OnlyCompressor Preheating Heatpump Only Outdoor Temperature Running Time secSump Heater Control 9, 12kBtu/h Model Only Heatpump Only 1 9,12kBtu/h ModelAutomatic defrost Heatpump Only 2 18,24,30kBtu/h Model Starting the defrosting operationControl algorithm of defrost completion Defrosting Control AlgorithmInverter Power Relay ControlOverheating Protection Power Module Heat sink sensor failure error Heat sink temperature controlFunction CT1 control Total Current Control Over Current ProtectionCT2 control Model KBtu/h Cooling Heating11A 12A 14A 15.5A Discharge Pipe Temp Control DC Peak controlInverter Compressor 18,24,30kBtu/h Model Constant Compressor only 30kBtu/h Model There can be two situationsCompressor working 12.1 9,12kBtu/h Model Low Ambient control12.2 18, 24, 30kBtu/h Model Model Mode-in Condition Mode-out ConditionOil equalizing control30kBtu/h Model Oil return control30kBtu/h Model Heatpump OnlyOperating Contion Operation ProcessPart 3 Test Run Check before Test Run Test Run Flow chart Test Run DetailCheck before Test Run Start Test Run Flow chartTest Run Detail Pump Down ProcedureSettlement of outdoor unit Evaluation of the performancePart 4 Trouble Shooting Way Valve Liquid Side Way, 3-Way ValvePumping Down ProcedureAir purging of the charge hose Set the 2-way valve to the closed positionEvacuation Gas Charging After Evacuation Mount the valve stem nuts and the service port nutConnect the charge hose to the charging cylinder Purge the air from the charge hoseTrouble analysis Cycle Troubleshooting GuideProcedure Specification Remedy Electronic Parts Troubleshooting GuideTrouble Compressor/Outdoor Fan does not operate 9, 12kBtu/h Model Trouble When indoor Fan does not operate.9~30kBtu/h Model Error Indicator Self-diagnosis Function12kBtu/h Model Outdoor Error 18,24,30kBtu/h Model Indoor ErrorError code Descrition Red Green StatusCode ErrorTroubleshooting Guide9,12kBtu/h Model Description Cause of error Heat-sink Temp. is over Description Cause of error DC Peak Error Description Cause of error Over current Error Description Cause of error Indoor fan is locked Description Cause of error Discharge pipe temp. is Check Point Troubleshooting CH01, CH02, CH06Troubleshooting CH05, CH53 Part Trouble ShootingTroubleshooting CH21 CompCopper Comp pipe Troubleshooting CH21, CH22 Troubleshooting CH23, CH28 Troubleshooting CH24, CH25 ‘B’ Troubleshooting CH26, CH27Troubleshooting CH32, CH33, CH40 Troubleshooting CH41, CH44, CH45, CH46, CH47, CH65 Troubleshooting CH51, CH60 Inverter/ConstantCondenser/Suction Pipe Troubleshooting CH61, CH62 Heat CONTROLLER, INC

VMC12SB-1/VMH12SB-1, VMC18SB-1/VMH18SB-1, VMC24SB-1/VMH24SB-1, VMC09SB-1/VMH09SB-1, VMC30SB-1/VMH30SB-1 specifications

The Heat Controller VMC30SB-1/VMH30SB-1, VMC09SB-1/VMH09SB-1, VMC24SB-1/VMH24SB-1, VMC18SB-1/VMH18SB-1, and VMC12SB-1/VMH12SB-1 are versatile and efficient HVAC systems designed for residential and commercial applications. These units stand out due to their innovative technologies, user-friendly features, and reliable performance, making them an excellent choice for heating and cooling needs.

One of the most significant features of these units is their Energy Efficiency Rating (EER). Each model has been engineered to provide optimal energy savings, thus minimizing operating costs and environmental impact. Utilizing advanced inverter technology, the systems adjust their cooling and heating output according to the room's demand, ensuring that energy is used only when necessary. This results in quieter operation, less energy consumption, and enhanced comfort.

The VMC and VMH models are equipped with high-performance compressors that provide rapid heating and cooling capabilities. This feature allows users to attain their desired temperatures more quickly compared to traditional systems, ensuring a comfortable environment throughout the year. In addition, the systems maintain consistent temperatures and reduce temperature fluctuations, contributing to a more enjoyable living or working space.

Another key characteristic of the Heat Controller units is their comprehensive filtration systems. These include multi-stage filters designed to trap dust, allergens, and other particulate matter, contributing to improved indoor air quality. This aspect is particularly important for those who suffer from allergies or respiratory issues, as the units help to create a cleaner, healthier living environment.

The compact design of these models allows for easy installation in various spaces, including small apartments or tight commercial setups. They feature an intuitive control panel that offers user-friendly programming options, enabling users to schedule operations according to their daily routines. Additionally, many models include smart connectivity features, allowing remote access and adjustments via mobile apps.

Finally, the aesthetic design of the VMC and VMH series complements modern interior decors, ensuring that these units not only perform well but look good while doing so. With a combination of reliability, energy efficiency, and user-centric features, the Heat Controller VMC and VMH series stand out as an excellent investment for any heating and cooling requirement. These units promise comfort, convenience, and cost-effective operation.