ELECTRIC HEATER KIT SPECIFICATIONS

ELECTRIC HEATER KIT SPECIFICATIONS

 

 

 

 

MODEL

 

 

 

MINIMUM CIRCUIT

MAX. FUSE OR

 

 

kW@

AMPACITY

BREAKER (HACR)

 

USED WITH

240V

208V

240V

208V

240V

208V

N/A

Without heat

0

0

2.1

1.9

15

15

7800-305B

 

5.0

3.8

29

25

30

25

7800-306B HAH1324-00-1A

8.0

6.0

44

39

45

40

7800-308B

 

10

7.5

55

48

60

50

N/A

Without heat

0

0

3.5

3.4

15

15

7800-305B

 

5.0

3.8

30

27

30

30

7800-306B

HAH1336-00-1A

8.0

6.0

46

40

50

40

7800-308B

10

7.5

56

49

60

50

 

7800-312B

 

15

11.3

56/26

49/23

60/30

50/30

N/A

Without heat

0

0

4.0

3.9

15

15

7800-313B

 

5.0

3.8

30

27

30

25

7800-314B

 

8.0

6.0

46

41

50

45

7800-315B HAH1348-00-1A

10

7.5

57

50

60

50

7800-316B

 

15

11.3

53/30

46/27

60/30

50/30

7800-317B

 

20

15

57/63

50/46

60/60

50/50

N/A

Without heat

0

0

6.0

5.9

15

15

7800-313B

 

5.0

3.8

32

29

35

30

7800-314B

 

8.0

6.0

48

42

50

45

7800-315B HAH1360-00-1A

10

7.5

59

52

60

60

7800-316B

 

15

11.5

53/32

46/29

60/35

50/30

7800-317B

 

20

15

59/53

52/46

60/60

60/50

7800-400

 

4-Pole Jumper Bar Assembly 15 and 20 kW only

 

5 of 6

HAHIOM062906

Image 5
Contents HAH13XX-00-1ASeries Electric Heat Installation, Operation and Maintenance ManualAir Handling Units HEAT CONTROLLER, INCD.Physical Installation MINIMUM CLEARANCES B. Rules for Safe Installation and OperationA. Introduction C. Unpacking the Unit9.Reinstall doors 6.Install modified coil assembly back into unitSee Electric Heater Kit Specifications Table F. POWER WIRINGN. PERIODIC MAINTENANCE TURN OFF POWER AT BREAKER PANELK. CONDENSATE DRAIN M. CHECK TEST AND START UPMODEL ELECTRIC HEATER KIT SPECIFICATIONSMINIMUM CIRCUIT MAX. FUSE ORHAH - TO 20 KW WITH TDR 6 of