Heat Controller RAD-183A, RAD-243A service manual Troubleshooting Guide

Page 33

Troubleshooting Guide

COMPLAINT

CAUSE

REMEDY

 

 

 

 

Compressor will not run,

Thermostat

Check the position of knob If not at the coldest set-

but fan motor runs.

 

ting, advance the knob to this setting and restart

 

 

 

unit.

 

 

 

Check continuity of the thermostat. Replace ther-

 

 

 

mostat if circuit is open.

 

 

 

 

 

 

Thermistor

Check the TEMP control. If not at the lowest num-

 

 

 

ber, set TEMP control to this setting and restart

 

 

 

the unit. Check the continuity of the thermistor.

 

 

 

Replace the thermistor if the circuit is open.

 

 

 

 

 

 

Capacitor (Discharge

Check the capacitor.

 

 

capacitor before servicing.)

Replace if not within ±10% of manufacturers rat-

 

 

 

ing. Replace if shorted, open, or damaged.

 

 

 

 

 

 

Compressor

Check the compressor for open circuit or ground. If

 

 

 

open or grounded, replace the compressor.

 

 

 

 

 

 

Overload

Check the compressor overload, if externally

 

 

 

mounted. Replace if open. (If the compressor tem-

 

 

 

perature is high, remove the overload, cool it, and

 

 

 

retest.)

 

 

 

 

Compressor cycles on

Voltage

Check the voltage.

overload.

 

If not within limits, call an electrician.

 

 

 

 

 

 

Overload

Check overload, if externally mounted.

 

 

 

Replace if open. (If the compressor temperature is

 

 

 

high, remove the overload, cool, and retest.)

 

 

 

 

Compressor cycles on

Fan motor

If not running, determine the cause. Replace if

overload.

 

required.

 

 

 

 

 

 

Condenser air flow restric-

Remove the cabinet. inspect the interior surface of

 

 

tion

the condenser; if restricted, clean carefully with a

 

 

 

vacuum cleaner (do not damage fins) or brush.

 

 

 

Clean the interior base before reassembling.

 

 

 

 

 

 

Condenser fins (damaged)

If condenser fins are closed over a large area on

 

 

 

the coil surface, head pressures will increase,

 

 

 

causing the compressor to overload. Straighten

 

 

 

the fins or replace the coil.

 

 

 

Compressor cycles on

Capacitor

Test capacitor.

overload.

Wiring

Check the terminals. If loose, repair or replace.

 

 

 

 

 

 

Refrigerating system

Check the system for a restriction.

 

 

 

Insufficient cooling or heat-

Air filter

If restricted, clean of replace.

ing

 

 

Exhaust damper door

Close if open.

 

 

 

 

 

 

 

 

Unit undersized

Determine if the unit is properly sized for the area

 

 

 

to be cooled.

 

 

 

Excessive noise

Turbo or fan

Check the set screw or clamp. If loose or missing,

 

 

 

correct. If the turbo or fan is hitting air guide,

 

 

 

rearrange the air handling parts.

 

 

 

 

 

 

Copper tubing

Remove the cabinet carefully and rearrange tubing

 

 

 

not to contact cabinet, compressor, shroud, and

 

 

 

barrier.

 

 

 

 

33Room Air Conditioner

Image 33
Contents +$7&21752//5,1& Table of Contents Be sure not to do Be sure to follow the instruction Safety PrecautionsDo not modify or extend the power cord Dimensions Symbols Used in this ManualOutside Dimensions Items Models Product Specifications760/1,850 Installation Check InstallationHow to Secure the Drain Pipe Select the Best LocationWindow Requirements Installation Kits ContentsPreparation of Chassis Suggested Tool RequirementsCabinet Installation Installation Operation FeaturesControl Locations Function of Controls Cooling Only ModelRAD-183A, RAD-243A Display Remote ControlMechanical Parts DisassemblyFront Grille CabinetCover at the top BlowerFan Shroud Electrical PartsMotor CompressorCapacitor Power CordThermistor Synchronous MotorRefrigerating Cycle EvaporatorCapillary Tube Disassembly Pulling Vacuum CN-TH1 DiagramModel RAD-183A and RAD-243A Wiring DiagramComponents Location Main P.W.B Assembly Display P.W.B AssemblyPiping System Troubleshooting GuideUnit runs but poor cooling Troubleshooting GuideFails to Start Possible Trouble Electrical Parts Troubleshooting GuideIC01M 0V? IC01M DC 5V? Delay? IC01M 0V? Possible Trouble 6 Remote controller does not operate Complaint Cause Remedy Room Air Conditioner Voltage LimitsTroubleshooting Guide Troubleshooting Guide Cooling Model Exploded ViewRemark Grille ASSY,FrontSINGLE Replacement Parts List LocNoGrille ASSY,INLET 35211A+$7&21752//5,1&

RAD-183A, RAD-243A specifications

The Heat Controller RAD-183A and RAD-243A are advanced heating solutions designed for optimal climate control and energy efficiency. These models cater to both residential and commercial spaces, providing reliable heating with user-friendly features and innovative technologies.

One of the standout features of the RAD series is its exceptional heating capacity. The RAD-183A has the capability to heat spaces up to 1,800 square feet, making it ideal for medium-sized rooms, while the RAD-243A can effectively service larger areas, catering to spaces of up to 2,400 square feet. This capacity ensures that users can maintain a comfortable environment regardless of external weather conditions.

Both models are equipped with smart heating technology that adjusts the output based on the room's temperature. The thermostat embedded in the RAD-183A and RAD-243A allows for precise temperature control, ensuring that the desired warmth is maintained without unnecessary energy consumption. This means users can rely on their heating system to provide a cozy atmosphere while saving on energy bills.

Energy efficiency is at the forefront of the design for both models. They are engineered to comply with rigorous energy consumption regulations, helping to reduce carbon footprints and lower operating costs. Their high efficiency ratings reflect their capability to deliver maximum heat output while utilizing minimal electricity. This makes them an environmentally friendly choice for conscientious consumers.

Another key characteristic of the RAD-183A and RAD-243A is their user-friendly interface. Both units feature easy-to-read displays and intuitive controls, allowing users to adjust settings effortlessly. With programmable features, homeowners can set schedules to align with their daily routines, further optimizing energy use while ensuring comfort.

Safety is also a paramount consideration in the design of these models. Equipped with multiple safety features, including overheat protection and tip-over switches, users can have peace of mind knowing that their heater operates safely and reliably.

In summary, the Heat Controller RAD-183A and RAD-243A stand out in the market due to their efficient heating capabilities, smart technology, energy efficiency, and user-centric design. With these models, individuals can experience warmth and comfort in their spaces while being mindful of energy consumption and safety.