Haier AD842AHEAA, AU84NATEAA operation manual Outdoor Unit Connection of refrigerant pipe Warning

Page 22

Installation Precedure

Outdoor Unit

4.Connection of refrigerant pipe Warning

During installation, if refrigerant leakage occurs, ventilation measures must be taken. When refrigerant meets with fire, hazadous gas will be produced.

After installation, make sure that there is no refrigerant leakage. Refrigerant, if meeting with heaters and stoves, ect. in the room, may produce hazardous gas.

Connection of refrigerant pipe

(1)The joints of the refrigerant pipe are inside the unit. Take off the access hole cover in front of the unit.

(2)The pipe can be connected from the front or bottom of the outdoor unit. (3)Remove the L-shaped pipe from the valve by welding and connect the

accessory pipe to the valve.

(4)In the case of front connection, cut the accessory pipe at the height of the fixing panel. Then join the pipe with an elbow and let it go through the fixing panel. For the convenience of maintenance, bend the pipe down (once) and then connect pipe to the right or left.

(5)In the case of bottom connection, join the pipe with accessory pipe through the holes in the base plate of the outdoor unit, and connect pipe the left or right or the back.

 

 

 

 

 

 

 

Tube fixing

 

 

 

 

 

 

 

 

 

 

 

panel

 

 

M6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M4

 

 

 

 

Base plate

 

 

 

 

 

 

Access hole cover

Tube

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

to

 

 

 

 

 

 

 

 

 

 

 

 

the

back

 

 

the

tight

 

 

 

 

 

 

 

 

 

to

 

 

 

 

 

 

 

 

Tube

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

tight

 

 

 

 

 

 

 

 

 

 

to

the

 

 

 

 

 

 

 

 

 

Tube

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

left

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the

 

 

 

 

 

 

the

left

 

 

to

 

 

 

 

 

 

to

Tube

 

 

 

 

 

Tube

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(6)During welding, the gas pipe valve must be cooled down with a wet cotton cloth.

(7)The maximum connnection pipe is 50 meters, the maximum drop difference between indoor unit and outdoor unit is 30 meters.

(8)It should install the liquid check-ring and accumulator according to the outdoor unit and indoor unit position.(see the following figures)

Fig.1 Outdoor unit below the indoor unit.

Fig. 2 Outdoor unit is above the indoor unit

Liquid check-ring

indoor unit

outdoor unit

outdoor unit

Accumulator ( a set per 6 meters)

indoor unit

During welding of the distribution pipe

(1).In case of brazing weld of joint, nitrogen must be filled in the pipe to prevent oxidization.

(2).The refrigerant pipe should be newly-made and clean. During installation, do not let water and other substance into the pipe.

(3).Use two spanners to tighten the connecting nut. One spanner will make loose connection.

(4).The torque moment should conform to the specified value. (Refer to the below) Torque moment for tightening the nut

Tube diameter (mm)

Torque moment for

Torque moment for

pre-installation (N.m)

tightening up (N.m)

 

 

 

 

 

12.70

49.0(5.0kgf.m)

53.9(5.5kgf.m)

5. Outdoor unit pipelines connection

According to the pipeline connection method, connect the distribute pipes and inlet & outlet liquid pipes.

21

Image 22
Contents Duct Type AIR Conditioner Contents Disposal of the old air conditioner Safety Instructions and WarningsDisposal of the packaging of your new air conditioner Safety Precautions Shock Machine is adaptive in following situation Indoor Unit Parts and FunctionsOutdoor Unit HOT Keep function Heating ModeWarming Operation Care and Maintenance Cooling or heating is not sufficient TroubleshootingCooling Is not sufficient Shuru Followings are not malfunctionShows resumable fault, shows it is not resumable fault Diagnosis for On-Off modelsPrecaution for Installation Safety precautionsFor inspection and maintenance Is the Unit Installed CorrectlyWhen you change your address or the installation place Electric workInstallation Precedure Height of ceilingInstalling indoor unit Indoor Unit Preparation before installationAdjusting to the levelness Indoor Unit Drain Piping ProceduresDrainage Test Indoor Unit Installation of air suction and discharging duct Chosen chart of simple duct Note1Pa/m=0.1mmAg/mExamples of improper installation Refrigerant pipeInstalltion space Outdoor Unit Selecting the installation place WarningDimension of outdoor unit Delivery of outdoor unitOutdoor Unit Mounting outdoor unit During welding of the distribution pipe Outdoor Unit Connection of refrigerant pipe WarningConnection of refrigerant pipe Outdoor unit pipelines connectionCheck if the pressure decrease Outdoor Unit Leak TestCheck for leakage Outdoor Unit Pipe Vacuumizing Indoor unit Outdoor unitRefill refrigerant Outdoor Unit Refrigerant chargeCalculation of the the refrigerant charge Open all valvesSelection of size of power supply and interconnecting wires Electrical WiringPrecautions for Electrical wiring Wiring connectionPage Haier Group

AU84NATEAA, AD842AHEAA specifications

The Haier AD842AHEAA and AU84NATEAA are two innovative air conditioning models designed to enhance indoor comfort while optimizing energy efficiency. These units are well-regarded for their advanced technologies and user-friendly features, making them ideal choices for both residential and light commercial applications.

One of the standout features of the Haier AD842AHEAA is its Inverter Technology. This technology allows the compressor to adjust its speed according to the cooling demand, resulting in significant energy savings compared to traditional air conditioning systems. It ensures a more stable temperature and reduces noise levels, providing a peaceful environment.

The AU84NATEAA, on the other hand, showcases Haier's commitment to smart comfort solutions with its integrated Wi-Fi capabilities. Users can control the unit remotely via a smartphone app, enabling them to adjust settings, monitor energy usage, and receive maintenance alerts, contributing to a smarter and more convenient lifestyle.

Both models come equipped with an intelligent air flow system. This technology helps in distributing cool air evenly throughout the room, ensuring that no spot is left untouched. The air distribution design minimizes hot or cold pockets, promoting overall comfort and satisfaction for users.

Additionally, both units feature an energy-efficient design that is compliant with international energy standards. They utilize eco-friendly refrigerants, which not only help in reducing the carbon footprint but also provide reliable cooling performance without compromising environmental safety.

The Haier AD842AHEAA and AU84NATEAA are designed for easy installation and maintenance, boasting a streamlined user interface and accessible components for service. This focus on practicality and ease of use extends to their sleek and modern aesthetic, allowing them to blend seamlessly into any interior décor while functioning efficiently.

In summary, the Haier AD842AHEAA and AU84NATEAA air conditioning units represent a harmonious blend of advanced technology, comfort, and energy efficiency. With features like Inverter Technology, smart home integration, intelligent airflow, and eco-friendly refrigerants, these models stand out in the competitive air conditioning market, offering consumers modern solutions to their cooling needs. Whether for home use or in small business environments, these units provide a reliable and effective way to maintain ideal indoor conditions.