Haier HC18-60C1VAR, HC18-60D1VAR, HC18-60A1VAR/S operation manual Line Insulation, Outdoor Unit

Page 9

OUTDOOR UNIT

OUTDOOR UNIT

PITCH SUCTION LINE TOWARD OUTDOOR UNIT 1/2" FRO EVERY 10' OF LINE

INDOOR UNIT ABOVE OR

LEVEL TO OUTDOOR UNIT

70'

MAX. LIQUID LINE SUCTION LINE OIL TRAP WHEN INDOOR

ADDITIONAL SUCTION LINE OIL TRAP FOR EACH 20 FOOT RISE OF PIPE

INDOOR UNIT

INVERTED LOOP LIQUID LINE

LIQUID LINE

A

INDOOR UNIT

6'

UNIT IS 4 FEET OR

M O R E B E L O W

OUTDOOR UNIT

INDOOR UNIT BELOW OUTDOOR UNIT

B-1

OUTDOOR UNIT

INDOOR UNIT

50'

MAX.

SUCTION LINE

B-2Figure 3

Only refrigeration-grade copper piping (dehydrated and sealed) should be used. Take extreme care to keep the refrigerant tubing clean and dry prior to and during installation. If in doubt, blow out the tubing with dry nitrogen to remove any chips or debris before connection. Always keep tubing sealed until it is in place and the connections are to be made.

Refrigerant piping should be as short as possible, with a minimum of elbows or bends, to avoid capacity loss and increased operating costs.

Refrigerant lines must be adequately supported. If metal strapping is used to secure the tubing, do not allow the strapping to directly contact the tubing. Use a closed cell insulation to separate the strapping from the tubing.

Do not kink or twist the tubing.

Refrigerant piping should not be installed in a cement slab, as this limits access to the refrigerant should a leak be suspected.

To ensure good oil return to the compressor, it is important to pitch the horizontal suction line toward the compressor, approximately 1/2" for every 10' of line.

Line Insulation

Suction line requires insulation in order to prevent condensation from forming on the piping and to prevent heat gain caused by surrounding air. Generally 3/8" wall thickness of Armflex or equivalent is satisfactory. In severe application (hot, high humidity areas) greater thickness may be required. Apply the line insulation by sliding it on the sealed tuing before cutting and making connections.

Liquid line does not necessarily need insulation, however, if they are exposed to high ambient temperatures (i.e. kitchen, boiler rooms, hot attics & rooftop surface), then, they should be insulated. Make sure to use the proper size tubing for the liquid line to prevent liquid refrigerant flashing to a vapor within the liquid line.

Do not allow the vapor line and liquid line to touch together. This would cause an undesirable heat transfer resulting in capacity loss and increased power consumption.

7

Image 9
Contents HC18-60C1VAR HC18-60D1VAR Message to Owner Nomenclature for Model Number IntroductionModel SpecificationSeer System Cooling CapacityModelHC18-60D1VAR Installation Unit InspectionEquipment Protection from Environment Unit Clearances Outdoor Unit Line InsulationRefrigerant Line Length Ft Unit Size Ton Refrigerant Line SizingVertical Separation between Indoor and Outdoor Units Tubing ConnectionsCharging the System EvacuationElectrical Wiring See unit wiring diagram furnished with this instructionSystem charging table by superheat System Startup Copper Wire Size AWGTroubleshooting Guide Replacement PartsWiring Diagram OperationSymptom Possible Cause Remedy Air Conditioner Wi ring Diagram Made in P.R.C

HC18-60A1VAR/S, HC18-60D1VAR, HC18-60C1VAR specifications

Haier, a recognized brand in the home appliance sector, has consistently focused on delivering innovative and reliable products to enhance consumer convenience. Among their impressive offerings are the Haier HC18-60C1VAR, HC18-60A1VAR/S, and HC18-60D1VAR, which are compact and versatile refrigeration solutions designed to meet diverse storage needs.

The Haier HC18-60C1VAR is known for its impressive capacity and energy efficiency. With a total storage capacity that effectively accommodates a variety of food items, it is perfect for small kitchens, apartments, or dormitories. The unit features a user-friendly design that includes adjustable shelves, ensuring that users can customize the internal space according to their storage requirements. The efficient cooling technology employed in this model ensures that food remains fresh for longer periods while minimizing energy consumption.

Similarly, the HC18-60A1VAR/S model stands out with its sleek finish and modern aesthetics. This model integrates advanced cooling technology that enhances temperature stability, preventing food spoilage. The inclusion of a reversible door offers added convenience, allowing users to adapt the refrigerator to their specific kitchen layout. Additional features such as an adjustable thermostat and LED lighting make it easier for users to monitor and manage their food storage effectively.

On the other hand, the HC18-60D1VAR model is specifically designed for versatility and performance. This refrigerator model is equipped with a separate freezer compartment, providing users with the ability to store frozen foods efficiently. The frost-free technology is another highlight, as it eliminates the need for manual defrosting, a common issue with traditional refrigerators. This feature not only saves time but also ensures that the freezer maintains optimal performance.

All three models share common characteristics such as quiet operation, making them ideal for residential or office environments. They are designed with environmentally friendly refrigerants, ensuring compliance with modern sustainability standards. The easy-to-clean interiors and exterior surfaces also facilitate maintenance, adding to their user-friendly appeal.

In summary, the Haier HC18-60C1VAR, HC18-60A1VAR/S, and HC18-60D1VAR are exemplary compact refrigerators that blend performance, efficiency, and design. With features like adjustable shelving, energy efficiency, and user-friendly technologies, these models cater to the needs of modern consumers looking for reliable refrigeration solutions. Whether for small homes, offices, or student housing, Haier has a model that fits seamlessly into any lifestyle.