Goodman Mfg GPC 14 SEER R-410 Package Air Conditioners with R-410A, RS6300011 service manual

Page 13

PACKAGE COOLING SPECIFICATIONS GPC14[48-60]H41AA

 

 

GPC1448H41*

GPC1460H41*

 

 

 

 

COOLING

COOLING CAPACITY, BTUH

46,500

57,500

CAPACITY

SEER / EER

14.5 / 12.0

14.5 / 12.0

 

 

 

 

UNIT

VOLTAGE (NAMEPLATE)

208-230/1/60

208-230/1/60

ELECTRICAL

AMPS (TOTAL)

24.2

30.7

SPECIFICATION

MINIMUM CIRCUIT AMPACITY

29.1

37.3

 

MAXIMUM OVERCURRENT PROTECTION (1)

45

60

COMPRESSOR

TYPE

SCROLL

SCROLL

 

RATED LOAD AMPS

19.9

26.4

 

LOCKED ROTOR AMPS

109

134

 

 

 

 

CONDENSER

HORSEPOWER

1/4

1/4

FAN MOTOR

RPM

1075

1075

 

FULL LOAD AMPS

1.4

1.4

 

LOCKED ROTOR AMPS

2.9

2.9

 

 

 

 

CONDENSER FAN

BLADE DIAMETER (INCHES) / # OF BLADES

22 / 4

22 / 4

CONDENSER

FACE AREA - SQ. FT.

19.1

19.1

COIL

NUMBER OF ROWS

1

2

 

FINS PER INCH

21

16

 

 

 

 

EVAPORATOR

HORSEPOWER - NO. OF SPEEDS

3/4 - 5

3/4 - 5

BLOWER

FULL LOAD AMPS

2.9

2.9

MOTOR

LOCKED ROTOR AMPS

NA

NA

 

MOTOR SPEED TAP - COOLING

T2

T2

 

RPM

1050

1050

 

 

 

 

EVAPORATOR

DIAMETER X WIDTH (INCHES)

10 x 8

11 x 8

BLOWER

HI EFFICIENCY COOLING CFM

1,600

1,600

 

5 TON NOMINAL COOLING CFM

NA

1,800

 

FAN ONLY COOLING CFM

1,400

1,600

 

MAX EXTERNAL STATIC PRESS ("w.c.)

0.5

0.5

EVAPORATOR

FACE AREA - SQ. FT.

6.2

7.0

COIL

NUMBER OF ROWS

4

4

 

FINS PER INCH

14

14

 

 

 

 

GENERAL

FILTER SIZE - SQ. FT. *

(2) 20 x 20 x 1

(2) 20 x 25 x 1

INFORMATION

DRAIN SIZE (INCHES)

3/4"

3/4"

 

EXPANSION DEVICE

ORIFICE (0.076)

ORIFICE (0.088)

 

REFRIGERANT CHARGE R-410A (Oz.)

123

188

 

POWER SUPPLY CONDUIT KNOCKOUT SIZE (IN.)

3/4, 1, 1-1/4

3/4, 1, 1-1/4

 

LOW VOLTAGE CONDUIT KNOCKOUT SIZE (IN.)

1/2

1/2

 

SHIPPING WEIGHT LBS.

400

400

 

OPERATING WEIGHT LBS.

390

390

 

 

 

 

(1)Maximum Overcurrent Protection Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted. * Calculated external filter size based on air velocity of 300 ft/min.

Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.

Unit specifications are subject to change without notice. ALWAYS refer to the units serial plate for the most up-to-date general and electrical information.

IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters.

13

Image 13
Contents TECHNICAL MANUAL GPC 14 SEER R-410A Package Air Conditioners with R-410APRODUCT IDENTIFICATION CONFIGURATIONHIGH VOLTAGE VOLTAGEGPC1436H41AA GPC1436H41AB GPC1442H41AA GPC1442H41AB GPC1424H41AA GPC1424H41AB GPC1430H41AA GPC1430H41ABGPC1448H41AA GPC1448H41AB GPC1460H41AA AB model specific 5 mm information begins on pagePRODUCT DESIGN Outside Slab Installation - Horizontal HLocation and Clearances Rooftop Installation - Horizontal H GPC1424-60H41A PRODUCT DIMENSIONSChassis ModelGPC1424-60H41A HKR ELECTRICAL DATAPart Number ACCESSORIESGPC1424-60H41ADescription Dry Coil Data BLOWER PERFORMANCE DATABLOWER PERFORMANCE DATAPACKAGE COOLING SPECIFICATIONS GPC1424-30H41AA GPC1436-42H41AA PACKAGE COOLING SPECIFICATIONSPACKAGE COOLING SPECIFICATIONS GPC1448-60H41AA EXPANDED PERFORMANCE DATA COOLING PERFORMANCE DATA GPC1424H41AAMODEL GPC1424H41A COOLING OPERATIONEntering Indoor Wet EXPANDED PERFORMANCE DATAMODEL GPC1430H41A COOLING PERFORMANCE DATA GPC1430H41AAAirflow EXPANDED PERFORMANCE DATA MODEL GPC1436H41A COOLING PERFORMANCE DATA GPC1436H41AAShaded areas MODEL GPC1442H41A COOLING PERFORMANCE DATA GPC1442H41AAOutdoor Ambient Temperature EXPANDED PERFORMANCE DATA MODEL GPC1448H41A COOLING PERFORMANCE DATA GPC1448H41AAEXPANDED PERFORMANCE DATA MODEL GPC1460H41A COOLING PERFORMANCE DATA GPC1460H41AAEXPANDED PERFORMANCE DATA PERFORMANCE TEST COOLING PERFORMANCE DATAGPC1424-60H41AA WIRING DIAGRAMSGPC1424H41AB GPC1442H41AB GPC1430H41AB GPC1448H41AB GPC1436H41AB GPC 14 SEER R-410A 5mm Package Air ConditionersPL ATFO RM UNI T PL ENUMMODELS WITH 5MM COILS PACKAGE COOLING SPECIFICATIONS GPC1424-30H41ABPACKAGE COOLING SPECIFICATIONS GPC1436-48H41AB COOLING PERFORMANCE DATA 5MM COILS GPC1424H41AB 24.6 Bulb Temperature0.74 1.90COOLING PERFORMANCE DATA 5MM COILS GPC1430H41AB 2.26 28.410.2 COOLING PERFORMANCE DATA 5MM COILS GPC1436H41AB EXPANDED PERFORMANCE DATA COOLING PERFORMANCE DATA 5MM COILS GPC1442H41AB EXPANDED PERFORMANCE DATA MODEL GPC1448H41AB COOLING PERFORMANCE DATA 5MM COILS GPC1448H41AB0.75 47.13.25 17.1PERFORMANCE TEST GPC1424-48H41AB 5MM COILSHIGH WARNING UNIT. DO