PACKAGE COOLING SPECIFICATIONS GPC14[36-48]H41AB
MODELS WITH 5MM COILS
|
| GPC1436H41AB | GPC1442H41AB | GPC1448H41AB |
|
|
|
|
|
COOLING | COOLING CAPACITY, BTUH | 35,600 | 40,000 | 46,500 |
CAPACITY | SEER / EER | 14.0 / 12.0 | 14.2 / 12.0 | 14.5 / 12.0 |
UNIT | VOLTAGE (NAMEPLATE) | |||
ELECTRICAL | AMPS (TOTAL) | 20.06 | 22.2 | 24.2 |
SPECIFICATION | MINIMUM CIRCUIT AMPACITY | 24.2 | 26.6 | 29.1 |
| MAXIMUM OVERCURRENT PROTECTION (1) | 40 | 40 | 45 |
COMPRESSOR | TYPE | SCROLL | SCROLL | SCROLL |
| RATED LOAD AMPS | 16.7 | 17.9 | 19.9 |
| LOCKED ROTOR AMPS | 79 | 112 | 109 |
|
|
|
|
|
CONDENSER | HORSEPOWER | 1/4 | 1/4 | 1/4 |
FAN MOTOR | RPM | 830 | 1075 | 1075 |
| FULL LOAD AMPS | 1.5 | 1.4 | 1.4 |
| LOCKED ROTOR AMPS | 3.0 | 2.9 | 2.9 |
|
|
|
|
|
CONDENSER FAN | BLADE DIAMETER (INCHES) / # OF BLADES | 22 / 3 | 22 / 4 | 22 / 4 |
CONDENSER | FACE AREA - SQ. FT. | 12.3 | 16.0 | 19.5 |
COIL | NUMBER OF ROWS | 1 | 1 | 1 |
| FINS PER INCH | 26 | 28 | 28 |
|
|
|
|
|
EVAPORATOR | HORSEPOWER - NO. OF SPEEDS | 1/2 - 5 | 1/2 - 5 | 3/4 - 5 |
BLOWER | FULL LOAD AMPS | 1.86 | 2.9 | 2.9 |
MOTOR | LOCKED ROTOR AMPS | NA | NA | NA |
| MOTOR SPEED TAP - COOLING | T2 | T2 | T2 |
| RPM | 1050 | 1050 | 1050 |
|
|
|
|
|
EVAPORATOR | DIAMETER X WIDTH (INCHES) | 10 X 8 | 10 x 8 | 10 x 8 |
BLOWER | HI EFFICIENCY COOLING CFM | 1,200 | 1,300 | 1,600 |
| 5 TON NOMINAL COOLING CFM | NA | NA | NA |
| FAN ONLY COOLING CFM | 1,100 | 1,200 | 1,400 |
| MAX EXTERNAL STATIC PRESS ("w.c.) | 0.5 | 0.5 | 0.5 |
EVAPORATOR | FACE AREA - SQ. FT. | 5.2 | 6.2 | 6.2 |
COIL | NUMBER OF ROWS | 3 | 4 | 4 |
| FINS PER INCH | 14 | 14 | 14 |
|
|
|
|
|
GENERAL | FILTER SIZE - SQ. FT. * | 25 x 25 x 1 | (2) 20 x 20 x 1 | (2) 20 x 20 x 1 |
INFORMATION | DRAIN SIZE (INCHES) | 3/4" | 3/4" | 3/4" |
| EXPANSION DEVICE | ORIFICE (0.068) | ORIFICE (0.072) | ORIFICE (0.078) |
| REFRIGERANT CHARGE | 65 | 94 | 90 |
| POWER SUPPLY CONDUIT KNOCKOUT SIZE (IN.) | 3/4, 1, | 3/4, 1, | 3/4, 1, |
| LOW VOLTAGE CONDUIT KNOCKOUT SIZE (IN.) | 1/2 | 1/2 | 1/2 |
| SHIPPING WEIGHT LBS. | 370 | 370 | 400 |
| OPERATING WEIGHT LBS. | 360 | 360 | 390 |
|
|
|
|
|
(1)Maximum Overcurrent Protection Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted. * Calculated external filter size based on air velocity of 300 ft/min.
Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
Unit specifications are subject to change without notice. ALWAYS refer to the units serial plate for the most
IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters.
31