ESPECIFICACIONES DEL PRODUCTO
DATOS DE CAPACIDAD DE ENFRIAMIENTO
Nota: Las capacidades sensibles y totales son brutas y no tienen en cuenta el calor del motor. Remítase a la página 10 para mayor infor- mación sobre el calor del motor.
TABLA 1A: PGB090210-5 (UNIDADES SI)
Aire de |
|
|
|
|
| Temperatura del Aire del Condensador |
|
|
|
|
| ||||||
Interior |
| 23.9°C |
|
| 29.4°C |
|
| 35.0°C |
|
| 40.6°C |
|
| 46.1°C |
| ||
L/S | WB | Cap. | Cap. | kW | Cap. | Cap. | kW | Cap. | Cap. | kW | Cap. | Cap. | kW | Cap. | Cap. | kW | |
Total | Sens. | Total | Sens. | Total | Sens. | Total | Sens. | Total | Sens. | ||||||||
|
|
|
|
|
|
| |||||||||||
| 22.2 | 32.77 | 15.48 | 8.36 | 30.67 | 14.52 | 9.29 | 28.56 | 13.56 | 10.23 | 26.46 | 12.60 | 11.17 | 24.35 | 11.64 | 12.10 | |
1203 | 19.4 | 30.23 | 18.70 | 7.82 | 28.17 | 17.90 | 8.73 | 26.11 | 17.10 | 9.64 | 24.05 | 16.31 | 10.55 | 21.99 | 15.51 | 11.46 | |
16.7 | 27.52 | 23.00 | 7.46 | 26.07 | 21.73 | 8.30 | 24.62 | 20.45 | 9.14 | 23.17 | 19.18 | 9.98 | 21.72 | 17.91 | 10.82 | ||
| |||||||||||||||||
| 13.9 | 26.59 | 24.96 | 7.18 | 24.98 | 23.20 | 8.06 | 23.38 | 21.43 | 8.94 | 21.77 | 19.67 | 9.83 | 20.17 | 17.91 | 10.71 | |
| 22.2 | 34.17 | 17.16 | 8.63 | 31.91 | 16.15 | 9.58 | 29.65 | 15.14 | 10.53 | 27.39 | 14.14 | 11.48 | 25.13 | 13.13 | 12.43 | |
1416 | 19.4 | 31.36 | 21.95 | 8.08 | 29.28 | 20.81 | 9.01 | 27.20 | 19.66 | 9.93 | 25.12 | 18.52 | 10.86 | 23.03 | 17.38 | 11.78 | |
16.7 | 28.62 | 26.83 | 7.53 | 26.96 | 25.02 | 8.49 | 25.30 | 23.20 | 9.44 | 23.65 | 21.39 | 10.40 | 21.99 | 19.58 | 11.35 | ||
| |||||||||||||||||
| 13.9 | 28.62 | 26.83 | 7.53 | 26.96 | 25.02 | 8.49 | 25.30 | 23.20 | 9.44 | 23.65 | 21.39 | 10.40 | 21.99 | 19.58 | 11.35 | |
| 22.2 | 35.01 | 18.42 | 8.82 | 32.73 | 17.46 | 9.77 | 30.46 | 16.50 | 10.73 | 28.18 | 15.54 | 11.69 | 25.90 | 14.59 | 12.64 | |
1628 | 19.4 | 32.19 | 24.67 | 8.28 | 30.10 | 23.35 | 9.21 | 28.00 | 22.04 | 10.14 | 25.91 | 20.72 | 11.07 | 23.81 | 19.40 | 11.99 | |
16.7 | 30.24 | 28.49 | 7.89 | 28.44 | 26.54 | 8.86 | 26.64 | 24.60 | 9.84 | 24.84 | 22.65 | 10.81 | 23.03 | 20.71 | 11.78 | ||
| |||||||||||||||||
| 13.9 | 30.24 | 28.49 | 7.89 | 28.44 | 26.54 | 8.86 | 26.64 | 24.60 | 9.84 | 24.84 | 22.65 | 10.81 | 23.03 | 20.71 | 11.78 |
Las capacidades de calefacción sensible indicadas se basan en aire entrante a 26,7ºC con bulbo seco en el serpentín evaporador. Para otras capacidades de calefacción sensible, restar 44,32 W cada 47 L/S de aire en el serpentín evaporador por cada grado por debajo de los 26,7ºC o sumar 44,32 W cada 47 L/S de aire en el evaporador por encima de la temperatura mencionada.
TABLA 1B: PGB090210-5 (UNIDADES INGLESAS)
Aire de |
|
|
|
|
| Temperatura del Aire del Condensador |
|
|
|
|
| ||||||
Interior |
| 75°F |
|
| 85°F |
|
| 95°F |
|
| 105°F |
|
| 115°F |
| ||
SCFM | WB | Total | Sens | kW | Total | Sens | kW | Total | Sens | kW | Total | Sens | kW | Total | Sens | kW | |
KBTU/h | KBTU/h | KBTU/h | KBTU/h | KBTU/h | KBTU/h | KBTU/h | KBTU/h | KBTU/h | KBTU/h | ||||||||
|
|
|
|
|
|
| |||||||||||
| 72 | 111.8 | 52.8 | 8.36 | 104.6 | 49.6 | 9.29 | 97.5 | 46.3 | 10.23 | 90.3 | 43.0 | 11.17 | 83.1 | 39.7 | 12.10 | |
2550 | 67 | 103.2 | 63.8 | 7.82 | 96.1 | 61.1 | 8.73 | 89.1 | 58.4 | 9.64 | 82.1 | 55.6 | 10.55 | 75.0 | 52.9 | 11.46 | |
62 | 93.9 | 78.5 | 7.46 | 89.0 | 74.1 | 8.30 | 84.0 | 69.8 | 9.14 | 79.1 | 65.5 | 9.98 | 74.1 | 61.1 | 10.82 | ||
| |||||||||||||||||
| 57 | 90.7 | 85.2 | 7.18 | 85.2 | 79.1 | 8.06 | 79.8 | 73.1 | 8.94 | 74.3 | 67.1 | 9.83 | 68.8 | 61.1 | 10.71 | |
| 72 | 116.6 | 58.5 | 8.63 | 108.9 | 55.1 | 9.58 | 101.2 | 51.7 | 10.53 | 93.5 | 48.2 | 11.48 | 85.7 | 44.8 | 12.43 | |
3000 | 67 | 107.0 | 74.9 | 8.08 | 99.9 | 71.0 | 9.01 | 92.8 | 67.1 | 9.93 | 85.7 | 63.2 | 10.86 | 78.6 | 59.3 | 11.78 | |
62 | 97.6 | 91.6 | 7.53 | 92.0 | 85.4 | 8.49 | 86.3 | 79.2 | 9.44 | 80.7 | 73.0 | 10.40 | 75.0 | 66.8 | 11.35 | ||
| |||||||||||||||||
| 57 | 97.6 | 91.6 | 7.53 | 92.0 | 85.4 | 8.49 | 86.3 | 79.2 | 9.44 | 80.7 | 73.0 | 10.40 | 75.0 | 66.8 | 11.35 | |
| 72 | 119.5 | 62.9 | 8.82 | 111.7 | 59.6 | 9.77 | 103.9 | 56.3 | 10.73 | 96.2 | 53.0 | 11.69 | 88.4 | 49.8 | 12.64 | |
3450 | 67 | 109.9 | 84.2 | 8.28 | 102.7 | 79.7 | 9.21 | 95.6 | 75.2 | 10.14 | 88.4 | 70.7 | 11.07 | 81.3 | 66.2 | 11.99 | |
62 | 103.2 | 97.2 | 7.89 | 97.0 | 90.6 | 8.86 | 90.9 | 83.9 | 9.84 | 84.7 | 77.3 | 10.81 | 78.6 | 70.7 | 11.78 | ||
| |||||||||||||||||
| 57 | 103.2 | 97.2 | 7.89 | 97.0 | 90.6 | 8.86 | 90.9 | 83.9 | 9.84 | 84.7 | 77.3 | 10.81 | 78.6 | 70.7 | 11.78 |
Las capacidades de calefacción sensible indicadas se basan en aire entrante a 80ºF con bulbo seco en el serpentín evaporador. Para otras capacidades de calefacción sensible, restar 84 BTU/H cada 100 CFM de aire en el serpentín evaporador por cada grado por debajo de 80ºF ó sumar 84 BTU/h cada 100 CFM de aire en el evaporador por encima de 80ºF.
TABLA 2A: PGB120245-5 (UNIDADES SI)
Aire de |
|
|
|
|
| Temperatura del Aire del Condensador |
|
|
|
|
| ||||||
Interior |
| 23.9°C |
|
| 29.4°C |
|
| 35.0°C |
|
| 40.6°C |
|
| 46.1°C |
| ||
L/S | WB | Cap. | Cap. | kW | Cap. | Cap. | kW | Cap. | Cap. | kW | Cap. | Cap. | kW | Cap. | Cap. | kW | |
Total | Sens | Total | Sens | Total | Sens | Total | Sens | Total | Sens | ||||||||
|
|
|
|
|
|
| |||||||||||
| 22.2 | 43.67 | 21.02 | 9.95 | 41.04 | 19.52 | 11.27 | 38.41 | 18.03 | 12.59 | 35.78 | 16.54 | 13.91 | 33.15 | 15.04 | 15.23 | |
1605 | 19.4 | 40.29 | 25.44 | 9.31 | 37.70 | 24.09 | 10.59 | 35.11 | 22.74 | 11.86 | 32.52 | 21.38 | 13.14 | 29.93 | 20.03 | 14.41 | |
16.7 | 36.65 | 31.24 | 8.89 | 34.88 | 29.22 | 10.07 | 33.11 | 27.19 | 11.25 | 31.34 | 25.17 | 12.43 | 29.57 | 23.14 | 13.61 | ||
| |||||||||||||||||
| 13.9 | 35.42 | 33.85 | 8.54 | 33.43 | 31.17 | 9.78 | 31.44 | 28.49 | 11.01 | 29.45 | 25.82 | 12.24 | 27.45 | 23.14 | 13.47 | |
| 22.2 | 45.54 | 23.30 | 10.28 | 42.71 | 21.72 | 11.62 | 39.87 | 20.13 | 12.96 | 37.04 | 18.55 | 14.30 | 34.20 | 16.96 | 15.64 | |
1888 | 19.4 | 41.79 | 29.83 | 9.62 | 39.18 | 27.99 | 10.92 | 36.57 | 26.14 | 12.22 | 33.97 | 24.29 | 13.52 | 31.36 | 22.45 | 14.82 | |
16.7 | 38.12 | 36.41 | 8.95 | 36.07 | 33.63 | 10.29 | 34.03 | 30.85 | 11.62 | 31.98 | 28.07 | 12.95 | 29.93 | 25.29 | 14.29 | ||
| |||||||||||||||||
| 13.9 | 38.12 | 36.41 | 8.95 | 36.07 | 33.63 | 10.29 | 34.03 | 30.85 | 11.62 | 31.98 | 28.07 | 12.95 | 29.93 | 25.29 | 14.29 | |
| 22.2 | 46.65 | 25.03 | 10.50 | 43.81 | 23.49 | 11.85 | 40.96 | 21.94 | 13.20 | 38.11 | 20.39 | 14.55 | 35.26 | 18.84 | 15.90 | |
2170 | 19.4 | 42.90 | 33.53 | 9.86 | 40.28 | 31.41 | 11.17 | 37.66 | 29.29 | 12.48 | 35.04 | 27.18 | 13.78 | 32.41 | 25.06 | 15.09 | |
16.7 | 40.29 | 38.65 | 9.39 | 38.05 | 35.67 | 10.75 | 35.82 | 32.70 | 12.11 | 33.59 | 29.72 | 13.46 | 31.36 | 26.75 | 14.82 | ||
| |||||||||||||||||
| 13.9 | 40.29 | 38.65 | 9.39 | 38.05 | 35.67 | 10.75 | 35.82 | 32.70 | 12.11 | 33.59 | 29.72 | 13.46 | 31.36 | 26.75 | 14.82 |
Las capacidades de calefacción sensible indicadas se basan en aire entrante a 26,7ºC con bulbo seco en el serpentín evaporador. Para otras capacidades de calefacción sensible, restar 44,32 W cada 47 L/S de aire en el serpentín evaporador por cada grado por debajo de los 26,7ºC o sumar 44,32 W cada 47 L/S de aire en el evaporador por encima de la temperatura mencionada.