PERFORMANCE DATA

PERFORMANCE TEST

All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor air cubic feet per minute (CFM) as listed in the Performance Data Sheets:

If conditions vary from this, results will change as follows:

1.As indoor dry bulb temperatures increase, a slight increase will occur in indoor air temperature drop (Delta T). Low and high side pressures and power will not change.

2.As indoor CFM decreases, a slight increase will occur in indoor temperature drop (Delta T). A slight decrease will occur in low and high side pressures and power.

A properly operating unit should be within plus or minus 2 degrees of the subcooling value shown in the installation instructions.

A properly operating unit should be within plus or minus 3 degrees of the typical (Delta T) value shown.

A properly operating unit should be within plus or minus 10 PSIG of the HI PR shown.

A properly operating unit should be within plus or minus 5 PSIG of the LO PR shown.

A properly operating unit should be within plus or minus 3 Amps of the typical value shown.

19

Image 19
Contents Technical Manual Product Identification 036Do not connect or use any device Me asurements in inches. Desi gnates metric equi valents Product DesignDimensions CKF24 CKF36-2 CKF36-5 CKF48-5 CKF6 CKF70 Condensing Unit Specifications244 Entering Indoor Wet Bulb Temperature22.2 12.4260 Airflow24.0 12.918.9 30.6253 270 Outdoor Ambient Temperature 105 115 118F 125F33.0 19.7254 Outdoor Ambient Temperature271 105 115 118F 125F11.2 40.8246 11.6 44.0271 11.1 51.055.0 Cooling Performance Data11.5 13.6 56.5264 14.1 61.0282 Performance Test Performance DataDiagrams WiringCKF48-70M/N/P Wiring Diagrams